You are on page 1of 9

Building and Environment 45 (2010) 1923e1931

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Air distribution in office environment with asymmetric workstation layout


using chilled beams
Hannu Koskela a, *, Henna Häggblom a, Risto Kosonen b, Mika Ruponen b
a
Finnish Institute of Occupational Health, Lemminkäisenkatu 14-18 B, 20520 Turku, Finland
b
Halton Oy, Niittyvillankuja 4, 01510 Vantaa, Finland

a r t i c l e i n f o a b s t r a c t

Article history: Air flow patterns and mean air speeds were studied under laboratory conditions representing a full scale
Received 28 October 2009 open-plan office. Three basic conditions were tested: summer, spring/autumn and winter. Chilled beams
Received in revised form were used to provide cooling, outdoor air supply and air distribution in the room. The heat sources had
6 February 2010
a notable influence on the flow pattern in the room causing large scale circulation and affecting the
Accepted 9 February 2010
direction of inlet jets. The maximum air speed in the occupied zone was higher than the
recommendations. The mean air speed was also high on at the floor level but low on at the head level.
Keywords:
The air speed was highest in the summer case under high cooling load. Results indicate that especially
Air distribution
Chilled beam
with high heat loads, it is difficult to fulfill the targets of the existing standards in practice. Two main
Thermal comfort sources of draught risk were found: a) downfall of colliding inlet jets causing local maxima of air speed
Office environment and b) large scale circulation caused by asymmetric layout of chilled beams and heat sources. The first
CFD-simulation phenomenon can cause local draught risk when the workstation is located in the downfall area. The flow
Full-scale measurements pattern is not stable and the position of draught risk areas can change in time and also due to changes in
room heat sources. The second phenomenon can cause more constant high air speeds on at the floor
level. CFD-simulation was able to predict the general flow pattern but somewhat overestimated the air
speed compared to measurements.
Ó 2010 Elsevier Ltd. All rights reserved.

1. Introduction lighting, the internal heat load per floor area is 25 W/m2. When the
occupant density is doubled to 6 m2/person, the internal heat load
Organisational changes in most companies are continuous and becomes 50 W/m2.
require flexible changes in work methods and workspaces. The The external heat load comes from direct and diffuse solar load
traditional one person office areas, or cells, and open offices, or and heat leakage through the windows. It depends on several
hives, seen in traditional offices are today changing into spaces that factors including the time of year, orientation of the office, solar
are more suited to team work, referred to as dens or clubs [1]. shading of the building, window type, etc. During summer period,
In addition to this, information technology contributes to inde- the external heat load can be higher than the internal load espe-
pendence of time and location, transforming offices more into cially, if the building has large windows.
meeting places for sharing information. The office space must be In order to control the indoor temperature, the office has to be
utilised efficiently, and therefore a dedicated workstation is no cooled by air conditioning. Cooling can be realized with different
longer deemed necessary for a worker who spends only a few hours techniques, basically either by all-air or air-water systems. One
a day at the office. Working at several workstations and at customer common solution especially in the Nordic countries is to use active
sites is becoming more common. chilled beams. They are induction devices that combine supply air
Efficiency demands have led to increased density of the work- with cooling of re-circulated room air. Common to all these solu-
stations in modern offices. This development has also increased tions is that with high cooling loads, large amounts of cool air
internal heat loads in offices. The heat load from an office work- (either supply or room air) has to be blown into the office space.
station typically comes from PC, person and lighting. If we consider The higher the cooling load, the higher becomes the risk of draught.
a moderate occupant density of 12 m2/person and assume heat With isothermal supply air, the room air flow pattern is mainly
loads of 80 W from person, 100 W from PC and 120 W from controlled by the supply jets. From the design point of view, the
flow pattern can be predicted by jet formulas and diffuser throw
* Corresponding author. Tel.: þ358 30 4741. lengths. When the heat load in the room increases, the buoyancy
E-mail address: hannu.koskela@ttl.fi (H. Koskela). forces start to affect the flow pattern. The cool supply jets can

