You are on page 1of 10

HI-02-6-2

Control of Slab Heating and Cooling Systems


Studied by Dynamic Computer Simulations

Bjarne W. Olesen, Ph.D. Klaus Sommer, Ph.D., P.E. Björn Düchting


Fellow ASHRAE Member ASHRAE

ABSTRACT peak load will also be reduced and it will be possible to transfer
some of the load to outside the period of occupancy. Because
Due to the high energy consumption and first cost, several
these systems for cooling operate at water temperatures close
European countries debate if air conditioning of buildings is
to room temperature, they increase the efficiency of heat
to be recommended or prohibited by law. Air conditioning will
pumps, ground heat exchangers and other systems using
give better control of the indoor temperature and improve
renewable energy sources.
comfort and productivity. There exist, however, many examples
of discomfort in air-conditioned buildings due to draft, noise, These types of systems are mainly used in multistory
and sick building syndrome. office buildings with a low heating load in winter (10 to 30 W/
Alternatively, sensible heating and cooling loads may be m2) and a moderate cooling load in summer (30 to 60 W/m2).
satisfied by hydronic radiant heating and cooling systems, As office buildings often have a raised floor for cabling, most
where pipes are embedded in the concrete slabs between each of the heat transfer between the heated or cooled slabs and the
story. These systems are often combined with a ventilation space will take place through the ceiling surface. Suspended
system, where the outside air volume is based on the require- ceilings are not installed with these kinds of systems.
ments for acceptable air quality. Because these types of When using surface systems for cooling, it is important to
systems use the building mass for heating and cooling, it is control surface temperatures or water temperatures to avoid
often questioned what kind of control concept should be used. condensation. One possibility is to set a lower limit for the
The present paper presents a parametric study of different supply water temperature (Olesen 1997; Simmonds 1994)
control concepts, based on dynamic computer simulations. equal to the dew-point temperature, i.e., absolute humidity in
The results show that a combination of time control and water the space.
temperature control according to outside temperature condi- In many applications, surface heating and cooling
tions will provide acceptable indoor conditions and low energy systems are combined with a ventilation system. In this case,
consumption. the supply air is preconditioned to obtain a supply air temper-
ature lower than the space temperature and remove latent loads
INTRODUCTION by dehumidification. In this way, the humidity (i.e., the dew
A new trend, which started in the early nineties in Swit- point) will be controlled and the performance of the radiant
zerland (Meierhans 1993, 1996), is to use the thermal storage cooling systems is then increased.
capacity of the concrete slabs between each story in multistory Using pipes embedded in the concrete slabs will result in
buildings to heat or cool buildings. Pipes carrying water for a system with a very high thermal mass. In this case, individual
heating and cooling are embedded in the center of the concrete room control is not applicable. In most cases, a zone control
slab. (south-north) is used, where the supply water temperature, the
By activating the building mass, there will not only be a average water temperature, or the flow rate may differ from
direct heating/cooling effect, but due to the thermal mass, the zone to zone.

Bjarne W. Olesen is the head of research and development at Wirsbo-Velts Gmbh, Norderstedt, Germany. Klaus Sommer is a professor at
the University of Applied Sciences, Köln, Germany. Björn Düchting is with VDI-TGA, Düsseldorf, Germany.

