Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Print Time: 15-Jul-2025 05:14 PM
Feeder Name: Bulind Hill(49 Tail) Feeder Code: 090802 Loss Year: 2024-25
Load With Growth: 280 Total Feeder Demand: 5335 Total Feeder DemandG: 5335
Demand Factor; 0.48 Executed By: MUAZ RASHEED Execution Date: 15-Jul-25 05:14 PM
Created By: MUAZ RASHEED Created Date: 15-Jul-25 05:14 PM
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
1 HT_1007_216 10070000 10070001 0.019 0 11070 500 MCM 280 52 0 0 0.626 0 MainParent
_1
2 HT_1007_216 10070001 10070003 0.061 0 11070 DOG 280 91 0.1 0.1 4.821 1 HT_1007_216_
_2 1
3 HT_1007_216 10070003 10070004 0.009 0 11070 DOG 280 91 0 0.1 0.711 2 HT_1007_216_
_3 2
4 HT_1007_216 10070004 10070005 0.02 0 0 DOG 0 0 0 0.1 0 3 HT_1007_216_
_4 3
5 HT_1007_216 10070004 10070006 0.017 200 200 DOG 5.1 2 0 0.1 0 3 HT_1007_216_
_5 3
6 HT_1007_216 10070004 10070009 0.091 0 10870 RABBIT 275 136 0.3 0.4 13.605 3 HT_1007_216_
_6 3
7 HT_1007_216 10070009 10070015 0.145 0 10870 DOG 275 90 0.3 0.7 11.053 4 HT_1007_216_
_7 6
8 HT_1007_216 10070015 10070020 0.149 0 10870 DOG 275 90 0.3 1 11.358 5 HT_1007_216_
_8 7
9 HT_1007_216 10070015 10070340 0.01 0 0 500 MCM 0 0 0 0.7 0 5 HT_1007_216_
_166 7
10 HT_1007_216 10070020 10070021 0.038 0 10870 500 MCM 275 51 0 1 1.207 6 HT_1007_216_
_9 8
11 HT_1007_216 10070021 10070025 0.183 0 10870 DOG 275 90 0.4 1.4 13.95 7 HT_1007_216_
_10 9
12 HT_1007_216 10070025 10070033 0.361 400 10870 DOG 275 90 0.8 2.2 27.519 8 HT_1007_216_
_11 10
13 HT_1007_216 10070033 10070035 0.058 0 10470 DOG 264.8 86 0.1 2.3 4.099 9 HT_1007_216_
_12 11
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
14 HT_1007_216 10070035 10070036 0.027 0 1175 RABBIT 29.7 15 0 2.3 0.047 10 HT_1007_216_
_13 12
15 HT_1007_216 10070035 10070085 0.131 200 9295 DOG 235.1 77 0.2 2.5 7.299 10 HT_1007_216_
_35 12
16 HT_1007_216 10070085 10070088 0.06 0 9095 DOG 230.1 75 0.1 2.6 3.202 11 HT_1007_216_
_36 35
17 HT_1007_216 10070036 10070038 0.072 100 1175 RABBIT 29.7 15 0 2.3 0.126 11 HT_1007_216_
_14 13
18 HT_1007_216 10070038 10070042 0.144 25 25 RABBIT 0.6 0 0 2.3 0 12 HT_1007_216_
_15 14
19 HT_1007_216 10070038 10070046 0.214 100 1050 RABBIT 26.6 13 0.1 2.4 0.299 12 HT_1007_216_
_16 14
20 HT_1007_216 10070088 10070089 0.063 200 700 RABBIT 17.7 9 0 2.6 0.039 12 HT_1007_216_
_37 36
21 HT_1007_216 10070088 10070103 0.259 0 8395 RABBIT 212.4 105 0.6 3.2 23.1 12 HT_1007_216_
