Professional Documents
Culture Documents
Field Measurements of
Operative Temperatures in
Buildings Heated or Cooled by
Embedded Water-Based Radiant Systems
Michele De Carli, Ph.D., P.E. Bjarne W. Olesen, Ph.D.
Fellow ASHRAE
ABSTRACT the Romans 2000 years ago to heat thermal baths and houses
The performance of radiant heating systems (floor heat- by means of the combustion products coming from external
ing, ceiling panels) is relatively well documented. Water-based furnaces. People have felt that a room surrounded by low-
systems, where pipes are embedded in the building structure, temperature surfaces is more comfortable than one with a fire-
are now being increasingly used for cooling purposes. Several place, which provides thermal nonuniformity and high levels
theoretical studies based on the use of computer simulations of air circulation. It has also been the traditional heating
have been published, but very little has been reported on the system in Korea for hundreds of years.
actual performance in existing buildings. There are still uncer- More recently, the technique, based on low-temperature
tainties on how such systems operate and on how well the space
heated surfaces by means of pipes circulating water inside
temperatures are kept within the comfort range under varying
building elements, used increasingly in the 1950s with many
external and internal loads.
applications in buildings. Many theoretical studies led by
To study this aspect, field measurements of thermal
Shoemaker (1954) and Missenard (1959) investigated the
comfort conditions were made in several buildings with radi-
ant surface systems: floor, wall, and systems with pipes embed- possibility of floor radiant cooling systems.
ded in the concrete slabs between each floor in a multistory After this initial period, the interest in this technique
building. Long-term measurements of operative, air, surface, became less and less because of the conjunction of two
system, and external temperatures have been carried out. The aspects. The first is related to technological defects, mainly
present paper present the results of the measured operative due to steel pipes with weak soldering under the floor. The
temperatures. second one represents the high values of surface temperatures
The analysis of the data shows that, for the major part of of the floor, which occurred because of high values of perfor-
the time of occupancy, the operative temperature is inside the mance required by the systems (up to 100 W/m2) as a conse-
comfort range. The data show an increase in space tempera- quence of the inadequate insulation used in the envelope of the
ture during the day, which is counterbalanced by a correspond-
buildings.
ing decrease during the night. This study shows that hydronic
radiant systems in many buildings are an interesting alterna- The decrease of U-factors of buildings allows use of
tive to full air-conditioning systems for obtaining acceptable systems with less capacity and, therefore, lower surface
indoor thermal environments. temperatures. To heat up a room to 20°C by a heat load of 40
W/m2 requires only a floor temperature of 24°C, while in the
INTRODUCTION 1950s, with more than 100 W/m2 heat load, the required floor
Heating systems using large surfaces with surface surface temperature was above 30°C. It should be noted that
temperatures close to room temperature are not a new tech- the maximum design floor is 29°C (ASHRAE 1994; ISO
nique. The so-called hypocaust heating was already known by 1994).
Michele de Carli is a research associate at Istituto di Fisica Tecnica, University of Padova, Italy. Bjarne W. Olesen is the head of research
and development, Wirsbo-VELTA GmbH, Norderstedt, Germany.
TABLE 1
Classes of Thermal Comfort (CR 1752)
Accuracy Resolution
Probe Type [°C] [°C] Building
Operative temperature I Ellipsoide 0.5 0.1 1, 2, 3,4
Operative temperature II Globe thermometer (40 mm) 0.5 0.1 2, 3
Operative Temperature III Half-globe thermometer (40 mm) 0.5 0.1 2
Air temperature I Pt 100 0.2 0.1 1, 2, 3, 4
Air temperature II NTC sensor 0.5 0.1 3
Dew-point temperature Chilled mirror 0.5 0.1 1, 2, 3, 4
Measurements
Measurements have been made with different tempera-
ture probes, whose specifications are reported in Table 2. For
operative temperature, three different probes have been used.
The first probe is a temperature sensor shaped like an ellipsoid Figure 2 Schematic construction of Building 1.