0360-1323/$ e see front matter Ó 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.buildenv.2010.02.007
1924 H. Koskela et al. / Building and Environment 45 (2010) 1923e1931

separate from the ceiling and negative buoyancy accelerates the environment. The study is based on measurements in a full scale
downward flow of cool air. On the other hand, warm upward air laboratory office module. CFD-simulation was carried out in
flows are created by heat sources. The interaction of cool and warm order to analyze the flow pattern and predict the thermal
air flows makes the room flow pattern more complex and more conditions. The effect of typical heat loads during different seasons
difficult to predict and control. was studied.
Müller et al. studied the effect regularly spaced heat sources on
room flow pattern by laboratory measurements and CFD- 2. Methods
simulation [2]. They found that the increase of heat load first led
to an unstable flow pattern until further increase created a new The experiments were carried out in environmental chamber at
stable condition dominated by buoyancy forces. The maximum the Finnish Institute of Occupational Health in Turku, Finland. The
velocity in the occupied zone increased with the heat load in their test room, having a floor area of 33.6 m2, is shown in Fig. 1. Cooling
measurements. They concluded that maximum velocity exceeds and air distribution in the room was realized with active chilled
0.2 m/s when the heat load is higher than 60 W/m2. beams. The room is built to represent a typical building module of
It has not generally been acknowledged that the convection a modern flexible office building. The width of the module is
flows caused by thermal loads may significantly affect the flow defined by the distance between the construction beams of the
range produced by the room devices in use. Kosonen et al. studied building; typically 8.1 m. The division of the windows and instal-
the effect of plumes from heat sources on the supply air flow lation of chilled beams enables walls to be built in several locations.
pattern from chilled beams [3]. They found that plumes from This paper presents the results of experiments and simulations
workstations were able to turn the supply jets and change the flow without separating walls.
pattern notably. The point of occurrence of the maximum speed in One wall of the test room had six windows of size 1.22 m  1.47 m.
the occupied zone depends on the thermal effect and location of Their surface temperature was controlled by blowing air into the
the thermal load as well as on the momentum flux and on the flow chamber behind them. Convective heaters were placed under the
pattern with respect to the convection flow. windows and were only used in the winter test case.
The room air flow pattern in cooling conditions depends on the The active chilled beam model Halton CCE was selected to
relative locations of air distribution units and heat sources. In ideal represent a typical unit with exposed installation in the room. In
conditions, the air distribution units and workstations would be the device, outdoor air supply is combined with cooling of
placed symmetrically, which would make it easier to control the re-circulated room air. Outdoor air supply is typically introduced
conditions in workstations. In practice, the locations of air distri- through small nozzles inside of the beam. Outdoor air jets induce
bution and cooling units are usually designed based on the building room air through a heat exchanger, where it is cooled and the
modules. In a flexible office building, the space can either be mixture (referred as inlet jets) is blown into the room through
divided to rooms by adding walls, or left as an open-plan office. The supply air openings. The flow rate of induced room air is usually
installations should be designed is such way that this flexibility is much higher than the outdoor air flow rate. The heat exchanger
possible. consists of a cooling coil, which is cooled by water flow. In this case,
The workstation layout is not necessarily based on the building the inlet jets are blown from inlet jet openings in the upper surface
module division and is therefore often asymmetric compared to the of the beam. The supply of inlet jets creates plane jets to both sides
air distribution. When the office layout is changed, the ventilation of the beam that normally attach to the ceiling. Fig. 2 shows the
flow pattern should also be adjusted to avoid draught problems in operation principle of an active chilled beam.
workstations. With a high office churn rate, the adjustments are not The chilled beams were installed asymmetrically in the room in
always conducted and the thermal comfort in individual worksta- the centreline of every second window. The distance from the
tions can differ notably. ceiling was 0.15 m. The dimensions of the beams were 3.3 m 
The purpose of this study was to characterize the flow pattern 0.41 m, height 0.18 m. The length of the inlet slot was 3.0 m and it
and thermal conditions in a typical flexible open-plan office was located symmetrically in relation to the centreline of the room.

Fig. 1. Dimensions and layout of the test room from the corresponding CFD-model.
H. Koskela et al. / Building and Environment 45 (2010) 1923e1931 1925

Fig. 2. Operating principle of the active chilled beam.