698 ASHRAE Transactions: Symposia


Relatively small temperature differences between the izes the thermal behavior of all rooms that are at least two
heated or cooled surface and the space are typical for surface rooms away from the roof, corner, and ground floor rooms.
heating and cooling systems. This results in a significant The geometrical dimensions of the room module are shown in
degree of self control because a small change in the tempera- Figure 2.
ture difference will significantly influence the heat transfer Table 1 contains the thermal characteristics of the compo-
between the cooled or heated surface and the space. nents used as the basis for this study. A differentiation is made
For a well-designed building with a low heating and low between lightweight and heavyweight types of construction.
cooling load, a concrete slab system may be controlled at a
constant core (water) temperature year-round. If, for example, Boundary Conditions
the core is kept at 22°C, the system will heat at room temper-
atures below 22°C and cool when the room temperature The meteorological ambient boundary conditions corre-
increases above 22°C. As the cooling capacity of such a spond to those of Würzburg, Germany (open terrain). The
system, which also uses the heat storage potential of the external temperature variations for the simulated period from
concrete slabs, is difficult to predict and as it is a very dynamic May 1st till September 30th are shown in Figure 3. Both the
system, it may be necessary to use building computer simula- hourly temperature and daily mean values are given in Figures
tion to evaluate the performance of a concrete slab heating/ 3a and b. The time of occupancy was Monday to Friday from
cooling system. 8:00 to 17:00, 12:00 to 13:00 lunch break. The system was
The present paper presents the results of a dynamic only in operation for cooling by room temperatures higher
computer simulation of such a system. A parametric study of than 23°C. The system was only in operation for heating by
different control concepts has been performed. room temperatures lower than 22°C.

METHOD Internal Heat Sources: During occupied periods, 550 W


The study was performed with the aid of a dynamic simu- corresponding to 27.8 W/m2, which
lation program (TRNSYS 1998). The multidimensional heat corresponds to two persons, two
transfer processes in the slab were modeled via a special computers, a printer, and light. During
module developed by Fort (1996). The following describes the the lunch break, 350 W corresponding
test space and other boundary conditions, which were very to 17.7 W/m2, 50% convective, 50%
similar to the conditions reported in the study by Hauser et. al. radiant.
(2000).
Moisture Production: During occupation, 100 g/h.
Description of System and Test Space Ventilation: Outside time of occupation 0.3 h-1.
During occupation 0.8 h-1.
The system considered is shown in Figure 1. The ceiling/
floor consists of an 18 cm thick concrete slab with 20 mm plas- At operative temperature above 24°C,
tic pipes embedded in the middle with 150 mm spacing. The 5.0 h-1 .
slab is finished with 20 mm of acoustical insulation and 45 mm At operative temperature above 26°C,
of screed. Heat is supplied or removed by the heated or cooled 10.0 h-1
water flowing in the embedded pipes. The mass flow rate of Outside time of occupancy the
the system is constant at 350 kg/h. windows were closed.
The effect of heating and cooling the ceiling is described
using a central room module in an office building with offices
on either side (west and east) of the corridor. This character-

Figure 2 Central room module used for the computer


Figure 1 Construction of the thermal slab. All dimensions simulation of a building with concrete slab
in mm. cooling. All dimensions are in m.

ASHRAE Transactions: Symposia 699


TABLE 1
Thermal Characteristics of the Building Components

Density Conducting Capacity


[mm] [kg/m³] [W(mK)] [Wh(kgK)] Emission
Floor, ceiling Screed 45 2000 1.4 0.28
Acoustical insulation 20 50 0.04 0.42 0.94
Concrete 180 2400 2.1 0.28

Outside wall, light Aluminum 2 2600 200 0.28


(U = 0.37) Insulation 100 30 0.04 0.28 0.30
Aluminum 2 2600 200 0.28

Outside wall, heavy Plaster 8 1000 0.7 0.28


(U = 0.37) Insulation 80 40 0.04 0.42 0.82
Sandlimebrick 240 1200 0.56 0.28
Plaster 15 1200 0.35 0.28

Internal wall, light Plasterboard 25 900 0.21 0.28


Insulation 60 20 0.04 0.28 0.82
Plasterboard 25 900 0.21 0.28

Internal wall, heavy Plaster 15 1200 0.35 0.28 0.82


Sandlimebrick 115 1800 0.99 0.28 0.93

Window Wooden frame, 30% glass Uframe 2.1 W/(m²K)


Uglass 1.1 W/(m²K)
Uwindow 1.4 W/(m²K)
g 0.58

Figure 3a Hourly external temperature used in the computer Figure 3b Daily average external temperature used in the
simulation for the time period of May 1-September computer simulation for the time period of May 1-
30. September 30.

