PANEL REF.
LPP-M-SER
FINAL BRANCH CIRCUIT PANELBOARD PANEL TYPE. MCCB
BUILDING M LOCATION ELECTRICAL ROOM - BASEMENT FLOOR
VOLTAGE & FREQ. 380/220V, 50Hz S.C. RATING (I.C.) 16 kA
Wire Phase Load In Amps Phase Load In Amps Wire
TYPE
TYPE
Load Description Size Size Load Description
2
mm R Y B R Y B R Y B mm2
LTG LIGHTING (TELECOM) 3x3 4.5 16 16 C1 1.1 3x3 LIGHTING (ELEVATOR) LTG
1 2
LTG LIGHTING (STAIR) 3x3 5.7 C2 16 16 1.2 3x3 LIGHTING (ROOF) LTG
3 4
LTG LIGHTING (LOBBY & CORRIDOR)) 3x3 2.0 C3 16 16 C4 4.1 3x3 LIGHTING (CORRIDOR) LTG
5 6
S.O GENERAL USE SOCKET 3x4 6.5 20 20 4.9 3x4 GENERAL USE SOCKET S.O
7 8
S.O GENERAL USE SOCKET 3x4 4.9 20 20 4.9 3x4 GENERAL USE SOCKET S.O
9 10
S.O GENERAL USE SOCKET 3x4 3.3 20 16 C5 5.7 3x3 LIGHTING (STAIR) LTG
11 12
S.O GENERAL USE SOCKET 3x4 7.4 20 16 ___ ___ SPARE
13 14
S.O GENERAL USE SOCKET 3x4 4.9 20 20 ___ ___ SPARE
15 16
S.O GENERAL USE SOCKET 3x4 7.4 20 20 ___ ___ SPARE
17 18
SUBTOTAL (AMPS) 18.5 15.5 12.6 6.0 6.1 9.9
6.0 6.1 9.9
32 AMPS, MCCB
TOTAL CONNECTED AMPS 24.5 21.7 22.5
S.
LIGHTING MOTORS MISC. TOTAL
TOTAL CONNECTED LOAD 15.09 KVA OUTLETS
LTG: LIGHTING, HTR:HEATER, MTR: MOTORS, MISC: MISCELLANEOUS CONN. kVA 5.37 0.00 9.72 0.00 15.09
C1: ARE ACTIVATED AND DEACTIVATED ACCORDING TO TIME
SCHEDULES.
C3,C4: ARE ACTIVATED BY STAND ALONE MOTION DETECTOR AND DEM.
1.00 0.70 0.50 0.80 0.68
DEACTIVATED ACCORDING TO TIME SCHEDULES. FACTOR
C2,C5: ARE ACTIVATED BY PUSH BOTTONS AND DEACTIVATED
ACCORDING TO TIME SCHEDULES.
*:EQUIPPED WITH RESIDUAL CURRENT DEVICES DEMAND Kva 5.37 0.00 4.86 0.00 10.23
( 30mA FOR SOCKETS & 100mA OTHERWISE )