NEUTRAL GROUNDING RESISTOR INSPECTION REPORT (VISUAL)

REF. DWG : REPORT NO :


VOLTAGE : V MANUFACTURER :
RATED CURRENT : A SERIAL NO. :
TIME RATING : SEC IMPEDANCE : OHM

NO INSPECTION CHECK YES NO N/A REMARKS


Compare nameplate data with approved documents/drawings and confirm no
1
deviation.
Compare rating plate data with approved documents/drawings and confirm no
2
deviation.
Check that preservation are in good conditions (no damage, no rust, no undue
3
accumulation of dust and dirt, no condensation etc.).

4 Check NGR installation in accordance with approved construction drawings.

Check all NGR auxiliary equipment for proper installations in accordance with
5
approved vendor drawings.
Check cables for proper connections (no damage, within allowed cable bending
6
radius, proper cable supports, cable gland tightness and accessories).

7 Check any missing fixing bolts for termination enclosures.

8 Check earthing and bonding in accordance with approved construction drawings.

9 Confirm CT secondary wiring is shorted, if external connection is not provided.

10 Confirm CT secondary shorting link is removed, if external connection is provided.

11 Confirm that conduits for cable supports are made of non-metallic materials.

Prepared & Inspected by Inspected by PT PP Accepted by Client


Subcontractor

Name
Date
Page :
' PROJECT NAME ' Inspect Date :

NEUTRAL GROUNDING RESISTOR TEST REPORT

REF. DWG : REPORT NO :


VOLTAGE : V MANUFACTURER :
RATED CURRENT : A SERIAL NO. :
TIME RATING : SEC IMPEDANCE : OHM

INSULATION RESISTANCE TEST


PROCEDURE (Note) Measure IR between the resistor and earth by IR tester for 1 min.
Test voltage shall be 500Vdc for resistors rated 1kVac or less, 2500Vdc for
those rated 5kVac or less, and 5000Vdc for those rated over 5kVac.
Measurement shall be done with primary and secondary cables disconnected.
CRITERIA (Note)
Not less than 100 M Ohm
TESTING INSTRUMENT
RECORDED VALUE Resistor to Ground : MΩ
RESULT Pass N.A. Fail Comment
Note : In case of conflicts with the manufacturer's requirements, the manufacturer's requirements shall govern.

INSULATION RESISTANCE TEST FOR AUX POWER CIRCUIT


PROCEDURE (Note) Measure IR between the resistor and earth by IR tester at 500 Vdc for 1 min.
CRITERIA (Note)
Not less than 100 MΩ
TESTING INSTRUMENT
AUXILIARY CIRCUIT RESULT REMARKS
Actual Value (MΩ)
Description Tag No. (if Any) PASS FAIL N/A

Space heater

Note : In case of conflicts with the manufacturer's requirements, the manufacturer's requirements shall govern.

Prepared & Inspected by Inspected by PT PP Accepted by Client


Subcontractor

Name
Date