You are on page 1of 12

HI-02-6-4

Field Measurements of
Operative Temperatures in
Buildings Heated or Cooled by
Embedded Water-Based Radiant Systems
Michele De Carli, Ph.D., P.E. Bjarne W. Olesen, Ph.D.
Fellow ASHRAE

ABSTRACT the Romans 2000 years ago to heat thermal baths and houses
The performance of radiant heating systems (floor heat- by means of the combustion products coming from external
ing, ceiling panels) is relatively well documented. Water-based furnaces. People have felt that a room surrounded by low-
systems, where pipes are embedded in the building structure, temperature surfaces is more comfortable than one with a fire-
are now being increasingly used for cooling purposes. Several place, which provides thermal nonuniformity and high levels
theoretical studies based on the use of computer simulations of air circulation. It has also been the traditional heating
have been published, but very little has been reported on the system in Korea for hundreds of years.
actual performance in existing buildings. There are still uncer- More recently, the technique, based on low-temperature
tainties on how such systems operate and on how well the space
heated surfaces by means of pipes circulating water inside
temperatures are kept within the comfort range under varying
building elements, used increasingly in the 1950s with many
external and internal loads.
applications in buildings. Many theoretical studies led by
To study this aspect, field measurements of thermal
Shoemaker (1954) and Missenard (1959) investigated the
comfort conditions were made in several buildings with radi-
ant surface systems: floor, wall, and systems with pipes embed- possibility of floor radiant cooling systems.
ded in the concrete slabs between each floor in a multistory After this initial period, the interest in this technique
building. Long-term measurements of operative, air, surface, became less and less because of the conjunction of two
system, and external temperatures have been carried out. The aspects. The first is related to technological defects, mainly
present paper present the results of the measured operative due to steel pipes with weak soldering under the floor. The
temperatures. second one represents the high values of surface temperatures
The analysis of the data shows that, for the major part of of the floor, which occurred because of high values of perfor-
the time of occupancy, the operative temperature is inside the mance required by the systems (up to 100 W/m2) as a conse-
comfort range. The data show an increase in space tempera- quence of the inadequate insulation used in the envelope of the
ture during the day, which is counterbalanced by a correspond-
buildings.
ing decrease during the night. This study shows that hydronic
radiant systems in many buildings are an interesting alterna- The decrease of U-factors of buildings allows use of
tive to full air-conditioning systems for obtaining acceptable systems with less capacity and, therefore, lower surface
indoor thermal environments. temperatures. To heat up a room to 20°C by a heat load of 40
W/m2 requires only a floor temperature of 24°C, while in the
INTRODUCTION 1950s, with more than 100 W/m2 heat load, the required floor
Heating systems using large surfaces with surface surface temperature was above 30°C. It should be noted that
temperatures close to room temperature are not a new tech- the maximum design floor is 29°C (ASHRAE 1994; ISO
nique. The so-called hypocaust heating was already known by 1994).

Michele de Carli is a research associate at Istituto di Fisica Tecnica, University of Padova, Italy. Bjarne W. Olesen is the head of research
and development, Wirsbo-VELTA GmbH, Norderstedt, Germany.

