Srinath Builders & Housing Co. (P)Ltd.
CONTRACTORS, BUILDERS & ENGINEER
3rd FLOOR, ANIL PLAZA , ABC , G.S. ROAD,
GUWAHATI-781005(ASSAM)
CA NO. CE(AF)/SZ/BOR/27 OF 2018-19
COOLING LOAD ESTIMATE - MONSOON
To,
GARRISON ENGINEER(AIR FORCE)
AZARA P.O. LGBI AIRPORT
Floor : GROUND FLOOR
Space : EXPLOSIVE BUILDINGS
Total Ht : 18.40 FEET
AREA = 7359.00 Sq Ft F/c Ht : 18.40 FEET
VOLUME = 135406.00 Cu Ft
SOLAR GAIN GLASS Heat Gain
Item Area Sun Gain Factor (in Btu/Hr) CONDITION DB ( ̊ F) WB ( ̊ % RH DP ( ̊ F) GR/LB
(in Sq Ft) (Btu/[Link]) F)
N- GLASS 0 x 23.00 x 0.25 0 OUSIDE 90.2 88 91.6 199.5
NE- GLASS 0 x 12.00 x 0.25 0 INSIDE 71.6 61.09 55 63.7
E- GLASS 0 x 12.00 x 0.25 0 DIFFERENCE 18.6 XXX XXX XXX 135.8
SE- GLASS 0 x 12.00 x 0.25 0
S- GLASS 0 x 12.00 x 0.25 0 OUTSIDE AIR (VENTILATION)
SW- GLASS 0 x 86.00 x 0.25 0 FRESH AIR 5 People X 5 CFM/Person = 25
W- GLASS 0 x 163.00 x 0.25 0 7359.00 Sqft X 0.06 CFM/Sqft = 442
NW- GLASS 0 x 138.00 x 0.25 0 135406.00 Cu Ft X 2 Air Changes/Hr X 1/60 = 4514
Sky Light 0 x 118.00 x 0.25 0 FRESH AIR = 4514
SOLAR & TRANS. GAIN WALLS & ROOF
Item Area Eqvlt Temp U' Factor EFFECTIVE = Effec Room Sensible Heat = 0.75
(in Sq Ft) Diff ( ̊ F) (Btu/[Link] Ft. ̊ F) SENSIBLE HEAT Eff Room Total Heat
NE- WALL 1059.71 x 9.00 x 0.221 2108 FACTOR (ESHF)
N- WALL x x 0
E- WALL 2007.87 x 20.00 x 0.221 8875 Indicated ADP = 52.40
APPRATUS DEW POINT
SE- WALL x x 0 Selected ADP = 54.00
S- WALL 1059.71 x 23.50 x 0.221 5504
SW- WALL x x 0 Dehumidifying Temp = (Room DBT -ADP) x CF = 15.49
W- WALL 2007.87 x 18.00 x 0.221 7987 Rise
NW- WALL x x 0
Roof Sun 0.00 x 31.50 x 0.35 0 DEHUMIDIFIED CFM = Effec Room Sensible Heat = 7825
Roof Shaded x x 0 Dehumid. Temp Rise x 1.08
TRANS. GAIN EXCEPT WALLS & ROOF
Item Area Eqvlt Temp U' Factor Monsoon Reheat Calculation = [{ERSH (Summer) - ERSH (Monsoon)}/3410 ]
(in Sq Ft) Diff ( ̊ F) (Btu/[Link] Ft. ̊ F)
ALL GLASS 0 x 18.6 x 0.29 0 = 22.81 KW
PARTITION WALL 1060 x 13.6 x 0.12 1729 = 6.49 TR
CEILING 0.00 x 13.6 x 0.12 0
FLOOR 7359.00 x 13.6 x 0.192 19216
INTERNAL HEAT GAIN
PEOPLE - 5 Nos x 221 BTU/Hr/Person 1105
LIGHT - 7359.00 Sq Ft x 1.25 W/Sq Ft x 3.41 41907
EQPT - 3.4 x 1000 Watt x 3.41 11594
ROOM SENSIBLE HEAT (RSH) = 100025
Supply duct heat Supply Duct + Heat Gain +
+ Safety @ 20% 20005.01 Notes :-
gain (5%) Leak Loss from Fan Factor (5%)
(5%) HP (5%)
OUTSIDE & INFILTRATED AIR Occupancy = 5 Persons
CFM x ̊F x BF x FACTOR Light Load = 12290 Watt@1.67W/Sqft
4514 x 18.60 x 0.12 x 1.08 10881.27 Eqpt Load = 1 KW
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) = 130911.31 …........(1) Fresh Air Changes Per Hour = 2 Air Changes Per Hr
LATENT HEAT
People Nos x 215 BTU /Hr Per Person
5 Nos x 215 BTU /Hr Per Person 1075.00
OUTSIDE & INFILTRATED AIR
CFM x GR/LB x BF x FACTOR
4514 CFM x 104 x 0.12 x 0.68 38307.61
ROOM LATENT HEAT (RLH) = 39382.61
Supply duct heat + Safety @ 10% 3938.26
gain (5%) Factor (5%)
EFFECTIVE ROOM LATENT HEAT (ERLH) = 43320.87 …........(2)
EFFECTIVE ROOM TOTAL HEAT (ERTH) ….1+2 = 174232.18 …........(3)
FRESH AIR GAIN
OUTSIDE AIR HEAT (SENSIBLE)
CFM x ̊F x 1-BF x FACTOR
1767 18.6 0.88 1.08 31236.04 …........(4)
OUTSIDE AIR HEAT (LATENT)
CFM x GR/LB x 1-BF x FACTOR
1767 135.8 0.88 0.68 143591.23 …........(5)
HEAT SUB TOTAL ..(3+4+5) 349059.45 …........(6)
RETURN AIR GAIN
Return duct heat gain & Leak Loss + HP Pump + Dehume & @ 11% 38396.54 …........(7)
(1%) ( 5% ) Pipe Loss (5%)
TR LOAD 32.29 GRAND TOTAL HEAT (6+7) = 387455.99 TR WITH REHEAT 38.78 32