Professional Documents
Culture Documents
control
Objective
1 When cold discomfort conditions prevail:
a to prevent heat loss
b to utilise heat gain from the sun and internal sources
c to compensate for any net loss, by heating which uses some form of
energy supply
2 When hot discomfort conditions prevail:
a to prevent heat gain.
b to maximise heat loss.
c to remove any excess heat by cooling, which uses some form of
energy supply.
2
Objective
3 When conditions vary diurnally between hot and cold discomfort:
a to even out variations
b (1) in the cold phase and (2) in the hot phase (as above)
c to compensate for both excesses by a flexible heating-cooling
system
Objectives listed under a and b in each group can be achieved by
structural or constructional (passive) means, item c in each group is the
task of mechanical or energy-based (active) controls.
Degree of Control
Natural Condition
Microclimate control
Structural Control
Mechanical Control
Mechanical Control
Heating
Cooling
Heating
Conversion of some form of energy (fuel material) into heat.
Various fireplaces, stoves and ovens burning wood, coal. coke or oil .
Gas and electric heaters can be considered as using a processed fuel: the energy of coal,
mineral gas, oil or hydraulic and atomic energy
Processed centrally in readily usable form and distributed through a network of pipes or cables
to the points of use.
Central heating is the term used to describe an installation where heat is produced at a central
point (the boiler or furnace), using any of the above mentioned fuel materials, and is
subsequently distributed by some conveying medium.
The level of centralisation can vary
Any central heating system consists of three distinct elements:
I the heat raising plant' (boiler or furnace)
2 the distribution network (ducting or piping)
3 the heat emitter units (diffusers, radiators or convectors)
6
Cooling by ventilation
The moving air can be utilised as a heat conveying medium.
Ventilation can also provide a cooling effect simply by replacing the warm inside air with
cooler outside air.
Situation where the outdoor air is at a comfortable temperature or just below that, but there is a
significant internal heat gain (e.g. in a meeting room or a dance hall) which would cause indoor
overheating.
As an example, let us assume that the out-door temperature is 18C; the indoor temperature has
risen to 28C and there is an internal heat gain of 5 kW,
The temperature difference (T) is 28C 18C = 10 degC.
The specific heat of air is 1300( J/m3 degC).
Using the ventilation heat loss equation Q,= 1 300 X V X T.
Duct cross section = ventilation rate(m3/s)/air velocity(m/s)
8
Compres
sor
10
11
Dehumidification
To achieve air at 18C DBT and 60% RH.
The only way to remove moistur from the air is to force it
to condense out: done by cooling.
When air is cooled to its dew-point, further cooling would
cause it to move along the 100% RH curve.
The downwards movement in chart indicates that moisture
is being condensed out, i.e. the absolute humidity is being
reduced.
Air must be cooled far below the required DBT(say18C)
to get rid of moisture and then reheat it to 18C.
All this can be done by using the psychrometric chart
without any calculations. if any two of the DBT. RH, AH
and WBT are known, the
other two quantities can
be found from the chart.
12
Air conditioning
Air, supplied to a room or to a building by mechanical
means, is or can be:
propelled or moved
filtered
washed
humidified
cooled
dehumidified
heated or reheated
The collective term for the machinery which carries out all
these functions is 'air handling plant', and the installation is
referred to as air conditioning.
Without dehumidification the system is not air conditioning.
building installation can take- central handling, local
handling, an induction system.
13
Structural Control
14
15
Thermal insulation
A construction with a low U-value (air-to-air transmittance) will reduce all forms of conduction
heat transfer through the building envelope.
Such a conduction heat flow would be large, if the temperature difference were large.
With small temperature differences between the inside and outside, the heat flow would be
small anyway; an improvement in thermal insulation would not bring any significant reduction.
In a heat gain situation, with strong solar radiation, it is the sol-air temperature value which
must be used to find the temperature difference.
Even if the air temperature difference is small the actual temperature difference acting as a
motive force for heat flow may be large.
Insulation will be most effective under:
steady state conditions, or
if at least the direction of the heat flow is constant for long periods of time especially for
heated or air conditioned buildings.
16
Thermal capacity
Under conditions with large diurnal temperature variations the
significance of thermal capacity wi 11 be much greater than of
insulation.
Thermal capacity is referred as capacitive insulation, as opposed
to resistive insulation provided by low conductivity materials and low
transmittance constructions.
Thermal capacity: Time lag
How much thermal capacity, what length of time-lag, is desirable?
For example a wall facing east receives its maximum heating at
10.00 hours. A time - lag of 10 hours would put the inside surface
temperature maximum at 20.00 hours.
The question can be answered by drawing a graph of the out-door
(sol-air) temperature variations for each wall.
What time will the maximum indoor heating effect be required or
tolerated.
17
Solar Control
The effect of radiation on opaque surfaces can he combined with the effect of warm air by
using the sol-air temperature.
The magnitude of sol-air temperature is influenced by factors within the designer's control:
absorbance and surface conductance.
Selection of color has little effect; the selection of materials is, however, of greater
significance.
Variations in surface conductance are even less, but a lesser absorbance and a greater surface
conductance would reduce the solar heating effect.
Greatest source of heat gain can be the solar radiation entering through a window.
This could increase the indoor temperature far above the out-door air temperature, even in
moderate climates, through greenhouse effect.
There are four methods available for the reduction of solar heat gain through windows
1 orientation and window size
2 internal blinds. curtains
3 special glasses
4 external shading devices
18
Orientation
Near the Equator, the horizontal surface receives the greatest intensity.
At the higher latitude the wall facing the Equator receives the next highest intensity in the
winter (low sun) but it receives very little in the summer.
In the equatorial location north and south walls receive the least intensity and that only for
short periods of the year.
East and west facing walls receive the second highest intensities in the equatorial location and
consistently large intensities even at the higher latitude.
In the equatorial location if solar heat gain is to be avoided, the main windows should face
north or south.
At the higher latitude, an orientation away from the Equator would receive the least sunshine.
but here it may be desirable to have some solar heat gain in the winter.
Minor openings of unimportant rooms should be placed on the east and west side.
19
33 deg S Sydney
20
Shadow angles
The performance of shading devices is specified by two
angles: the horizontal and The vertical shadow angle.
These are both measured from a line perpendicular to the
elevation, and indicate the limit, beyond which the sun
would be excluded, but within which the sun would reach
the point considered.
Horizontal shadow angle
The horizontal shadow angle () characterises a vertical
shading device and it is the difference between the solar
azimuth and wall azimuth, same as the horizontal
component for the angle of incidence.
The vertical shadow angle
characterises a horizontal shading device, e.g. a long
horizontal projection from the wall, and it is measured on a
vertical plane normal to the elevation considered.
21
Shading Devices
These can be of three basic types:
1 vertical devices
2 horizontal devices
3 egg-crate devices
23
25
26
Structural Control
27