714 ASHRAE Transactions: Symposia


In the 1980s and 1990s, the market for radiant cooling METHOD
panels (suspended ceiling panels) increased significantly in In the present study, the operative temperature at several
middle Europe (De Carli et al. 2000). positions was monitored in four existing buildings. Air
In the middle of the 1990s, interest in radiant floor cooling temperatures and system data were also monitored but are not
started (Michel and Isoardi 1994; Olesen 1997; Olesen et al. presented in this paper. Subjective assessments from the occu-
2000) and since the end of the 1990s, the so-called “active pants were not monitored. Evaluation criteria for the operative
thermal slab” (Olesen 2000) has been installed in several temperature were based on existing national and international
multistory buildings. Until now, papers presenting theoretical standards.
studies of this new technology have been published (Brunello
et al. 2001; De Carli and Olesen 2001; Hauser et al. 2000; Thermal Comfort Evaluation
Simmonds et al. 2000; Koschenz and Lehmann 2000; Meier- On the basis of the international standards and guidelines
hans and Olesen 1999; Meierhans 1996). At the beginning of (ISO 7730 1994, CR 1752 1998, ASHRAE 55-1994), the
2001, more than 60 buildings with the active thermal slab tech- recommended comfort range for operative temperatures
nique were in operation or were being constructed in during winter (heating season) is between 20°C and 24°C for
Germany. Most of them are office buildings with a floor area people with sedentary activity level (1.2 met) with clothing
between 250 m2 and 40,000 m2, but other types of buildings, thermal resistance equal to 1.0 clo. In cooling conditions
such as museums, hospitals, and schools, are also built with (summer), the recommended comfort range for an activity
embedded cooling systems. level of 1.2 met and a clothing thermal resistance of 0.5 clo is
23°C to 26°C. These ranges are based on a predicted percent-
During the last three years, temperature measurements on
age of dissatisfied (PPD) below 10% and a predicted mean
some buildings have been made in order to investigate the
vote (PMV) between –0.5 and +0.5. Similar requirements can
performance of different radiant cooling systems in different
be found in a German standard (DIN 1946, Part 2), which
climatic zones. In the present paper, measurements from four
allow for higher room temperatures by increasing outside
buildings are presented.
temperatures (Figure 1). For radiant systems, it is very impor-
tant to refer to the operative temperature, both for evaluating
the comfort conditions and the performance of the system
itself.
Thermal active slab systems use the thermal storage of the
concrete slabs to reduce peak loads and transfer some of the
energy use to outside the time of occupancy. This has a
dynamic effect on the thermal characteristics of the indoor
environment, i.e., the operative temperature will often
increase during daytime in summer and decrease in winter. In
the German standard DIN1946, the space temperature may
increase to 27°C with outside temperatures of 32°C (see
Figure 1). In EN ISO 7730 and CR 1752, the comfort criteria
for the temperature level inside are given as a range for PMV
or PPD. Depending on economy and outside climate, not all
countries will design for the same comfort level. Also, depend-
Figure 1 Requirements in the German Standard DIN 1946- ing on the type of building, it may be acceptable to design for
Part 2. Horizontal dashed zone: cool range. different levels of comfort. Therefore, CR 1752 and a
Crossed dashed zone: comfort range. Vertical proposed revision of ISO 7730 introduces three classes, as
dashed zone: warm range. shown in Table 1.

TABLE 1
Classes of Thermal Comfort (CR 1752)

Comfort Requirements Temperature Range


PPD PMV Winter Summer
Class 1.0 clo 1.2 met 0.5 clo 1.2 met
[%] [/] [°C] [°C]
A <6 -0.2 < PMV < + 0.2 21-23 23.5-25.5
B < 10 -0.5 < PMV < + 0.5 20-24 23.0-26.0
C < 15 -0.7 <PMV < + 0.7 19-25 22.0-27.0

ASHRAE Transactions: Symposia 715


TABLE 2
Specifications of the Measurement Probes (Includes Building 4 Using Sensor 1)

Accuracy Resolution
Probe Type [°C] [°C] Building
Operative temperature I Ellipsoide 0.5 0.1 1, 2, 3,4
Operative temperature II Globe thermometer (40 mm) 0.5 0.1 2, 3
Operative Temperature III Half-globe thermometer (40 mm) 0.5 0.1 2
Air temperature I Pt 100 0.2 0.1 1, 2, 3, 4
Air temperature II NTC sensor 0.5 0.1 3
Dew-point temperature Chilled mirror 0.5 0.1 1, 2, 3, 4

The standards give values for the comfort conditions in


steady-state conditions but, according to Knudsen et al.
(1989), the PMV-PPD index can be used as long as the rate of
temperature change is lower than 5°C per hour.
In many cases, it may be too costly to keep the tempera-
ture levels in buildings always within the specified comfort
ranges. There should be some allowance for a limited time to
exceed the specified range.

