PANEL REF.
LPP-C-SER-1
FINAL BRANCH CIRCUIT PANELBOARD PANEL TYPE. MCCB
BUILDING C LOCATION ELECTRICAL ROOM - BASEMENT FLOOR
VOLTAGE & FREQ. 380/220V, 50Hz S.C. RATING (I.C.) 16 kA
Wire Phase Load In Amps Phase Load In Amps Wire
TYPE
TYPE
Load Description Size Size Load Description
2 R Y B R Y B R Y B 2
mm mm
LTG LIGHTING (STAIRE CASE) 3x3 2.6 C1 16 16 C2 0.6 3x3 LIGHTING (ELEVATOR CORE) LTG
1 2
LTG LIGHTING (ELEVATOR CORE) 3x3 0.6 C3 16 16 C4 2.6 3x3 LIGHTING (STAIR CASE) LTG
3 4
LTG LIGHTING (TELECOM & GARBAGE) 3x3 4.4 16 16 2.0 3x3 LIGHTING (TELECOM & GARBAGE) LTG
5 6
LTG LIGHTING (CORRIDOR) 3x3 4.8 C5 16 16 C6 2.5 3x3 LIGHTING (CORRIDOR) LTG
7 8
S.O GENERAL USE SOCKET 3x4 3.3 20 20 2.5 3x4 GENERAL USE SOCKET S.O
9 10
S.O GENERAL USE SOCKET 3x4 3.3 20 20 3.3 3x4 GENERAL USE SOCKET S.O
11 12
LTG LIGHTING (ROOF) 3x3 0.9 16 20 3.3 3x4 GENERAL USE SOCKET S.O
13 14
S.O GENERAL USE SOCKET 3x4 3.3 20 20 3.3 3x4 GENERAL USE SOCKET S.O
15 16
S.O GENERAL USE SOCKET 3x4 1.6 20 20 1.6 3x4 GENERAL USE SOCKET S.O
17 18
S.O GENERAL USE SOCKET 3x4 6.5 20 16 SPARE
19 20
S.O GENERAL USE SOCKET 3x4 4.9 20 20 SPARE
21 22
S.O GENERAL USE SOCKET 3x4 3.3 20 20 4.9 3x4 GENERAL USE SOCKET S.O
23 24
SPARE 20 20 SPARE
25 26
SPACE SPACE
27 28
SPACE SPACE
29 30
SUBTOTAL (AMPS) 14.8 12.1 12.6 6.4 8.3 11.8
6.4 8.3 11.8
32 AMPS, MCCB
TOTAL CONNECTED AMPS 21.3 20.4 24.4
S.
LIGHTING MOTORS MISC. TOTAL
TOTAL CONNECTED LOAD 14.52 KVA OUTLETS
LTG: LIGHTING, HTR:HEATER, MTR: MOTORS, MISC: MISCELLANEOUS CONN. kVA 4.63 0.00 9.89 0.00 14.52
C1,C4: ARE ACTIVATED BY PUSH BUTTONS AND DEACTIVATED
ACCORDING TO TIME SCHEDULES.
C2,C3: ARE ACTIVATED AND DEACTIVATED ACCORDING TO TIME DEM.
0.90 1.00 0.60 1.00 0.70
SCHEDULES. FACTOR
C5,C6: ARE ACTIVATED BY STAND BY MOTION DETECTOR AND
DEACTIVATED ACCORDING TO TIME SCHEDULES.
DEMAND Kva 4.17 0.00 5.94 0.00 10.10
*:EQUIPPED WITH RESIDUAL CURRENT DEVICES
( 30mA FOR SOCKETS & 100mA OTHERWISE )