700 ASHRAE Transactions: Symposia


Sun Protection: During occupation by direct exposure The highest amount of cooling is obtained by controlling
of sunlight and operative temperature the water supply temperature at the lowest level possible
above 23°C, reduction factor z = 0.5. before condensation occurs. This is done by controlling the
supply water temperature according to the dew-point temper-
Control Methods ature in the room. For this purpose, a humidity balance (latent
Three methods of control were studied: loads from people, outside humidity gain from ventilation)
was also included in the simulation. It was then possible to
• Time of operation calculate the dew point in the room for each time step in the
• Intermittent operation of circulating pump simulation. This is an extreme case and should not be used in
• Control of water temperature practice because it may result in overcooling, but for reason of
comparison it is included in the present study.
Time of Operation Instead of controlling the supply water temperature, it
Due to the thermal mass, some of the internal heat will be may be better to control the average water temperature. The
stored in the concrete slab during occupancy. It may therefore return water temperatures are influenced by the room condi-
be sufficient to operate the system outside the time of occupa- tions. By constant supply water temperature, an increase in
tion. This will be beneficial for use of the often lower energy internal loads from sun or internal heat sources will increase
costs during nighttime and better potential for use of free cool- the return temperature. The average water temperature will
ing at the lower outside temperatures during nighttime. then increase and the cooling potential will decrease. If instead
If the water-based system is combined with a mechanical the average water temperature (½(treturn – tsupply)) is
ventilation system with precooling of the supply air, it may be controlled, an increase in return temperature will automati-
possible to operate the cooling of the supply air during time of cally be compensated by a decrease in supply water tempera-
occupancy and cooling of the water outside time of occupancy, ture.
where the ventilation is not needed for indoor air quality In well-designed buildings with low heating and cooling
reasons. In this way, the cooling equipment can be downsized. loads, it may be possible to operate the system at a constant
Four different schedules of operation were studied: 24 water temperature. This was also studied. The following
hour, 8:00-17:00, 18:00-06:00, and 22:00-06:00. concepts for water temperature control were studied:
Intermittent Operation of Circulation Pump. It has
been suggested by Meierhans and Olesen (1999) to operate the • Supply water temperature is equal to internal dew-point
pump intermittently and save electrical energy. If the pump is temperature.
stopped, heat in the slab will continue to flow toward the • Supply water temperature is a function of outside tem-
cooler center, where the temperature will increase. When the perature according to the equation:
pump is started again, it will operate with a larger temperature
difference between water and concrete and remove more of the t supply = 1, 3∗ 0, 4∗ ( 20 – t external ) + 20
stored heat in a shorter time.
Three types of intermittent pump operation were studied: • Average water temperature is a function of outside tem-
perature according to
• Pump on for 1 hour – Pump off for 1 hour
• Pump on for ½ hour – Pump off for ½ hour t average = 1, 3∗ 0, 4∗ ( 20 – t external ) + 20 .
• Pump on for ¼ hour - Pump off for ¾ hour
• Supply water temperature is constant and equal to
During the first two types of operation, the total daily 18°C, 20°C, and 22°C.
running time for the pump may be the same, while for the last • Average water temperature is constant and equal to
it should be shorter. 18°C, 20°C, and 22°C.
Control of Water Temperature. In most heating and
cooling systems, the supply water or supply air temperatures RESULTS AND DISCUSSION
are controlled according to internal room temperature, outside
temperature, or a combination of both. The goal for the system The simulations were done for both an east- and a west-
used in the present study is to operate water temperatures as facing room and for heavy and light construction. Only results
close to the room temperature as possible. If very high or very for a west-facing heavy room are presented in this paper. In a
low water temperatures are introduced into the system, it may pretest, it was found that the highest exposures occurred in the
result in overheating or undercooling. Because of the large room facing west. The heavy construction was estimated to be
thermal mass, it is not possible to change the temperature of the most common.
the slab quickly. On the other hand, if water temperatures are Results from the summer period May 1st to September
close to room temperature, there will be a high degree of self 30th are presented.
control where a small room temperature change immediately The total number of hours in this period is ∼ 3690, number
changes the heat transfer. of working days ∼ 109, and number of working hours ∼ 981.