Measurements
Measurements have been made with different tempera-
ture probes, whose specifications are reported in Table 2. For
operative temperature, three different probes have been used.
The first probe is a temperature sensor shaped like an ellipsoid Figure 2 Schematic construction of Building 1.
(50 mm × 120 mm), which will directly measure the operative
temperature (ISO 7726). The second temperature sensor (II) is
a globe thermometer with 40 mm diameter, which, due to the RESULTS AND DISCUSSION
size according to ISO 7726 specifications, measures the aver- The results and discussion are presented below, building
age value between air and mean radiant temperature at low air for building.
velocities. The third probe (III) is a half-globe thermometer
with 40 mm diameter that has been installed on the surfaces Building 1
opposite to the external walls. In this way, the sensor will be
exposed to a radiant heat exchange with all surfaces except the This is a two-story building of a very light construction.
back wall. Probes II and III were transferring the temperatures In order to limit the indoor operative temperatures, floor heat-
to a logger via radio frequency. Data were recorded each half ing/cooling was installed in the offices and in the hallway, as
hour. well a wall heating/cooling system (Figure 2). The cooling is
supplied from a ground heat exchanger where pipes are
Analysis of the operative temperatures in the buildings
embedded in the foundation, which is more or less surrounded
has been made both for the whole day and for the working time by groundwater. This allows a supply water temperature of
only during the whole measuring period. Typical office hours 16°C. The offices are all located in a westerly direction with
have been defined as the reference working time (between external sun screens. There is a ventilation system that
8:00 and 18:00, Monday through Friday). In this paper, only provides primary air.
the data of the working time are reported.
Three offices and the hallway were investigated for one
Measurements were made in four buildings with different month (between July and August 1998). The operative
types of water-based radiant systems. Building 1 in Bregenz, temperatures were measured by means of an elliptical probe
Austria, has a combination of wall-floor-ceiling heating-cool- (Table 2). The external temperature was provided by the mete-
ing system. Building 2 in Halle, Germany, has a floor heating- orological institute. A sample of measured operative temper-
cooling system. Building 3 in Stuttgart, Germany, has an atures are shown in Figure 3: even if the outside temperature
active thermal slab system. Building 4 in Milan, Italy, has a is higher than 30°C, the inside temperature is always below
floor heating/cooling system. 26°C.

716 ASHRAE Transactions: Symposia


Figure 3 Operative temperature trends in one typical warm week.

TABLE 3
Percentage of Operative Temperature Distribution During Working Time

Temperature Range Total for Rooms 304,


[°C] Hallway Room 304 Room 404 Room 414 404, 414
<20 3.5 2.2 2.6 3.5 2.7
20-21 22.0 18.6 6.4 18.9 14.4
21-22 22.2 32.1 20.6 28.2 26.9
22-23 13.7 26.0 32.3 24.8 27.9
23-24 12.1 13.1 19.6 11.7 15.0
24-25 13.7 7.4 16.2 9.6 11.2
25-26 7.8 0.5 2.2 2.4 1.7
26-27 3.3 0 0 0.6 0.2
27-28 1.6 0 0 0.2 0.0
28-29 0.1 0 0 0.2 0.0

Table 3 shows that for 95% of the total working hours the The results show that even in a very light building it is
operative temperature in the offices is between 21°C and 25°C, possible with a surface cooling system to keep the room
and the temperatures increase above 26°C only in the hallway. temperatures from getting too high.
The temperature sensor in the hallway is exposed, around
noon, to the direct sun radiation coming from the glazed ceil- Building 2
ing. Table 4 shows that the operative temperature during a This rectangular building (11.5 m × 60 m) is equipped by
working day is in most cases below 4°C, with the exception of floor heating/cooling. In this building, the control of the floor
the hallway and office 404. heating/cooling system is separated in an east and a west zone.
By evaluation according to the German standard (Table The supply water temperature was controlled according to the
5), the operative temperatures in the offices are, for more than outside temperature. For the cooling, the supply temperature
50% of the time, in the optimal comfort range between 22°C was limited according to the dew point measured in an east-
and 26°C and about 40% in the cool range between 20°C and oriented office for the east zone and in a west-oriented office
22°C. for the west zone. The windows in the offices are shielded
The tuning of the control system was not completed at the from sun radiation by means of internal or external screens.
time of the measurements and the excess of low temperature The building has operable windows and no mechanical venti-
could be avoided by stopping the cooling earlier in the night. lation. Measurements were made from middle June to middle