_45 36
22 HT_1007_216 10070103 10070106 0.112 0 525 RABBIT 13.3 7 0 3.2 0.039 13 HT_1007_216_
_46 45
23 HT_1007_216 10070103 10070117 0.06 40 7870 DOG 199.1 65 0.1 3.3 2.397 13 HT_1007_216_
_53 45
24 HT_1007_216 10070089 10070090 0.046 200 500 RABBIT 12.6 6 0 2.6 0.014 13 HT_1007_216_
_38 37
25 HT_1007_216 10070046 10070047 0.13 0 950 RABBIT 24 12 0 2.4 0.148 13 HT_1007_216_
_17 16
26 HT_1007_216 10070047 10070048 0.038 100 450 RABBIT 11.4 6 0 2.4 0.01 14 HT_1007_216_
_18 17
27 HT_1007_216 10070090 10070092 0.063 0 300 RABBIT 7.6 4 0 2.6 0.007 14 HT_1007_216_
_39 38
28 HT_1007_216 10070047 10070060 0.065 200 500 RABBIT 12.6 6 0 2.4 0.02 14 HT_1007_216_
_24 17
29 HT_1007_216 10070117 10070120 0.1 15 7830 DOG 198.1 65 0.2 3.5 3.956 14 HT_1007_216_
_54 53
30 HT_1007_216 10070106 10070107 0.021 200 200 RABBIT 5.1 3 0 3.2 0.001 14 HT_1007_216_
_47 46
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
31 HT_1007_216 10070106 10070109 0.077 0 325 RABBIT 8.2 4 0 3.2 0.01 14 HT_1007_216_
_48 46
32 HT_1007_216 10070109 10070110 0.038 0 325 RABBIT 8.2 4 0 3.2 0.005 15 HT_1007_216_
_49 48
33 HT_1007_216 10070092 10070093 0.044 100 100 RABBIT 2.5 1 0 2.6 0.001 15 HT_1007_216_
_40 39
34 HT_1007_216 10070092 10070094 0.048 100 100 RABBIT 2.5 1 0 2.6 0.001 15 HT_1007_216_
_41 39
35 HT_1007_216 10070092 10070095 0.036 0 100 RABBIT 2.5 1 0 2.6 0 15 HT_1007_216_
_42 39
36 HT_1007_216 10070120 10070121 0.028 150 7815 DOG 197.7 64 0 3.5 1.103 15 HT_1007_216_
_55 54
37 HT_1007_216 10070060 10070064 0.147 0 300 RABBIT 7.6 4 0 2.4 0.017 15 HT_1007_216_
_25 24
38 HT_1007_216 10070048 10070049 0.041 0 350 RABBIT 8.9 4 0 2.4 0.006 15 HT_1007_216_
_19 18
39 HT_1007_216 10070064 10070066 0.122 0 300 RABBIT 7.6 4 0 2.4 0.014 16 HT_1007_216_
_26 25
40 HT_1007_216 10070049 10070050 0.054 0 350 RABBIT 8.9 4 0 2.4 0.008 16 HT_1007_216_
_20 19
41 HT_1007_216 10070121 10070123 0.069 0 7665 DOG 193.9 63 0.1 3.6 2.615 16 HT_1007_216_
_56 55
42 HT_1007_216 10070110 10070111 0.032 200 200 RABBIT 5.1 3 0 3.2 0.002 16 HT_1007_216_
_50 49
43 HT_1007_216 10070110 10070112 0.048 100 100 RABBIT 2.5 1 0 3.2 0.001 16 HT_1007_216_
_51 49
44 HT_1007_216 10070110 10070115 0.08 25 25 RABBIT 0.6 0 0 3.2 0 16 HT_1007_216_
_52 49
45 HT_1007_216 10070095 10070096 0.04 0 100 RABBIT 2.5 1 0 2.6 0 16 HT_1007_216_
_43 42
46 HT_1007_216 10070096 10070098 0.047 100 100 RABBIT 2.5 1 0 2.6 0.001 17 HT_1007_216_
_44 43
