PANEL REF.
LPP-B-SER-1
FINAL BRANCH CIRCUIT PANELBOARD PANEL TYPE. MCCB
BUILDING B LOCATION ELECTRICAL ROOM - BASEMENT FLOOR
VOLTAGE & FREQ. 380/220V, 50Hz S.C. RATING (I.C.) 16 kA
Wire Phase Load In Amps Phase Load In Amps Wire
TYPE
TYPE
Load Description Size Size Load Description
2
mm R Y B R Y B R Y B mm2
LTG LIGHTING (STAIRS) 3x3 4.3 C1 16 16 ___ ___ SPARE
1 2
LTG LIGHTING (STAIRS) 3x3 4.3 C2 16 16 6.1 3x3 LIGHTING (TELECOM & GARBAGE) LTG
3 4
LTG LIGHTING (LOBBY & CORRIDOR) 3x3 2.7 C3 16 16 C4 2.9 3x3 LIGHTING (CORRIDOR) LTG
5 6
S.O GENERAL USE SOCKETS 3x4 5.7 20 20 4.9 3x4 GENERAL USE SOCKETS S.O
7 8
S.O GENERAL USE SOCKETS 3x4 4.9 20 16 C5 1.1 3x3 LIGHTING (ELEVATOR) LTG
9 10
LTG LIGHTING (ROOF) 3x3 0.9 16 20 7.4 3x4 GENERAL USE SOCKETS S.O
11 12
S.O GENERAL USE SOCKETS 3x4 9.8 20 16 ___ ___ SPARE
13 14
SPARE ___ ___ 20 20 ___ ___ SPARE
15 16
S.O GENERAL USE SOCKETS 3x4 11.5 ___ ___ SPACE
17 18
SUBTOTAL (AMPS) 19.8 9.2 15.0 4.9 7.2 10.3
4.9 7.2 10.3
32 AMPS, MCCB
TOTAL CONNECTED AMPS 24.8 16.4 25.3
S.
LIGHTING MOTORS MISC. TOTAL
TOTAL CONNECTED LOAD 14.62 KVA OUTLETS
LTG: LIGHTING, HTR:HEATER, MTR: MOTORS, MISC: MISCELLANEOUS CONN. kVA 4.90 0.00 9.73 0.00 14.62
C1,C2: ARE ACTIVATED BY PUSH BOTTONS AND DEACTIVATED
ACCORDING TO TIME SCHEDULES.
C3,C4: ARE ACTIVATED BY STAND ALONE MOTION DETECTOR AND DEM.
1.00 0.70 0.50 0.80 0.67
DEACTIVATED ACCORDING TO TIME SCHEDULES. FACTOR
C5: ARE ACTIVATED AND DEACTIVATED ACCORDING TO TIME
SCHEDULES.
*:EQUIPPED WITH RESIDUAL CURRENT DEVICES DEMAND Kva 4.90 0.00 4.86 0.00 9.76
( 30mA FOR SOCKETS & 100mA OTHERWISE )