ASHRAE Transactions: Symposia 717


August in 2000. Operative temperature was measured by control would shut off the water flow to those rooms. Looking
means of a half-globe thermometer (Table 2) in eleven rooms. at Table 7, it can be observed that for most of the working days,
More detailed measurement has been done for a room on the the temperature range is inside an acceptable range of 4°C.
east side where the reference sensor for the control was It is anyway interesting to note that the rooms with exter-
installed. The operative temperature was also measured by nal sunscreens present values of room temperatures lower than
means of an elliptical probe (Table 2). For this room, the trend the ones with internal sunscreens. Also, the temperature
of relevant parameters is shown in Figure 4. The outside change (Table 7) during a day is lower in rooms with external
temperature was measured on the east side by means of a screens. This shows how important the position of the
PT100. For some hours of the day, this sensor was exposed to sunscreen is, especially for surface cooling systems character-
sun radiation, which can be seen from some high temperatures ized by a limited cooling capacity.
in Figure 4. The results from this building also show the importance of
As can be noted from Tables 6 through 8, the office rooms
optimizing the control setting after the building is in operation.
are below the comfort range for long periods. From the For the offices, the temperatures were in most cases below the
measured water temperature in Figure 4, it can be noted that
upper level of the comfort range, but they did, in several cases,
on several days (June 27-July 3 and July25) the cooling was go below the comfort range.
not in operation. Even in the period June 27 to June 30, heating
was provided. This is caused by the central control, which,
Building 3
according to outside temperature and internal temperature in
the reference room, turns on and off the heating and cooling. In this building, 6500 m2 of active thermal slab systems
The control system has the capability of also using an individ- were installed for heating and cooling. The building has raised
ual room control. This is used in the present building for heat- floors for the installation of cables, only a limited area with
ing operation but not for cooling, which meant all offices suspended ceiling, and operable windows. Mechanical venti-
would get cooling if the reference room required cooling. lation is provided by a displacement system, where the supply
Instead, the local control should have been used so that in air is precooled or preheated to a temperature 1 to 3 degrees
rooms where the temperatures were low enough, the room below room temperature.

TABLE 4
Percentage of the Operative Temperature Change Distribution During a Working Day

Temperature Change Dur- Total for Rooms


ing a Working Day [°C] Hallway Room 304 Room 404 Room 414 304, 404, 414
<1 5.3 0 0 0 0.0
1-2 5.3 15.8 5.3 0 9.5
2-3 26.3 31.6 42.1 50 38.1
3-4 0 47.4 26.3 50 38.1
4-5 21.1 5.3 21.1 0 11.9
5-6 26.3 0 0 0 0.0
>6 15.8 0 5.3 0 2.4

TABLE 5
Percentage of Operative Temperature Distribution According to DIN 1946

Total for Rooms


Temperature Range [°C] Hallway Room 304 Room 404 Room 414 304, 404, 414
<20 3.5 2.2 2.6 3.5 2.7
20-22 44.2 50.7 27.0 47.0 41.2
22-25 39.5 46.5 68.1 46.1 54.1
25-26 7.8 0.5 2.2 2.4 1.7
26-27 3.3 0.0 0.0 0.6 0.2
>27 1.7 0.0 0.0 0.3 0.1

718 ASHRAE Transactions: Symposia


Figure 4 Temperature trends in the measured period for relevant parameters in a
room.

