JOB NAME: DATE: Rev:

SPACE FOR: Estimated By:


SIZE: Sq ft 0 0 cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F)
ITEM Area Sun Gain Factor Btu/hour OUTSIDE
(Sq ft) (Btu/h.sq ft) ROOM
N - Glass 0 23 0.56 0 DIFFERENC 0 XXXX XXXX XXXX
NE - Glass 0 12 0.56 0
E - Glass 0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 12 0.56 0 0 People X 0 CFM/Person
S - Glass 0 12 0.56 0 0 Cu ft X 0 Air change per hour
SW - Glass 0 85 0.56 0 CFM VENTILATION
W - Glass 0 163 0.56 0
NW - Glass 0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = #DIV/0!
Sky light 0 118 0.56 0 Indicated ADP = 55 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = -45.90 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 0
N - Wall 0 14 0.36 0
NE - Wall 0 20 0.36 0
E - Wall 0 28 0.36 0
SE - Wall 0 28 0.36 0
S - Wall 0 26 0.36 0
SW - Wall 0 24 0.36 0
W - Wall 0 22 0.36 0
NW - Wall 0 16 0.36 0
Roof Sun 0 17 0.32 0
Roof Shaded 0 18 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = Nos
ITEM Area Temp. diff. U Lighting = W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = KW
All Glass 0 0 1.13 0 Height = FT
Partition 0 -5 0.32 0 Fresh Air= Cfm per person
Ceiling 0 -5 0.41 0 = Air changes per hour
Floor 0 -5 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 0 Nos X 245 0 Latent Heat = 205
Light 0 W X 1.25 3.41 0
Eq. Load 0 WX 3.41 0
ROOM SENSIBLE HEAT (RSH) 0
Supply duct Supply duct Heat gain 4 0
heat gain + leak. loss + from fan
HP(%)
Safety factor (%) 8.5 0

OUTSIDE AIR
CFM °F BF FACTOR
0 0 0.15 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 0
LATENT HEAT
People 0 Nos X 205
ROOM LATENT HEAT (RLH) 0
Supply duct leakage loss + Safety factor 5.0 0
OUTSIDE AIR
CFM GR/LB BF FACTOR
0 0 0.15 0.68 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 0
EFFECTIVE ROOM TOTAL HEAT (ERTH) 0
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = #DIV/0!
0 0 0.85 1.08 0 CFM / Sq ft = #DIV/0!
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = #DIV/0!
CFM GR/LB 1 - BF FACTOR CFM/ TR = #DIV/0!
0 0 0.85 0.68 0 cfm tonn 0.00
HEAT SUB TOTAL 0
Return duct HP Pump + Dehum. & 3.0 0
heat gain & Pipe loss
leak. loss + (%)

TR 0.00 RAND TOTAL HEAT 0