47 HT_1007_216 10070123 10070124 0.05 25 25 RABBIT 0.6 0 0 3.6 0 17 HT_1007_216_
_57 56
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
48 HT_1007_216 10070123 10070126 0.064 50 7640 DOG 193.3 63 0.1 3.7 2.41 17 HT_1007_216_
_58 56
49 HT_1007_216 10070050 10070051 0.045 100 100 RABBIT 2.5 1 0 2.4 0.001 17 HT_1007_216_
_21 20
50 HT_1007_216 10070050 10070054 0.111 50 250 RABBIT 6.3 3 0 2.4 0.009 17 HT_1007_216_
_22 20
51 HT_1007_216 10070066 10070070 0.127 0 300 RABBIT 7.6 4 0 2.4 0.015 17 HT_1007_216_
_27 26
52 HT_1007_216 10070070 10070071 0.013 100 300 RABBIT 7.6 4 0 2.4 0.001 18 HT_1007_216_
_28 27
53 HT_1007_216 10070054 10070058 0.137 200 200 RABBIT 5.1 3 0 2.4 0.007 18 HT_1007_216_
_23 22
54 HT_1007_216 10070126 10070129 0.068 200 200 RABBIT 5.1 3 0 3.7 0.003 18 HT_1007_216_
_59 58
55 HT_1007_216 10070126 10070130 0.029 25 7390 DOG 186.9 61 0 3.7 1.021 18 HT_1007_216_
_60 58
56 HT_1007_216 10070130 10070131 0.021 100 7365 DOG 186.3 61 0 3.7 0.735 19 HT_1007_216_
_61 60
57 HT_1007_216 10070071 10070082 0.091 0 0 RABBIT 0 0 0 2.4 0 19 HT_1007_216_
_34 28
58 HT_1007_216 10070071 10070073 0.105 0 200 RABBIT 5.1 3 0 2.4 0.005 19 HT_1007_216_
_29 28
59 HT_1007_216 10070073 10070074 0.039 0 200 RABBIT 5.1 3 0 2.4 0.002 20 HT_1007_216_
_30 29
60 HT_1007_216 10070073 10070079 0.066 0 0 RABBIT 0 0 0 2.4 0 20 HT_1007_216_
_32 29
61 HT_1007_216 10070131 10070133 0.053 0 7265 DOG 183.8 60 0.1 3.8 1.805 20 HT_1007_216_
_62 61
62 HT_1007_216 10070133 10070134 0.025 600 1625 DOG 41.1 13 0 3.8 0.043 21 HT_1007_216_
_63 62
63 HT_1007_216 10070133 10070161 0.143 200 5640 DOG 142.7 46 0.2 4 2.935 21 HT_1007_216_
_76 62
64 HT_1007_216 10070079 10070080 0.024 0 0 RABBIT 0 0 0 2.4 0 21 HT_1007_216_
_33 32
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
65 HT_1007_216 10070074 10070077 0.102 200 200 RABBIT 5.1 3 0 2.4 0.005 21 HT_1007_216_
_31 30
66 HT_1007_216 10070161 10070162 0.041 25 225 DOG 5.7 2 0 4 0.001 22 HT_1007_216_
_77 76
67 HT_1007_216 10070161 10070166 0.07 100 5215 DOG 131.9 43 0.1 4.1 1.228 22 HT_1007_216_
_79 76
68 HT_1007_216 10070134 10070135 0.041 0 1025 RABBIT 25.9 13 0 3.8 0.054 22 HT_1007_216_
_64 63
69 HT_1007_216 10070135 10070137 0.085 200 1025 RABBIT 25.9 13 0 3.8 0.113 23 HT_1007_216_
_65 64
70 HT_1007_216 10070162 10070164 0.036 200 200 RABBIT 5.1 3 0 4 0.002 23 HT_1007_216_
_78 77
71 HT_1007_216 10070166 10070168 0.075 0 5115 DOG 129.4 42 0.1 4.2 1.266 23 HT_1007_216_