TABLE 6
Percentage of Operative Temperature Distribution During Working Time

Temperature Range
[°C] East West Inside Shading Outside Shading All
<20 4.7 16.1 10.2 10.5 9.9
20-21 6.0 14.2 8.5 10.8 10.0
21-22 9.3 20.7 12.2 16.2 15.5
22-23 20.7 23.5 18.0 23.9 23.1
23-24 29.5 14.8 16.6 24.5 23.4
24-25 17.4 7.1 15.9 10.7 12.1
25-26 7.6 2.4 9.2 3.2 4.5
26-27 2.3 0.4 4.1 0.1 0.9
27-28 1.2 0.5 2.5 0.1 0.4
28-29 0.8 0.2 1.5 0.0 0.1
29-30 0.3 0.1 0.6 0.0 0.0
>30 0.3 0.1 0.7 0.0 0.1

TABLE 7
Percentage of Operative Temperature Change Distribution During a Working Day

Temperature Change
During a Day [°C] East West Inside Shading Outside Shading All

<1 1.9 1.9 0.0 2.7 1.9


1-2 17.5 26.9 8.3 28.1 22.2
2-3 30.6 21.3 15.6 30.4 25.9
3-4 21.3 23.8 22.9 22.3 22.5
4-5 14.4 10.6 16.7 10.7 12.5
5-6 5.6 4.4 13.5 1.3 5.0
>6 8.8 11.3 22.9 4.5 10.0

ASHRAE Transactions: Symposia 719


Measurements have been conducted in two open space From Tables 9 to 11, it can be seen that temperatures on
offices on the 4th and 5th floors. All measurements have been the 5th floor are higher than those on the 4th floor. This is
done by means of the globe thermometer probes (Table 2) with because the two floors are connected by an open stairway in
the exception of the middle place on the 5th floor measured the middle of the landscape offices. Therefore, some of the
during the 1999 campaign; here, the operative temperature convective part of the internal loads on the 4th floor (people,
was measured by means of the elliptic sensor (Table 2). equipment, sun) will rise to the 5th floor and increase the inter-
Measurements have been made during August 1999, from nal load there.
middle June till middle October 2000, and from December
It can be noted that on some days, the temperature in the
2000 till January 2001. The outside temperature was also
morning is on the cool side. As no subjective evaluations were
measured. The water supply temperatures were controlled in
made, it is not possible to determine if this caused a real
range of 19°C to 23°C, from summer to winter according to the
comfort problem or not. The low temperatures could probably
outside temperature.
be avoided by decreasing the number of hours of cooling oper-
The system was only in operation from 18:00 until 10:00.
ation during the night.
Cooling Period. A sample of operative temperatures can
be seen in Figure 5 for a typical warm working week. From Heating Period. A sample of operative temperature can
Table 9, it appears that around 95% of the total working time be seen in Figure 6 for a typical working week in heating
operative temperatures are between 21°C and 26°C. From conditions. From Table 12, it can be seen that operative
Table 10, it can be noted that the change of temperature during temperatures are for most of the time in the comfort range
working time is for all of the offices below 4°C, with the suggested by the existing standards. Also, the daily change in
exception of the office placed at the 5th floor west-oriented, the operative temperature (Table 13) is limited to a value of
which exceeds 4°C during only 4% of the working hours. 4°C.

TABLE 8
Percentage of Operative Temperature Distribution According to DIN 1946 During Working Time

Temperature Range
[°C] East West Inside Shading Outside Shading All
<20 4.7 16.1 10.2 10.5 9.9
20-22 15.3 34.9 20.7 27.0 25.5
22-25 67.6 45.4 50.5 59.1 58.6
25-26 7.6 2.4 9.2 3.2 4.5
26-27 2.3 0.4 4.1 0.1 0.9
>27 2.5 0.8 5.3 0.1 0.6

Figure 5 Sample of temperature trend in a working week for cooling conditions in


Building 3.