ASHRAE Transactions: Symposia 701


The results will be evaluated based on comfort (operative The calculated operative temperatures may be compared
temperature ranges, daily operative temperature drift during to the comfort range 23°C to 26 °C recommended for summer
occupancy) and energy (running hours for circulation pump, (cooling period) in ASHRAE Standard 55 (1992), ISO 7730
energy removed or supplied by the circulated water). (1993), or CR 1752 (1998). But they are based on a fixed level
of clothing insulation (0.5 clo), which may not be relevant for
the whole period of May to September. Instead, the data are
compared to the temperature ranges included in the German
DIN 1946 part 2 (1994), corresponding to Figure 4.

Study of Time of Operation


The results of the simulation are listed in Table 2.
From Table 2, it is seen that the operative temperature
never exceeds 27°C even if the operation of the system is only
nine hours during the night. There is almost no difference
between twelve hours and nine hours operation regarding
operative temperature. The shorter operating time results in a
6% increase of working hours at temperatures above 25°C but
results in 7% to 9% decrease of hours in the cool range 20°C
to 22°C.
Figure 4 Recommended ranges for operative temperature The temperature drifts during a day are in most cases
depending on outside temperature (DIN1946 part (95%) lower than 4 K. With a shorter time of operation the drift
2, 1994). is only during three to five days (3% to 5%) between 4 to 6 K.

TABLE 2
Operative Temperatures, Temperature Drift, Pump Running Time, and Energy Transfer for Different Operation Times

May to September Average Water Temperature Controlled


According to Outside Temperature
Time of operation 24 hours 18-6 22-6
0905 0901 0902
°C % % %
Operative temperature interval <20 0 0 0
20-22 11 4 2
22-25 88 88 92
25-26 1 6 5
26-27 0.0 2 1
>27 0.0 0 0

Temperature drift <2 53 41 39


2-4 46 54 58
4-6 1 5 3
>6 0 0 0

Pump running hours 1217 515 412


% of time 33 14 11

Energy Cooling 1180 855 775


(kWh)
Heating 493 83 11

702 ASHRAE Transactions: Symposia


Figure 5 Operative, external, supply, and return Figure 6 Operative, external, supply, and return
temperatures for the week of September 2-8. On temperatures for the week of September 2-8. On
the diagram is also indicated when the pump is the diagram is also indicated when the pump is off.
off. Average water temperature controlled as a Average water temperature controlled as a
function of outside temperature. Time of function of outside temperature. Time of operation
operation is 24 hours (code 0905). 18:00 to 06:00 (code 0901).