_80 79
72 HT_1007_216 10070168 10070169 0.024 200 1350 DOG 34.1 11 0 4.2 0.028 24 HT_1007_216_
_81 80
73 HT_1007_216 10070168 10070198 0.056 100 100 RABBIT 2.5 1 0 4.2 0.001 24 HT_1007_216_
_95 80
74 HT_1007_216 10070168 10070199 0.002 0 3665 DOG 92.7 30 0 4.2 0.017 24 HT_1007_216_
_96 80
75 HT_1007_216 10070137 10070139 0.085 200 825 RABBIT 20.9 10 0 3.8 0.073 24 HT_1007_216_
_66 65
76 HT_1007_216 10070139 10070141 0.056 25 625 RABBIT 15.8 8 0 3.8 0.028 25 HT_1007_216_
_67 66
77 HT_1007_216 10070199 10070200 0.027 50 3665 DOG 92.7 30 0 4.2 0.234 25 HT_1007_216_
_97 96
78 HT_1007_216 10070169 10070172 0.14 25 225 RABBIT 5.7 3 0 4.2 0.009 25 HT_1007_216_
_82 81
79 HT_1007_216 10070169 10070177 0.115 100 925 RABBIT 23.4 12 0 4.2 0.124 25 HT_1007_216_
_85 81
80 HT_1007_216 10070177 10070179 0.09 200 825 RABBIT 20.9 10 0 4.2 0.078 26 HT_1007_216_
_86 85
81 HT_1007_216 10070172 10070173 0.022 0 200 RABBIT 5.1 3 0 4.2 0.001 26 HT_1007_216_
_83 82
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
82 HT_1007_216 10070200 10070202 0.084 0 3615 DOG 91.4 30 0.1 4.3 0.707 26 HT_1007_216_
_98 97
83 HT_1007_216 10070141 10070144 0.073 200 600 RABBIT 15.2 8 0 3.8 0.033 26 HT_1007_216_
_68 67
84 HT_1007_216 10070144 10070145 0.02 0 400 RABBIT 10.1 5 0 3.8 0.004 27 HT_1007_216_
_69 68
85 HT_1007_216 10070202 10070205 0.116 200 400 RABBIT 10.1 5 0 4.3 0.023 27 HT_1007_216_
_99 98
86 HT_1007_216 10070173 10070174 0.036 200 200 RABBIT 5.1 3 0 4.2 0.002 27 HT_1007_216_
_84 83
87 HT_1007_216 10070179 10070182 0.115 25 625 RABBIT 15.8 8 0 4.2 0.057 27 HT_1007_216_
_87 86
88 HT_1007_216 10070202 10070208 0.146 50 3215 DOG 81.3 26 0.1 4.4 0.973 27 HT_1007_216_
_101 98
89 HT_1007_216 10070208 10070209 0.053 50 3165 DOG 80.1 26 0 4.4 0.343 28 HT_1007_216_
_102 101
90 HT_1007_216 10070205 10070206 0.047 200 200 RABBIT 5.1 3 0 4.3 0.002 28 HT_1007_216_
_100 99
91 HT_1007_216 10070182 10070183 0.067 100 600 RABBIT 15.2 8 0 4.2 0.031 28 HT_1007_216_
_88 87
92 HT_1007_216 10070145 10070146 0.03 0 400 RABBIT 10.1 5 0 3.8 0.006 28 HT_1007_216_
_70 69
93 HT_1007_216 10070146 10070149 0.131 100 400 RABBIT 10.1 5 0 3.8 0.026 29 HT_1007_216_
_71 70
94 HT_1007_216 10070183 10070184 0.07 0 500 RABBIT 12.6 6 0 4.2 0.022 29 HT_1007_216_
_89 88
95 HT_1007_216 10070209 10070210 0.031 25 3115 DOG 78.8 26 0 4.4 0.194 29 HT_1007_216_
_103 102