720 ASHRAE Transactions: Symposia


TABLE 9
Percentage of Operative Temperature Distribution During Working Time

4th Floor
Temperature 4th Floor Window 5th Floor 5th Floor 5th Floor All Offices Except
Range [°C] Window East South Window West Window East Middle Meeting Room Middle
<20 0.0 1.2 0.0 0.0 0.0 0.0 0.2
20-21 1.3 6.9 0.4 0.1 2.6 13.3 4.4
21-22 9.9 27.6 2.1 1.4 17.8 22.4 12.7
22-23 34.8 40.6 10.8 8.1 30.6 34.1 25.7
23-24 39.2 22.3 27.8 26.7 19.8 22.0 27.6
24-25 14.7 1.4 36.4 36.9 22.2 7.7 19.4
25-26 0.1 0.0 18.4 21.7 7.0 0.5 8.1
26-27 0.0 0.0 3.7 5.2 0.0 0.0 1.8
27-28 0.0 0.0 0.3 0.0 0.0 0.0 0.1

TABLE 10
Percentage of Operative Temperature Change Distribution During in a Working Day

Temperature 4th Floor 5th Floor


Change During a 4th Floor Window Window 5th Floor 5th Floor All Offices
Day [K] Window East South West Window East Middle Meeting Room Except Middle
<1 8.6 5.7 1.4 5.7 0.0 28.6 10.0
1-2 74.3 57.1 25.7 57.1 50.0 45.7 52.0
2-3 15.7 32.9 51.4 32.9 50.0 22.9 31.2
3-4 1.4 2.9 17.1 2.9 0.0 2.9 5.4
4-5 0.0 1.4 1.4 1.4 0.0 0.0 0.8
5-6 0.0 0.0 2.9 0.0 0.0 0.0 0.6
>6 0.0 0.0 0.0 0.0 0.0 0.0 0.0

TABLE 11
Percentage of Operative Temperature Distribution According to DIN1946 During Working Time

4th Floor 5th Floor


Temperature Range 4th Floor Window Window 5th Floor 5th Floor All Offices
[°C] Window East South West Window East Middle Meeting Room Except Middle
<20 0.0 1.2 0.0 0.0 0.0 0.0 0.2
20-22 11.2 34.5 2.5 1.4 20.4 35.7 17.1
22-25 88.6 64.4 75.0 71.7 72.6 63.8 72.7
25-26 0.1 0.0 18.4 21.7 7.0 0.5 8.1
26-27 0.0 0.0 3.7 5.2 0.0 0.0 1.8
>27 0.0 0.0 0.4 0.0 0.0 0.0 0.1

ASHRAE Transactions: Symposia 721


Figure 6 Sample of temperature trends, in a working week for heating conditions in
Building 3.

TABLE 12
Percentage of Operative Temperature Distribution During Working Time

Temperature Range 4th Floor 4th Floor 5th Floor 5th Floor
[°C] Window East Window South Window West Window East Meeting Room All Offices
<20 0.0 11.0 0.1 0.0 0.0 2.2
20-21 16.9 38.0 10.4 0.9 2.6 13.8
21-22 38.4 37.2 23.5 17.2 27.2 28.7
22-23 40.6 13.6 38.9 42.5 37.6 34.6
23-24 4.1 0.3 25.3 37.4 32.5 19.9
24-25 0.0 0.0 1.7 2.0 0.0 0.7

TABLE 13
Percentage of Operative Temperature Change Distribution During in a Working Day

Temperature Change 4th Floor 4th Floor 5th Floor 5th Floor
During a Day [K] Window East Window South Window West Window East Meeting Room All Offices
<1 16.7 19.4 2.8 11.1 11.1 13.3
1-2 69.4 30.6 25.0 75.0 75.0 52.2
2-3 13.9 44.4 52.8 13.9 13.9 29.4
3-4 0.0 5.6 19.4 0.0 0.0 5.0
>4 0.0 0.0 0.0 0.0 0.0 0.0

Except for 4th floor south, the measured operative two hours of occupancy, the supply temperature was again
temperatures are inside the recommended comfort range; in decreased below room temperature.
this position, 11% of the time the temperature dropped below
20°C. The building has an additional heating system installed, Building 4
which, however, has not been in operation. The basic heating The fourth building is located in Milan (Italy). It is a
is made by the activated concrete slab system. During the conference building designed by a renovation of an old farm.
winter, however, the supply air temperature increased above It is naturally ventilated and has a floor heating/cooling
the room temperature during the morning hours. After one to system. Measurements were carried out in the second floor