(50 mm × 120 mm), which will directly measure the operative
temperature (ISO 7726). The second temperature sensor (II) is
a globe thermometer with 40 mm diameter, which, due to the RESULTS AND DISCUSSION
size according to ISO 7726 specifications, measures the aver- The results and discussion are presented below, building
age value between air and mean radiant temperature at low air for building.
velocities. The third probe (III) is a half-globe thermometer
with 40 mm diameter that has been installed on the surfaces Building 1
opposite to the external walls. In this way, the sensor will be
exposed to a radiant heat exchange with all surfaces except the This is a two-story building of a very light construction.
back wall. Probes II and III were transferring the temperatures In order to limit the indoor operative temperatures, floor heat-
to a logger via radio frequency. Data were recorded each half ing/cooling was installed in the offices and in the hallway, as
hour. well a wall heating/cooling system (Figure 2). The cooling is
supplied from a ground heat exchanger where pipes are
Analysis of the operative temperatures in the buildings
embedded in the foundation, which is more or less surrounded
has been made both for the whole day and for the working time by groundwater. This allows a supply water temperature of
only during the whole measuring period. Typical office hours 16°C. The offices are all located in a westerly direction with
have been defined as the reference working time (between external sun screens. There is a ventilation system that
8:00 and 18:00, Monday through Friday). In this paper, only provides primary air.
the data of the working time are reported.
Three offices and the hallway were investigated for one
Measurements were made in four buildings with different month (between July and August 1998). The operative
types of water-based radiant systems. Building 1 in Bregenz, temperatures were measured by means of an elliptical probe
Austria, has a combination of wall-floor-ceiling heating-cool- (Table 2). The external temperature was provided by the mete-
ing system. Building 2 in Halle, Germany, has a floor heating- orological institute. A sample of measured operative temper-
cooling system. Building 3 in Stuttgart, Germany, has an atures are shown in Figure 3: even if the outside temperature
active thermal slab system. Building 4 in Milan, Italy, has a is higher than 30°C, the inside temperature is always below
floor heating/cooling system. 26°C.
TABLE 3
Percentage of Operative Temperature Distribution During Working Time
Table 3 shows that for 95% of the total working hours the The results show that even in a very light building it is
operative temperature in the offices is between 21°C and 25°C, possible with a surface cooling system to keep the room
and the temperatures increase above 26°C only in the hallway. temperatures from getting too high.
The temperature sensor in the hallway is exposed, around
noon, to the direct sun radiation coming from the glazed ceil- Building 2
ing. Table 4 shows that the operative temperature during a This rectangular building (11.5 m × 60 m) is equipped by
working day is in most cases below 4°C, with the exception of floor heating/cooling. In this building, the control of the floor
the hallway and office 404. heating/cooling system is separated in an east and a west zone.
By evaluation according to the German standard (Table The supply water temperature was controlled according to the
5), the operative temperatures in the offices are, for more than outside temperature. For the cooling, the supply temperature
50% of the time, in the optimal comfort range between 22°C was limited according to the dew point measured in an east-
and 26°C and about 40% in the cool range between 20°C and oriented office for the east zone and in a west-oriented office
22°C. for the west zone. The windows in the offices are shielded
The tuning of the control system was not completed at the from sun radiation by means of internal or external screens.