96 HT_1007_216 10070210 10070215 0.218 0 3090 DOG 78.2 25 0.1 4.5 1.344 30 HT_1007_216_
_104 103
97 HT_1007_216 10070184 10070187 0.117 200 300 RABBIT 7.6 4 0 4.2 0.013 30 HT_1007_216_
_90 89
98 HT_1007_216 10070184 10070189 0.029 0 200 DOG 5.1 2 0 4.2 0.001 30 HT_1007_216_
_92 89
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
99 HT_1007_216 10070149 10070151 0.068 0 300 RABBIT 7.6 4 0 3.8 0.008 30 HT_1007_216_
_72 71
100 HT_1007_216 10070151 10070154 0.13 0 300 RABBIT 7.6 4 0 3.8 0.015 31 HT_1007_216_
_73 72
101 HT_1007_216 10070189 10070190 0.043 200 200 RABBIT 5.1 3 0 4.2 0.002 31 HT_1007_216_
_93 92
102 HT_1007_216 10070189 10070196 0.372 0 0 DOG 0 0 0 4.2 0 31 HT_1007_216_
_94 92
103 HT_1007_216 10070187 10070188 0.029 100 100 RABBIT 2.5 1 0 4.2 0 31 HT_1007_216_
_91 90
104 HT_1007_216 10070215 10070216 0.019 0 750 DOG 19 6 0 4.5 0.007 31 HT_1007_216_
_105 104
105 HT_1007_216 10070215 10070238 0.109 0 2340 DOG 59.2 19 0 4.5 0.385 31 HT_1007_216_
_119 104
106 HT_1007_216 10070238 10070239 0.018 0 1600 RABBIT 40.5 20 0 4.5 0.058 32 HT_1007_216_
_120 119
107 HT_1007_216 10070216 10070218 0.086 200 750 RABBIT 19 9 0 4.5 0.061 32 HT_1007_216_
_106 105
108 HT_1007_216 10070238 10070310 0.145 0 740 DOG 18.7 6 0 4.5 0.051 32 HT_1007_216_
_152 119
109 HT_1007_216 10070154 10070155 0.047 100 100 RABBIT 2.5 1 0 3.8 0.001 32 HT_1007_216_
_74 73
110 HT_1007_216 10070154 10070156 0.046 200 200 RABBIT 5.1 3 0 3.8 0.002 32 HT_1007_216_
_75 73
111 HT_1007_216 10070310 10070311 0.016 15 740 DOG 18.7 6 0 4.5 0.006 33 HT_1007_216_
_153 152
112 HT_1007_216 10070239 10070272 0.136 25 1100 RABBIT 27.8 14 0 4.5 0.208 33 HT_1007_216_
_134 120
113 HT_1007_216 10070310 10070339 0.356 0 0 DOG 0 0 0 4.5 0 33 HT_1007_216_
_165 152
114 HT_1007_216 10070218 10070219 0.043 0 550 RABBIT 13.9 7 0 4.5 0.016 33 HT_1007_216_
_107 106
115 HT_1007_216 10070239 10070240 0.019 0 500 RABBIT 12.6 6 0 4.5 0.006 33 HT_1007_216_
_121 120
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
116 HT_1007_216 10070240 10070241 0.039 0 500 RABBIT 12.6 6 0 4.5 0.012 34 HT_1007_216_
_122 121
117 HT_1007_216 10070219 10070223 0.162 25 25 RABBIT 0.6 0 0 4.5 0 34 HT_1007_216_
_108 107
118 HT_1007_216 10070219 10070224 0.055 0 525 RABBIT 13.3 7 0 4.5 0.019 34 HT_1007_216_
_109 107
119 HT_1007_216 10070272 10070292 0.102 0 725 RABBIT 18.3 9 0 4.5 0.068 34 HT_1007_216_
_144 134
120 HT_1007_216 10070272 10070275 0.118 200 350 RABBIT 8.9 4 0 4.5 0.018 34 HT_1007_216_