722 ASHRAE Transactions: Symposia


and the third floor during July 2001. The third floor is a room the heating period (winter) and one for the cooling period
smaller than the second floor, which is an open space. (summer). These ranges may be appropriate for the design of
In Figure 7, the trend of relevant parameters can be seen. systems (heating-cooling capacity), but for a comfort evalua-
As can be noticed, temperatures are, for most of the time, in the tion, a certain variation of clothing according to outside
comfort range and never go over 27°C (Table 15). Also, the temperatures should be taken into account. Therefore, in the
daily change in the operative temperature (Table 16) is always present analysis, no attempts have been made to calculate how
less than 2°C, which is an optimal situation. Temperatures in many hours the operative temperatures were outside the spec-
the second level are always lower than the ones in the third ified comfort range.
level (Table 15 and 17) and this is mainly due to the fact that
all the walls and ceiling of the third floor are external and
CONCLUSIONS
exposed to sunshine. Moreover, the two rooms are connected
by a staircase, which allows convection between the two levels The four examples show that surface heating and cooling
(warm air upstairs, cool air downstairs). The rooms were not of office buildings is not only theory, but will also work in
generally occupied during the measurements except for a practice.
couple of days on the second floor.
In all four buildings, the measured operative temperatures
General Discussion specified in existing standards were only above the comfort
range during the summer period (> 26°C) for a few hours, even
By long-term evaluation of measurements, it can be
with outside temperatures above 30°C.
argued which comfort criteria should be used for the evalua-
tion. Most standards for thermal comfort give an operative The operative temperature variation during a working day
temperature range based on a fixed clothing-activity level for was, in most cases, below 3 to 4 K.

TABLE 14
Percentage of Operative Temperature Distribution According to DIN1946 During Working Time

Temperature Change 4th Floor 4th Floor 5th Floor 5th Floor
During a Day [°C] Window East Window South Window West Window East Meeting Room All Offices
<20 0 11 0.1 0 0 2.2
20-22 55.3 75.1 34 18.1 29.9 42.5
22-25 44.7 13.9 65.9 81.9 70.1 55.3
>25 0 0 0 0 0 0

Figure 7 Temperature trends in the measured period for relevant parameters in the
rooms for Building 4.

ASHRAE Transactions: Symposia 723


TABLE 15 TABLE 16
Percentage of Operative Temperature Distribution Percentage of Operative Temperature Change
During Working Time Distribution During in a Working Day

