PANEL REF.

LPP-C-SER-1

FINAL BRANCH CIRCUIT PANELBOARD PANEL TYPE. MCCB

BUILDING C LOCATION ELECTRICAL ROOM - BASEMENT FLOOR

VOLTAGE & FREQ. 380/220V, 50Hz S.C. RATING (I.C.) 16 kA

Wire Phase Load In Amps Phase Load In Amps Wire


TYPE

TYPE
Load Description Size Size Load Description
2 R Y B R Y B R Y B 2
mm mm

LTG LIGHTING (STAIRE CASE) 3x3 2.6 C1 16 16 C2 0.6 3x3 LIGHTING (ELEVATOR CORE) LTG
1 2

LTG LIGHTING (ELEVATOR CORE) 3x3 0.6 C3 16 16 C4 2.6 3x3 LIGHTING (STAIR CASE) LTG
3 4

LTG LIGHTING (TELECOM & GARBAGE) 3x3 4.4 16 16 2.0 3x3 LIGHTING (TELECOM & GARBAGE) LTG
5 6

LTG LIGHTING (CORRIDOR) 3x3 4.8 C5 16 16 C6 2.5 3x3 LIGHTING (CORRIDOR) LTG
7 8

S.O GENERAL USE SOCKET 3x4 3.3 20 20 2.5 3x4 GENERAL USE SOCKET S.O
9 10

S.O GENERAL USE SOCKET 3x4 3.3 20 20 3.3 3x4 GENERAL USE SOCKET S.O
11 12

LTG LIGHTING (ROOF) 3x3 0.9 16 20 3.3 3x4 GENERAL USE SOCKET S.O
13 14

S.O GENERAL USE SOCKET 3x4 3.3 20 20 3.3 3x4 GENERAL USE SOCKET S.O
15 16

S.O GENERAL USE SOCKET 3x4 1.6 20 20 1.6 3x4 GENERAL USE SOCKET S.O
17 18

S.O GENERAL USE SOCKET 3x4 6.5 20 16 SPARE


19 20

S.O GENERAL USE SOCKET 3x4 4.9 20 20 SPARE


21 22

S.O GENERAL USE SOCKET 3x4 3.3 20 20 4.9 3x4 GENERAL USE SOCKET S.O
23 24

SPARE 20 20 SPARE
25 26

SPACE SPACE
27 28

SPACE SPACE
29 30
SUBTOTAL (AMPS) 14.8 12.1 12.6 6.4 8.3 11.8

6.4 8.3 11.8


32 AMPS, MCCB
TOTAL CONNECTED AMPS 21.3 20.4 24.4

S.
LIGHTING MOTORS MISC. TOTAL
TOTAL CONNECTED LOAD 14.52 KVA OUTLETS

LTG: LIGHTING, HTR:HEATER, MTR: MOTORS, MISC: MISCELLANEOUS CONN. kVA 4.63 0.00 9.89 0.00 14.52

C1,C4: ARE ACTIVATED BY PUSH BUTTONS AND DEACTIVATED


ACCORDING TO TIME SCHEDULES.
C2,C3: ARE ACTIVATED AND DEACTIVATED ACCORDING TO TIME DEM.
0.90 1.00 0.60 1.00 0.70
SCHEDULES. FACTOR
C5,C6: ARE ACTIVATED BY STAND BY MOTION DETECTOR AND
DEACTIVATED ACCORDING TO TIME SCHEDULES.

DEMAND Kva 4.17 0.00 5.94 0.00 10.10


*:EQUIPPED WITH RESIDUAL CURRENT DEVICES

( 30mA FOR SOCKETS & 100mA OTHERWISE )