space temperature falls below 23°C, the pump will stop. It is


By the shorter time of operation, the running time of the indicated on the x-axis where the pump is running.
circulation pump is significantly reduced from ∼ 1200 hours to
400 to 500 hours. Even for 24 hours of possible operation time, Study of Intermittent Pump Control
the system is only in operation one-third of the time (pump The results of the simulation are shown in Table 3.
running). This occurs when the room temperature is below The results are based on tests with supply water temper-
23°C, and the pump is stopped. When the room temperature ature equal to dew point. The interval and drift of operative
falls below 22°C, heating is required and the pump will start temperatures by 24 hours of continued operation are almost
again. exactly the same as for 24 hours of continued operation but
with average water temperature controlled according to
This can be seen in Figure 5, which shows outside temper-
outside temperature (Table 2). The running time of the pump
ature, operative temperature, supply water temperature, and
is a little less. This is probably due to the somewhat cooler
return water temperature for the week of September 2 to water temperature when controlling according to the dew
September 8 for 24 hours operation. During the first two days point.
and during the last day (weekend), the operative temperature To decrease the running time, the operation time as in
falls below 22°C. Heating is required, the pump will start, and Table 2 can be reduced or the pump can be operated intermit-
the supply temperature is heated to about 26°C. From Table 2 tently. For this case, Table 3 shows very good performance,
for 24 hours of operation, it can also be seen that heating is even if the pump is only operated half of the time or even one-
often required during the whole period of May to September. forth of the time.
This is, however, partly because by 24-hour operation, too Only during a very few hours (∼ 1%), the temperature will
much cooling takes place, which, despite the significant increase above 26°C. With the intermittent operation a small
amount of heating, results in room temperatures between 20°C percent of the time, temperatures will increase above 25°C and
and 22°C during 10% of the occupied time. Therefore, 24 fewer hours will be in the cool range of 20°C to 22°C.
hours of operation of the system results in a significantly As the computer simulation routine basically performs
higher energy consumption for heating and cooling (1673 calculations on an hour-by-hour basis, the results with the
kWh) while a reduced time of operation with almost the same pump “on” only 15 minutes and “off” 45 minutes or “on” 30
comfort uses only 786 to 938 kWh and mainly for cooling. minutes and “off” 30 minutes are not very accurate. Therefore,
the calculated energy use for these tests cannot be fully relied
Figure 6 shows calculated temperatures for the reduced upon. It is, however, clear from the results that intermittent
operation time 18:00-06:00. Here, the room temperature is operation not only reduces the pump running time but also
never below 22°C and no heating is required. Because of the reduces energy consumption compared to continuous opera-
reduced time of operation, the pump is running less than with tion.
24-hour operation (Figure 5). It should also be noted that the The intermittent operation, however, does not give better
pump is only running part of the operation time. As soon as the performance at a reduced time of operation (see Table 2).

ASHRAE Transactions: Symposia 703


TABLE 3
Operative Temperatures, Temperature Drift, Pump Running Time, and Energy Transfer for Intermittent Operation
of the Pump (Supply Water Temperature Equal to Room Dew-Point Temperature)

May to September
Operation 24 hours
Pump operation Continuous 1 hour on – ½ hour on- ¼ hour on –
1001 1 hour off, ½ hour off, ¾ hour off,
0102a 0102 0102b
°C % % % %
Operative temperature interval <20 0 0 0 0
20-22 12 8 8 6
22-25 88 89 89 87
25-26 0.4 3 3 5
26-27 0 0 0 1
>27 0 0 0 1

Operative Temperature drift <2 47 73 36 46


2-4 52 26 63 51
4-6 1 1 1 3
>6 0 0 0 0

Pump running hours 1091 630 624 478


% 30 17 17 13

Energy, Cooling 1281 981 496 213


kWh
Heating 391 130 72 11

Figure 7 shows the calculated temperature for the week of for cooling (639 kWh) and for heating (1031 kWh) is signif-
September 2 to 8. In this case, the system was operating for 24 icant higher than for 24-hour operation. Even if the time of
hours and supply temperature was controlled according to dew operation is shorter (12 hours), the pump running time (1377
point. The results are very similar to the results in Figure 5, hours) is longer.
where the supply water is controlled as a function of outside This can be explained by the low water temperature used
temperature. The reason is the limitation by the room dew- during nighttime operation (18:00-06:00) when controlling
point temperature. During this week, the limit for the water water supply temperature equal to dew point. During this
temperature is the dew point even if controlled according to period, the space is not occupied and there is no latent load
outside temperature. (humidity from people). Therefore, when the system starts
cooling after 18:00, it will be with a relatively low water
Study of Water Temperature Control temperature.
This results in overcooling, which often will be compen-
The results of the simulation are listed in Table 4.
sated by heating when the space temperature drops below
This part of the simulation study investigated the perfor-
22°C. Due to the heating, the operative temperatures will not
mance of different water temperature control strategies.
drop and will stay above 20°C, but a lot of energy is consumed
Controlling the supply water equal to the dew point will for heating and cooling.
provide maximum cooling. The performance of the system Outdoor air temperature dependent supply water control
when controlling supply water equal to dew point and 12-hour is more efficient— there are no operative temperatures above
operation (Table 4, code 0202) is not as optimal as for 24-hour 27°C but a 10% exceedance above 25°C than when controlling
operation (Table 3, code 1001). The distribution of operative according to dew-point temperature. On the other hand, there
temperatures is almost the same, but the energy consumption will be almost no time when the temperatures are in the cool