2nd Floor Temperature 2nd Floor


Temperature Window 3rd Floor Change During a Window 3rd Floor
Range [°C] North Center Mean Day [K] North Center Mean
<20 33.7 0.0 16.8 <1 100.0 97.4 98.7
20-21 21.6 15.2 18.4 1-2 0.0 2.6 1.3
21-22 18.1 20.0 19.0 >2 0.0 0.0 0.0
22-23 5.7 17.8 11.7
TABLE 17
23-24 1.0 15.6 8.3 Percentage of Operative Temperature Distribution
24-25 20.0 11.4 15.7 According to DIN1946 During Working Time
25-26 0.0 1.6 0.8 2nd Floor
26-27 0.0 18.4 9.2 Temperature Window 3rd Floor
Range [°C] North Center Mean
>27 0.0 0.0 0.0
<20 33.7 0.0 16.8
In all four buildings, the operative temperature in the
20-22 39.7 35.2 37.5
morning at several workplaces was on the cool side. As the
subjective evaluation is missing, it is not possible to determine 22-25 26.7 44.8 35.7
if this caused a real comfort problem. Using existing interna- 25-26 0.0 1.6 0.8
tional standards, such as ISO 7730 or CR 1752, these spaces
would be judged as cool during several days. This could be 26-27 0.0 18.4 9.2
avoided by decreasing the hours of cooling during the night. >27 0.0 0.0 0.0
Before revision of the international standards how to
make long-term evaluations must be carefully discussed. It 710. Atlanta: American Society of Heating, Refrigerat-
seems inappropriate to use the same clothing level for the ing and Air-Conditioning Engineers, Inc.
whole summer period from May to September. ISO. 1998. ISO 7726-1998, Ergonomics of the thermal envi-
ronment—Instruments for measuring physical quanti-
REFERENCES ties. Geneva: International Organization for
Standardization.
ASHRAE. 1994. ANSI/ASHRAE Standard 55-1994, Thermal
ISO. 1994. ISO 7730-1994, Moderate thermal environ-
environmental conditions for human occupancy.
ments—Determination of the PMV and PPD indices and
Atlanta: American Society of Heating, Refrigerating
specification of the conditions for thermal comfort.
and Air-Conditioning Engineers, Inc.
Geneva: International Organization for Standardization.
Brunello, P., G. Di Gennaro, M. De Carli, and R. Zecchin.
Knudsen, H.N., et. al. 1989. Thermal comfort in passive
2001. Mathematical modelling of radiant heating and
cooling with massive thermal slab. Proceedings of Solar Buildings. Copenhagen: Internal report, Technical
Clima 2000, Naples. University of Denmark.
CEN. 1998. CR 1752, Ventilation for Buildings: Design Cri- Koschenz, M., and B. Lehmann. 2000. Thermoaktive Bau-
teria for the Indoor environment. Brussels: CEN. teilsysteme tabs. Zürich: ISBN 3-905594-19-6.
De Carli, M., F. Peron, P. Romagnoni, and R. Zecchin. 2000. Meierhans, R.A. 1996. Room air conditioning by means of
Computer simulation of ceiling radiant heating and overnight cooling of the concrete ceiling. ASHRAE
cooling panels and comfort evaluation. Proceedings of Transactions 102(2). Atlanta: American Society of
Healthy Buildings, Helsinki. Heating, Refrigerating and Air-Conditioning Engineers,
De Carli, M., and B.W. Olesen. 2001. Field measurements of Inc.
thermal comfort conditions in buildings with radiant Meierhans, R.A., and B.W. Olesen. 1999. Betonkernaktivier-
surface cooling systems. Proceedings of Clima 2000, ung. ISBN 3-00-004092-7.
Naples. Michel, E., and J.P. Isoardi. 1994. Cooling floor. Proceed-
DIN. 1994. DIN 1946-1994, Raumlufttechnik Teil 2. Berlin: ings of Clima 2000, London.
Deutsches Institut für Normung. Missenard, F.A. 1959. Le chauffage et le refraichissement
Hauser, G., Ch. Kempkes, and B.W. Olesen. 2000. Computer par rayonnement. Editions Eyrolles, Paris.
simulation of hydronic heating/cooling system with Olesen, B.W. 1997. Possibilities and limitations of radiant
embedded pipes. ASHRAE Transactions 106(1): 702- floor cooling. ASHRAE Transactions 103(1). Atlanta:

724 ASHRAE Transactions: Symposia


American Society of Heating, Refrigerating and Air- can Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. Conditioning Engineers, Inc.
Olesen, B.W. 2000. Cooling and heating of buildings by acti- Shoemaker, R.W. 1954. Le chauffage par rannoyement. Edi-
vating the thermal mass with embedded hydronic pipe tions Eyrolles, Paris.
systems. Proceedings ASHRAE-CIBSE, Dublin. Simmonds, P., W. Gaw, S. Holst, and S. Reuss. 2000 Using
Olesen, B.W., E. Michel, F. Bonnefoi, and M. De Carli. radiant cooled floors to condition large spaces and main-
2000. Heat exchange coefficient between floor surface tain comfort conditions. ASHRAE Transactions, Part 1.
and space by floor cooling: Theory or a question of def- Atlanta: American Society of Heating, Refrigerating
inition. ASHRAE Transactions, Part 1. Atlanta: Ameri- and Air-Conditioning Engineers, Inc.

ASHRAE Transactions: Symposia 725

You might also like