The document is a cooling load estimate for the Garrison Engineer at the Air Force's explosive buildings, detailing the area, volume, and various heat gain calculations. It includes data on solar gain through glass, heat gain from walls and roofs, internal heat gain from people and equipment, and outside air contributions. The final calculations indicate a total heat load of 387,455.99 BTU, with a TR load of 32.29 and a TR with reheat of 38.78.

Uploaded by

probin roy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views1 page

Monsoon

The document is a cooling load estimate for the Garrison Engineer at the Air Force's explosive buildings, detailing the area, volume, and various heat gain calculations. It includes data on solar gain through glass, heat gain from walls and roofs, internal heat gain from people and equipment, and outside air contributions. The final calculations indicate a total heat load of 387,455.99 BTU, with a TR load of 32.29 and a TR with reheat of 38.78.

Uploaded by

probin roy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Srinath Builders & Housing Co. (P)Ltd.

CONTRACTORS, BUILDERS & ENGINEER


3rd FLOOR, ANIL PLAZA , ABC , G.S. ROAD,
GUWAHATI-781005(ASSAM)
CA NO. CE(AF)/SZ/BOR/27 OF 2018-19
COOLING LOAD ESTIMATE - MONSOON
To,
GARRISON ENGINEER(AIR FORCE)
AZARA P.O. LGBI AIRPORT
Floor : GROUND FLOOR
Space : EXPLOSIVE BUILDINGS
Total Ht : 18.40 FEET
AREA = 7359.00 Sq Ft F/c Ht : 18.40 FEET
VOLUME = 135406.00 Cu Ft

SOLAR GAIN GLASS Heat Gain


Item Area Sun Gain Factor (in Btu/Hr) CONDITION DB ( ̊ F) WB ( ̊ % RH DP ( ̊ F) GR/LB
(in Sq Ft) (Btu/[Link]) F)
N- GLASS 0 x 23.00 x 0.25 0 OUSIDE 90.2 88 91.6 199.5
NE- GLASS 0 x 12.00 x 0.25 0 INSIDE 71.6 61.09 55 63.7
E- GLASS 0 x 12.00 x 0.25 0 DIFFERENCE 18.6 XXX XXX XXX 135.8
SE- GLASS 0 x 12.00 x 0.25 0
S- GLASS 0 x 12.00 x 0.25 0 OUTSIDE AIR (VENTILATION)
SW- GLASS 0 x 86.00 x 0.25 0 FRESH AIR 5 People X 5 CFM/Person = 25
W- GLASS 0 x 163.00 x 0.25 0 7359.00 Sqft X 0.06 CFM/Sqft = 442
NW- GLASS 0 x 138.00 x 0.25 0 135406.00 Cu Ft X 2 Air Changes/Hr X 1/60 = 4514
Sky Light 0 x 118.00 x 0.25 0 FRESH AIR = 4514
SOLAR & TRANS. GAIN WALLS & ROOF
Item Area Eqvlt Temp U' Factor EFFECTIVE = Effec Room Sensible Heat = 0.75
(in Sq Ft) Diff ( ̊ F) (Btu/[Link] Ft. ̊ F) SENSIBLE HEAT Eff Room Total Heat
NE- WALL 1059.71 x 9.00 x 0.221 2108 FACTOR (ESHF)
N- WALL x x 0
E- WALL 2007.87 x 20.00 x 0.221 8875 Indicated ADP = 52.40
APPRATUS DEW POINT
SE- WALL x x 0 Selected ADP = 54.00
S- WALL 1059.71 x 23.50 x 0.221 5504
SW- WALL x x 0 Dehumidifying Temp = (Room DBT -ADP) x CF = 15.49
W- WALL 2007.87 x 18.00 x 0.221 7987 Rise
NW- WALL x x 0
Roof Sun 0.00 x 31.50 x 0.35 0 DEHUMIDIFIED CFM = Effec Room Sensible Heat = 7825
Roof Shaded x x 0 Dehumid. Temp Rise x 1.08
TRANS. GAIN EXCEPT WALLS & ROOF
Item Area Eqvlt Temp U' Factor Monsoon Reheat Calculation = [{ERSH (Summer) - ERSH (Monsoon)}/3410 ]
(in Sq Ft) Diff ( ̊ F) (Btu/[Link] Ft. ̊ F)
ALL GLASS 0 x 18.6 x 0.29 0 = 22.81 KW
PARTITION WALL 1060 x 13.6 x 0.12 1729 = 6.49 TR
CEILING 0.00 x 13.6 x 0.12 0
FLOOR 7359.00 x 13.6 x 0.192 19216
INTERNAL HEAT GAIN
PEOPLE - 5 Nos x 221 BTU/Hr/Person 1105
LIGHT - 7359.00 Sq Ft x 1.25 W/Sq Ft x 3.41 41907
EQPT - 3.4 x 1000 Watt x 3.41 11594
ROOM SENSIBLE HEAT (RSH) = 100025
Supply duct heat Supply Duct + Heat Gain +
+ Safety @ 20% 20005.01 Notes :-
gain (5%) Leak Loss from Fan Factor (5%)
(5%) HP (5%)
OUTSIDE & INFILTRATED AIR Occupancy = 5 Persons
CFM x ̊F x BF x FACTOR Light Load = 12290 Watt@1.67W/Sqft
4514 x 18.60 x 0.12 x 1.08 10881.27 Eqpt Load = 1 KW
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) = 130911.31 …........(1) Fresh Air Changes Per Hour = 2 Air Changes Per Hr
LATENT HEAT
People Nos x 215 BTU /Hr Per Person
5 Nos x 215 BTU /Hr Per Person 1075.00
OUTSIDE & INFILTRATED AIR
CFM x GR/LB x BF x FACTOR
4514 CFM x 104 x 0.12 x 0.68 38307.61
ROOM LATENT HEAT (RLH) = 39382.61
Supply duct heat + Safety @ 10% 3938.26
gain (5%) Factor (5%)
EFFECTIVE ROOM LATENT HEAT (ERLH) = 43320.87 …........(2)
EFFECTIVE ROOM TOTAL HEAT (ERTH) ….1+2 = 174232.18 …........(3)
FRESH AIR GAIN
OUTSIDE AIR HEAT (SENSIBLE)
CFM x ̊F x 1-BF x FACTOR
1767 18.6 0.88 1.08 31236.04 …........(4)
OUTSIDE AIR HEAT (LATENT)
CFM x GR/LB x 1-BF x FACTOR
1767 135.8 0.88 0.68 143591.23 …........(5)
HEAT SUB TOTAL ..(3+4+5) 349059.45 …........(6)
RETURN AIR GAIN
Return duct heat gain & Leak Loss + HP Pump + Dehume & @ 11% 38396.54 …........(7)
(1%) ( 5% ) Pipe Loss (5%)

TR LOAD 32.29 GRAND TOTAL HEAT (6+7) = 387455.99 TR WITH REHEAT 38.78 32