PANEL REF.
LPP-G-SER
FINAL BRANCH CIRCUIT PANELBOARD PANEL TYPE. MCCB
BUILDING G LOCATION ELECTRICAL ROOM - BASEMENT FLOOR
VOLTAGE & FREQ. 380/220V, 50Hz S.C. RATING (I.C.) 16 kA
Wire Phase Load In Amps Phase Load In Amps Wire
TYPE
TYPE
Load Description Size Size Load Description
mm2 R Y B R Y B R Y B mm2
LTG LIGHTING (ELEVATOR) 3x3 0.5 C1 16 16 C2 0.5 3x3 LIGHTING (ELEVATOR) LTG
1 2
LTG LIGHTING (STAIRS) 3x3 2.9 C3 16 16 C4 2.5 3x3 LIGHTING (STAIRS) LTG
3 4
LTG LIGHTING (GARBAGE & TELECOM) 3x3 2.8 16 16 5.4 3x3 LIGHTING (GARBAGE & TELECOM) LTG
5 6
LTG LIGHTING (LOBBY & CORRIDOR) 3x3 5.7 C5 16 16 C6 6.7 3x3 LIGHTING (CORRIDOR) LTG
7 8
S.O GENERAL USE SOCKET 3x4 1.6 20 20 7.4 3x4 GENERAL USE SOCKET S.O
9 10
S.O GENERAL USE SOCKET 3x4 9.8 20 16 1.3 3x3 LIGHTING (ROOF) LTG
11 12
S.O GENERAL USE SOCKET 3x4 9.8 20 20 8.2 3x4 GENERAL USE SOCKET S.O
13 14
S.O GENERAL USE SOCKET 3x4 9.8 20 20 9.0 3x4 GENERAL USE SOCKET S.O
15 16
S.O GENERAL USE SOCKET 3x4 9.8 20 20 8.2 3x4 GENERAL USE SOCKET S.O
17 18
S.O GENERAL USE SOCKET 3x4 7.4 20 20 7.4 3x4 GENERAL USE SOCKET S.O
19 20
S.O GENERAL USE SOCKET 3x4 8.2 20 20 SPARE
21 22
S.O GENERAL USE SOCKET 3x4 8.2 20 20 SPARE
23 24
SPARE 20 SPACE
25 26
SPACE SPACE
27 28
SPACE 20 SPACE
29 30
SUBTOTAL (AMPS) 23.4 22.5 30.6 22.7 18.9 14.9
22.7 18.9 14.9
32 AMPS, MCCB
TOTAL CONNECTED AMPS 46.1 41.4 45.6
S.
LIGHTING MOTORS MISC. TOTAL
TOTAL CONNECTED LOAD 29.28 KVA OUTLETS
LTG: LIGHTING, HTR:HEATER, MTR: MOTORS, MISC: MISCELLANEOUS CONN. kVA 6.24 0.00 23.04 0.00 29.28
C1,C2: ARE ACTIVATED AND DEACTIVATED ACCORDING TO TIME
SCHEDULES.
C3,C4: ARE ACTIVATED BY PUSH BOTTONS AND DEACTIVATED ACCORDING DEM.
1.00 0.70 0.50 0.80 0.61
TO TIME SCHEDULES. FACTOR
C5,C6: ARE ACTIVATED BY STAND ALONE MOTION DETECTOR AND
DEACTIVATED ACCORDING TO TIME SCHEDULES.
DEMAND Kva 6.24 0.00 11.52 0.00 17.76
*:EQUIPPED WITH RESIDUAL CURRENT DEVICES
( 30mA FOR SOCKETS & 100mA OTHERWISE )