Professional Documents
Culture Documents
SYSTEM
Prepared by
SANCHIT
SINGHAL
WHAT IS A SUBSTATION
An electrical sub-station is an assemblage of electrical
components including bus bars, switchgear, power
transformers, auxiliaries etc. These components are connected
in a definite sequence such that a ckt. can be switched off
during normal operation by manual command and also
automatically during abnormal conditions such as short-ckt.
Basically an electrical substation consists of No. of incoming
ckt. and outgoing ckt. connected to a common Bus-bar
systems.
A sub-station receives electrical power from generating
station via incoming transmission lines and delivers elect.
power via the outgoing transmission lines.
"Sub-station are integral parts of a power system and form
important links between the generating station, transmission
systems, distribution systems and the load points."
SUBSTATION VIEW
CONTINUED
Determining the energy transfer through
transmission lines.
Reliable supply by feeding the network at
various points.
Establishment of economic load distribution
and several associated functions
TYPES OF SUBSTATION
Classification based on application
Step Up Substation: Associated with generating
station as the generating voltage is low.
Primary Grid Substation: Created at suitable
load centre alongPrimary transmission lines.
Secondary Substation: Along Secondary
Transmission Line.
Distribution Substation: Created where the
transmission line voltage is Step Down to supply
voltage.
Bulk supply and industrial substation: Similar
to distribution sub-station but created separately
for each consumer.
Mining Substation: Needs special design
CONTINUED
Classification based on Outdoor or Indoor :
outdoor substation is under open sky and Indoor
substation is inside a building.
Classification based on voltage levels, e.g. :
A.C. Substation : EHV, HV, MV, LV; HVDC
Classification based on configuration,e.g. :
Conventional air insulated outdoor substation or
SF6Gas Insulated Substation (GIS) or Composite
substations having combination of the above
two.
Mobile Substation: Temporary requirement.
CONTINUED.
Strips, earthing spikes & earth electrodes.
Overhead earth wire shielding against lightening
strokes.
Galvanized steel structures for towers, gantries,
equipment supports.
PLCC equipment including line trap, tuning unit,
coupling capacitor, etc.
Power cables
Control cables for protection and control
Roads, Railway track, cable trenches
Station illumination system
11KVSwitchgear, LV
11KVIndoor Switchgear
CONTINUED.
BatteryRoom
andD.C.DistributionSystem
D.C .Battery system and charging equipment
D.C. distribution system
CONTINUED.
Arresters
Breakers
Voltage regulators
Current transformers
Potential Transformers
CouplingCapacitors
Line Traps
TRANSFORMER
MAIN PARTS OF
TRANSFORMER
WHAT IS A CIRCUIT
BREAKER
CircuitBreakers are theswitching and current
interrupting devices. Basically a circuit breaker
comprises a set offixed and movable contacts. The
contacts can be separated by means of
anoperating mechanism. The separation of current
carrying contacts produces an arc. The arc is
extinguished by a suitable medium such
asdielectric oil, air vacuum, SF6 gas. The CBs are
necessary at every switching point in the substation
IN SIMPLE WORDS, A C.Bis an equipment which can
open / close a circuit under all conditions i.e.no
load, full load, fault conditions.
CURRENT TRANSFORMERS
CAPACITIVE VOLTAGE
TRANSFORMER
ACVT is more economical as
electromagnetic voltage
transformer when the voltage
level is above 66KV.
SURGE ARRESTOR
SURGE ARRESTOR is
used to divert the
transient over
voltages Surges to
earth and thus
protects the
Substation
equipment
fromlightening and
switching over
voltage surges.
WAVE TRAP
WAVE TRAP is
connected in series
of circuit which
allows only normal
frequency signal to
pass and check or
stop the High
Frequency PLCC
signals.
CAPACITOR BANK
Capacitor bank is
used in sub station
to control POWER
FACTOR and
VOLATGE PROFILE.
EARTHING SYSTEM
Purpose of earthing
Safety of the living beings around the vicinity
of the substation
Proper functioning of the protection system
under fault condition
To limit the touch and step potential within
tolerable limits
HUMAN SAFETY
CURRENT RANGE
1 mA
1-6 mA
9-25 mA
25-60 mA
60-100 mA
EFFECT ON HUMANS
Threshold of
perception
Let go currents
Pain full, hard to let
go
Muscular
contractions
Ventricular
fibrillation
THANK
YOU