704 ASHRAE Transactions: Symposia


TABLE 4
Operative Temperatures, Temperature Drift, Pump Running Time, and Energy Transfer
by Different Control Strategies of the Water Temperature (Time of Operation 18:00-06:00)

May to September
Time of operation 18:00-06:00
Control water Supply = Supply = °F Average = °F Average = Supply = Supply = Supply =
temperature dew point, (outside), (outside), 22°C, 22°C, 20°C, 18°C,
0202 0801 0901 1201 1101 1105 1109
°C % % % % % % %
Operative <20 0 0 0 0 0 0 2
temperature interval 20-22 14 1 4 1 1 10 22
22-25 84 88 88 68 62 69 66
25-26 2 9 6 16 19 12 7
26-27 0 2 2 10 12 6 2
>27 0 0 0 5 6 3 1

Temperature drift <2 24 48 41 53 49 46 31


2-4 74 49 54 44 46 51 66
4-6 2 3 5 3 5 3 3
>6 0 0 0 0 0 0 0

Pump running hours 1377 1215 515 1989 1989 1989 1894
% of time 38 33 14 54 54 54 52

Energy, Cooling 1639 782 855 952 865 1092 1278


kWh
Heating 1031 44 83 0 0 0 0

range (20°C to 22°C, Table 4), which altogether will result in


better comfort.
Added to this, the energy consumption is much lower for
both cooling (782 kWh) and heating (44 kWh). This is because
undercooling is avoided so there is no need for additional heat-
ing.
If, instead, the average water temperature is controlled as
a function of outside temperature (Table 4, code 0901, Figure
6), the running time of the circulation pump is much shorter
(515 hours) but still results in somewhat lower operative
temperatures. The energy use is also higher. The reason is that
for this control concept, the average water temperature will be
lower than when the supply temperature is controlled accord-
ing to outside temperature. This means the same amount of
cooling can be provided in a shorter time. See in Table 4 the Figure 7 Operative, external, supply, and return
lower running time of the pump (515 hours). temperatures for the week of September 2-8. On
Figure 8 shows the calculated temperatures for the week the diagram is also indicated when the pump is
of September 2-8. The system is operating outside time of off. Supply water temperature = dew point
occupancy, 18:00-06:00, and the supply water temperature is temperature, °C. Time of operation is 24 hours
a function of outside temperature. It can be seen during the (code 1001).
night that when the outside temperature decreases, the supply
ASHRAE Transactions: Symposia 705
Figure 8 Operative, external, supply, and return
temperatures for the week of September 2-8. On
the diagram is also indicated when the pump is Figure 10 Operative, external, supply, and return
off. Supply water temperature is a function of temperatures for the week of September 2-8. On
external temperature, °C. Time of operation is the diagram is also indicated when the pump is
18:00 to 06:00 (code 0801). off. Average water temperature = 22°C. Time of
operation is 18:00 to 06:00 (code 1201).

slightly lower operative temperatures. The operative temper-


atures are, however, in many cases too high.
Five to six percent of the time, which corresponds to 50
working hours, the operative temperatures are above 27°C and
15% to 18% of the time above 26°C. This is somewhat surpris-
ing because more heat is removed by the circulated water in
the case of constant water temperature (22°C) compared to
controlling according to outside temperature. The combined
energy use for heating and cooling is, however, very much the
same as if no heating has taken place. But due to the long pump
running time, the total energy use is higher with constant water
Figure 9 Operative, external, supply, and return
temperature control.
temperatures for the week of September 2-8. On
the diagram is also indicated when the pump is Figure 9 shows the results for a constant supply water
off. Supply water temperature = 22°C. Time of temperature of 22°C. For this week (September 02-08), the
operation is 18:00 to 06:00 (code 1101). operative temperature increases to 30°C, which is too warm.
Most of the time, operative temperatures are above 24°C, so
the pumps are running during the whole time of operation.
For comparison, Figure 10 shows the results with a
water temperature increases. But the water temperature never
constant average water temperature.
goes above room temperature, so no heating takes place. Most
Tests were also made with constant supply water temper-
of the time the pump is only running until 02:00-03:00 in the
atures of 20°C and 18°C. At 20°C, the comfort performance is
night. better than with 22°C but with higher energy consumption.
The other results in Table 4 are from a test with constant Using 18°C water will result in too many hours in the cool/cold
supply or average water temperature. Almost similar results range.