_135 134
121 HT_1007_216 10070311 10070313 0.065 0 725 DOG 18.3 6 0 4.5 0.022 34 HT_1007_216_
_154 153
122 HT_1007_216 10070313 10070317 0.092 200 200 RABBIT 5.1 3 0 4.5 0.005 35 HT_1007_216_
_155 154
123 HT_1007_216 10070313 10070320 0.11 0 525 DOG 13.3 4 0 4.5 0.02 35 HT_1007_216_
_156 154
124 HT_1007_216 10070275 10070278 0.11 50 150 RABBIT 3.8 2 0 4.5 0.003 35 HT_1007_216_
_136 135
125 HT_1007_216 10070292 10070296 0.15 25 25 RABBIT 0.6 0 0 4.5 0 35 HT_1007_216_
_145 144
126 HT_1007_216 10070292 10070299 0.074 0 700 RABBIT 17.7 9 0 4.5 0.046 35 HT_1007_216_
_147 144
127 HT_1007_216 10070224 10070225 0.048 100 525 RABBIT 13.3 7 0 4.5 0.017 35 HT_1007_216_
_110 109
128 HT_1007_216 10070241 10070248 0.261 0 0 RABBIT 0 0 0 4.5 0 35 HT_1007_216_
_123 122
129 HT_1007_216 10070241 10070249 0.007 0 500 RABBIT 12.6 6 0 4.5 0.002 35 HT_1007_216_
_124 122
130 HT_1007_216 10070249 10070251 0.047 50 50 RABBIT 1.3 1 0 4.5 0 36 HT_1007_216_
_125 124
131 HT_1007_216 10070249 10070255 0.19 100 450 RABBIT 11.4 6 0 4.5 0.049 36 HT_1007_216_
_126 124
132 HT_1007_216 10070225 10070228 0.103 0 425 RABBIT 10.8 5 0 4.5 0.024 36 HT_1007_216_
_111 110
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
133 HT_1007_216 10070299 10070300 0.026 200 200 RABBIT 5.1 3 0 4.5 0.001 36 HT_1007_216_
_148 147
134 HT_1007_216 10070299 10070302 0.092 100 500 RABBIT 12.6 6 0 4.5 0.029 36 HT_1007_216_
_149 147
135 HT_1007_216 10070296 10070297 0.04 0 0 RABBIT 0 0 0 4.5 0 36 HT_1007_216_
_146 145
136 HT_1007_216 10070320 10070328 0.128 200 300 DOG 7.6 2 0 4.5 0.007 36 HT_1007_216_
_160 156
137 HT_1007_216 10070278 10070281 0.111 100 100 RABBIT 2.5 1 0 4.5 0.001 36 HT_1007_216_
_137 136
138 HT_1007_216 10070320 10070323 0.069 100 225 DOG 5.7 2 0 4.5 0.002 36 HT_1007_216_
_157 156
139 HT_1007_216 10070323 10070324 0.045 0 125 DOG 3.2 1 0 4.5 0 37 HT_1007_216_
_158 157
140 HT_1007_216 10070328 10070329 0.055 0 100 DOG 2.5 1 0 4.5 0 37 HT_1007_216_
_161 160
141 HT_1007_216 10070302 10070306 0.113 200 400 RABBIT 10.1 5 0 4.5 0.023 37 HT_1007_216_
_150 149
142 HT_1007_216 10070228 10070230 0.137 25 425 RABBIT 10.8 5 0 4.5 0.032 37 HT_1007_216_
_112 111
143 HT_1007_216 10070255 10070258 0.092 0 350 RABBIT 8.9 4 0 4.5 0.014 37 HT_1007_216_
_127 126
144 HT_1007_216 10070258 10070260 0.069 0 350 RABBIT 8.9 4 0 4.5 0.011 38 HT_1007_216_
_128 127