time of the measurements and the excess of low temperature The building has operable windows and no mechanical venti-
could be avoided by stopping the cooling earlier in the night. lation. Measurements were made from middle June to middle
TABLE 4
Percentage of the Operative Temperature Change Distribution During a Working Day
TABLE 5
Percentage of Operative Temperature Distribution According to DIN 1946
TABLE 6
Percentage of Operative Temperature Distribution During Working Time
Temperature Range
[°C] East West Inside Shading Outside Shading All
<20 4.7 16.1 10.2 10.5 9.9
20-21 6.0 14.2 8.5 10.8 10.0
21-22 9.3 20.7 12.2 16.2 15.5
22-23 20.7 23.5 18.0 23.9 23.1
23-24 29.5 14.8 16.6 24.5 23.4
24-25 17.4 7.1 15.9 10.7 12.1
25-26 7.6 2.4 9.2 3.2 4.5
26-27 2.3 0.4 4.1 0.1 0.9
27-28 1.2 0.5 2.5 0.1 0.4
28-29 0.8 0.2 1.5 0.0 0.1
29-30 0.3 0.1 0.6 0.0 0.0
>30 0.3 0.1 0.7 0.0 0.1
TABLE 7
Percentage of Operative Temperature Change Distribution During a Working Day
Temperature Change
During a Day [°C] East West Inside Shading Outside Shading All
TABLE 8
Percentage of Operative Temperature Distribution According to DIN 1946 During Working Time
Temperature Range
[°C] East West Inside Shading Outside Shading All
<20 4.7 16.1 10.2 10.5 9.9
20-22 15.3 34.9 20.7 27.0 25.5
22-25 67.6 45.4 50.5 59.1 58.6
25-26 7.6 2.4 9.2 3.2 4.5
26-27 2.3 0.4 4.1 0.1 0.9
>27 2.5 0.8 5.3 0.1 0.6
4th Floor
Temperature 4th Floor Window 5th Floor 5th Floor 5th Floor All Offices Except
Range [°C] Window East South Window West Window East Middle Meeting Room Middle
<20 0.0 1.2 0.0 0.0 0.0 0.0 0.2
20-21 1.3 6.9 0.4 0.1 2.6 13.3 4.4
21-22 9.9 27.6 2.1 1.4 17.8 22.4 12.7
22-23 34.8 40.6 10.8 8.1 30.6 34.1 25.7
23-24 39.2 22.3 27.8 26.7 19.8 22.0 27.6
24-25 14.7 1.4 36.4 36.9 22.2 7.7 19.4
25-26 0.1 0.0 18.4 21.7 7.0 0.5 8.1
26-27 0.0 0.0 3.7 5.2 0.0 0.0 1.8
27-28 0.0 0.0 0.3 0.0 0.0 0.0 0.1
TABLE 10
Percentage of Operative Temperature Change Distribution During in a Working Day
TABLE 11
Percentage of Operative Temperature Distribution According to DIN1946 During Working Time
TABLE 12
Percentage of Operative Temperature Distribution During Working Time
Temperature Range 4th Floor 4th Floor 5th Floor 5th Floor
[°C] Window East Window South Window West Window East Meeting Room All Offices
<20 0.0 11.0 0.1 0.0 0.0 2.2
20-21 16.9 38.0 10.4 0.9 2.6 13.8
21-22 38.4 37.2 23.5 17.2 27.2 28.7
22-23 40.6 13.6 38.9 42.5 37.6 34.6
23-24 4.1 0.3 25.3 37.4 32.5 19.9
24-25 0.0 0.0 1.7 2.0 0.0 0.7
TABLE 13
Percentage of Operative Temperature Change Distribution During in a Working Day
Temperature Change 4th Floor 4th Floor 5th Floor 5th Floor
During a Day [K] Window East Window South Window West Window East Meeting Room All Offices
<1 16.7 19.4 2.8 11.1 11.1 13.3
1-2 69.4 30.6 25.0 75.0 75.0 52.2
2-3 13.9 44.4 52.8 13.9 13.9 29.4
3-4 0.0 5.6 19.4 0.0 0.0 5.0
>4 0.0 0.0 0.0 0.0 0.0 0.0
Except for 4th floor south, the measured operative two hours of occupancy, the supply temperature was again
temperatures are inside the recommended comfort range; in decreased below room temperature.
this position, 11% of the time the temperature dropped below
20°C. The building has an additional heating system installed, Building 4
which, however, has not been in operation. The basic heating The fourth building is located in Milan (Italy). It is a
is made by the activated concrete slab system. During the conference building designed by a renovation of an old farm.
winter, however, the supply air temperature increased above It is naturally ventilated and has a floor heating/cooling
the room temperature during the morning hours. After one to system. Measurements were carried out in the second floor
TABLE 14
Percentage of Operative Temperature Distribution According to DIN1946 During Working Time
Temperature Change 4th Floor 4th Floor 5th Floor 5th Floor
During a Day [°C] Window East Window South Window West Window East Meeting Room All Offices
<20 0 11 0.1 0 0 2.2
20-22 55.3 75.1 34 18.1 29.9 42.5
22-25 44.7 13.9 65.9 81.9 70.1 55.3
>25 0 0 0 0 0 0
Figure 7 Temperature trends in the measured period for relevant parameters in the
rooms for Building 4.