are obtained by controlling supply water temperature as by Another way of representing the calculated operative
temperatures is shown in Figure 11 together with the recom-
controlling average water temperature. During the time of
mended comfort range by ASHRAE 55 and ISO 7730. The
operation (18:00-06:00), the pump is in both cases running all examples are for supply temperature controlled according to
the time. A little more cooling is provided (952 kWh) when outside temperature and time operation 18:00-06:00 or 22:00-
controlling the average water temperature. It also resulted in 06:00.

706 ASHRAE Transactions: Symposia


CONCLUSION
The results of a dynamic computer simulation of different
control concepts for a water-based radiant cooling and heating
system have been presented. The system was studied for the
period May to September.
For this type of system, where the pipes are embedded in
the building structure, it is important not to use water temper-
atures too high or too low due to the dynamic result in under-
cooling or overheating of the occupied space.
Controlling supply water temperature equal to dew-point
temperature in the occupied space provides the maximum
amount of cooling without resulting in condensation. Comfort
performance is not optimal due to undercooling. Energy Figure 11 Operative temperature distribution for the period
performance is also not good due to the need for reheating. of May 1 to September 30. Water supply
The time of operation can be limited by operating the temperature controlled as a function of outside
system only during nighttime or using intermittent operation temperature. Operation time is 18:00 to 06:00
of the circulation pump. and 22:00 to 06:00 (code 0802).
The best comfort and energy performance is obtained by
controlling the water temperature (supply or average) as a
function of outside temperature but with a low inclination of
the control curve. Meierhans, R.A., and B.W. Olesen. 1999. Betonkernaktivier-
ung, Book, ISBN 3-00-004092-7.
REFERENCES
Meierhans, R.A. 1993. Slab cooling and earth coupling.
ASHRAE. 1992. ASHRAE 55-1992, Thermal environmental ASHRAE Transactions 99(2). Atlanta: American Soci-
conditions for human occupancy. Atlanta: American ety of Heating, Refrigerating and Air-Conditioning
Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Engineers, Inc. Meierhans, R.A. 1996. Room air conditioning by means of
CR 1752 (1998): Ventilation for Buildings: Design Criteria overnight cooling of the concrete ceiling. ASHRAE
for the Indoor environment, CEN, Brussels. Transactions 102(2). Atlanta: American Society of
DIN 1946 (1994): Ventilation and air conditioning; Part 2- Heating, Refrigerating and Air-Conditioning Engineers,
Technical health requirements. DIN, Berlin. Inc.
Fort, K. 1996. Type 160: Floor heating and hypocaust. Olesen, B.W. 1997. Possibilities and limitations of radiant
Hauser, G., C. Kempkes, and B.W. Olesen. 2000. Computer floor cooling. ASHRAE Transactions 103(1). Atlanta:
simulation of the performance of a hydronic heating and American Society of Heating, Refrigerating and Air-
cooling system with pipes embedded into the concrete Conditioning Engineers, Inc.
slab between each floor. ASHRAE Winter meeting, Dal- Simmonds, P. 1994. Control strategies for combined radiant
las, 5-9 February 2000. heating and cooling systems. ASHRAE Transactions
ISO 7730 (1993): Moderate thermal environments—Deter- 100(1). Atlanta: American Society of Heating, Refriger-
mination of the PMV and PPD indices and specification ating and Air-Conditioning Engineers, Inc.
of the conditions for thermal comfort. TRNSYS. 1998. TRNSYS 14.2, User’s Manual.

ASHRAE Transactions: Symposia 707

You might also like