145 HT_1007_216 10070230 10070231 0.043 0 400 RABBIT 10.1 5 0 4.5 0.009 38 HT_1007_216_
_113 112
146 HT_1007_216 10070306 10070308 0.076 200 200 RABBIT 5.1 3 0 4.5 0.004 38 HT_1007_216_
_151 150
147 HT_1007_216 10070329 10070334 0.055 0 0 DOG 0 0 0 4.5 0 38 HT_1007_216_
_164 161
148 HT_1007_216 10070329 10070331 0.044 0 100 RABBIT 2.5 1 0 4.5 0.001 38 HT_1007_216_
_162 161
149 HT_1007_216 10070324 10070325 0.011 125 125 DOG 3.2 1 0 4.5 0 38 HT_1007_216_
_159 158
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Sr SectionID From Node To Node Len KM Connected Commulative Conductor Section % Loading % Voltage Commulative Loss KW Sort Order Parent
KVA KVA Current Drop Voltage Drop SectionID
150 HT_1007_216 10070331 10070333 0.054 100 100 RABBIT 2.5 1 0 4.5 0.001 39 HT_1007_216_
_163 162
151 HT_1007_216 10070231 10070232 0.04 0 400 RABBIT 10.1 5 0 4.5 0.008 39 HT_1007_216_
_114 113
152 HT_1007_216 10070260 10070261 0.015 0 350 RABBIT 8.9 4 0 4.5 0.002 39 HT_1007_216_
_129 128
153 HT_1007_216 10070261 10070263 0.051 200 350 RABBIT 8.9 4 0 4.5 0.008 40 HT_1007_216_
_130 129
154 HT_1007_216 10070232 10070233 0.025 0 400 RABBIT 10.1 5 0 4.5 0.005 40 HT_1007_216_
_115 114
155 HT_1007_216 10070233 10070234 0.04 0 0 RABBIT 0 0 0 4.5 0 41 HT_1007_216_
_116 115
156 HT_1007_216 10070263 10070264 0.04 100 150 RABBIT 3.8 2 0 4.5 0.001 41 HT_1007_216_
_131 130
157 HT_1007_216 10070233 10070236 0.023 0 400 RABBIT 10.1 5 0 4.5 0.005 41 HT_1007_216_
_118 115
158 HT_1007_216 10070264 10070269 0.26 0 50 RABBIT 1.3 1 0 4.5 0.001 42 HT_1007_216_
_132 131
159 HT_1007_216 10070234 10070235 0.031 0 0 RABBIT 0 0 0 4.5 0 42 HT_1007_216_
_117 116
160 HT_1007_216 10070236 10070282 0.034 100 400 RABBIT 10.1 5 0 4.5 0.007 42 HT_1007_216_
_138 118
161 HT_1007_216 10070282 10070283 0.013 100 100 RABBIT 2.5 1 0 4.5 0 43 HT_1007_216_
_139 138
162 HT_1007_216 10070282 10070287 0.152 0 200 RABBIT 5.1 3 0 4.5 0.008 43 HT_1007_216_
_140 138
163 HT_1007_216 10070269 10070270 0.041 50 50 RABBIT 1.3 1 0 4.5 0 43 HT_1007_216_
_133 132
164 HT_1007_216 10070287 10070288 0.016 200 200 RABBIT 5.1 3 0 4.5 0.001 44 HT_1007_216_
_141 140
165 HT_1007_216 10070287 10070290 0.077 0 0 RABBIT 0 0 0 4.5 0 44 HT_1007_216_
_142 140
166 HT_1007_216 10070290 10070291 0.022 0 0 RABBIT 0 0 0 4.5 0 45 HT_1007_216_
_143 142
Designed and Developed by
Field Survey, Mapping Through Enterprise GIS Application
Load Flow Analysis Input Details
Designed and Developed by