The test room had eight workstations arranged in two groups. where Ta is the air temperature, V is the mean air speed (0.05 m/s)
The persons were simulated with painted cylinders (height 1.1 m, and Tu is the turbulence intensity (10%  Tu  60%).
diameter 0.3 m) containing 2 light bulbs of total 80 W of heat
power. Each workstation had a PC under the table with power
3. Results
consumption adjusted to 90 W. Three lamps with power
consumption of 120 W each were installed between the chilled
3.1. Test cases
beams at height of 2.3 m.
The measurements of air velocity were carried out by using
Three test cases were measured in the laboratory and simulated
ultrasonic anemometers (Kaijo Denki WA-390, accuracy  0.02 m/s),
with CFD:
moved by an automated traversing system. The averaging time in
each measurement point was 60 s. The measurement grid density
1. Summer case with 100 W/m2 cooling load (warm windows and
was 0.1 m  0.1 m. Additional measurements were done using
direct solar heat load)
Dantec 54N10 flow analyzer with hot sphere sensors. The locations
2. Spring/autumn case with 45 W/m2 cooling load (cool windows)
of the measurement planes were selected to cover four workstations
3. Winter case with 45 W/m2 (cold windows and heaters under
in the central part of the room. The measurements heights were
them)
0.1 m and 1.2 m. Measurement height 1.2 m was used with the
automated traversing system instead of the standard height 1.1 m
In all cases, the internal heat loads were the same. Direct solar
because of obstacles.
load was simulated by placing heater panels (size 1.02 m  0.55 m,
The flow pattern was visualized using smoke and video recor-
height 0.05 m) on the floor in the middle section shown in Fig. 1.
ded during experiments. The cooling power of the chilled beams
The heaters under the windows in the winter test case had
was determined by measuring the cooling water flow rate and the
dimensions of 1.2 m  0.4 m  0.1 m. They produced mainly
rise of water temperature in the heat exchanger.
convective heat load due to stainless steel covering on all vertical
Recommendations for air speed and draught rate (DR) are given
surfaces. The heat load from the window surfaces was estimated by
in several international and national documents. ISO standard 7730
measuring the surface temperatures and calculating both radiation
(Table A.5) gives following design criteria for maximum mean
and convection heat output from Equations (2)e(6) [5].
air speed for office environment assuming turbulence intensity of
40% [4]:  
1 4
Q_ c ¼ hc ADT ¼ 1:07 DT 1=4 xtr þ 1:3DT 1=3 ðL  xtr Þ ADT;
3=4
(2)
 Category A (DR 10%): summer 0.12 m/s, winter 0.10 m/s L 3
 Category B (DR 20%): summer 0.19 m/s, winter 0.16 m/s where hc is the convective heat transfer coefficient, A is the window
 Category C (DR 30%): summer 0.24 m/s, winter 0.21 m/s surface area, L is the window height, DT is the temperature differ-
ence between window surface and room air and xtr is the transition
These maximum air speed values are based on the assumption point from laminar to turbulent flow. The transition point can be
that the room temperature is in the lower end of the corresponding calculated from
recommended temperature range. Draught rate is calculated from
Equation (1). " #1=3
109 n2
xtr ¼ ; (3)
ðDT=TÞg
DR ¼ ð34  Ta ÞðV  0:05Þ0:62 ð37$TuV þ 3:14Þ (1)

Table 1
Heat loads in the test cases.

Heat load Heat load Count 1. Summer 2. Spring/autumn 3. Winter


type (W) (W) (W) (W)
Persons 80 8 640 640 640
(cylinders)
Computers 90 8 720 720 720
Lights 120 3 360 360 360
Heaters 73 6 e e 437
Solar load 739 e e
(panels)
Windows 915 200 640
(calculated)

Total load 3374 1520 1517


Total load per 100 45 45
floor area
Fig. 3. Simplified model for the chilled beam.
1926 H. Koskela et al. / Building and Environment 45 (2010) 1923e1931

Fig. 4. Flow pattern in the summer case, experimental and CFD-results.

where n is the dynamic viscosity of air and g is the acceleration due with inflation layers on the room and heat source surfaces and had
to gravity. For cases with forced convection flow along the window 1 350 000 nodes. The grid density was 1 cm in the supply opening,
surface, the convective heat transfer coefficient hc was calculated 5 cm in the supply jet area and 10 cm in other parts of the room. No
from the Nusselt number Nu radiation model was used. The convective parts of the heat loads
were given to the surfaces as heat fluxes. The radiation part was
hc ¼ NuL=k ¼ 0:036Re0:8 Pr0:43 (4) distributed to room surfaces based on their approximate view
factors (6). The mean air speed was calculated from mean air
where k is the thermal conductivity of air and Re is the Reynolds velocity and turbulent kinetic energy using a correction formula
number reported by Koskela et al. [6].
The simplified model for the chilled beam was made of
Re ¼ VL=n (5) similar size as the actual device (Fig. 3). The outlets representing
where V is the air speed along the window. The radiation heat room air re-circulation openings were larger than in reality
exchange can be calculated from covering the whole vertical surfaces of the beam. The inlet
boundary conditions were determined based on the information
 
obtained from the manufacturer. The total inlet air flow rate was
Q_ r ¼ F1;2 A3s Tw
4
 Tr4 (6)
125 l/s per unit. The dimensions of the inlet slots were
where F1,2 is the view factor of the two surfaces, 3 is the emissivity 3.0 m  0.025 m. This gives an inlet momentum flow rate of
of window surface, s is the Stefan-Bolzmann constant and Tw and Tr 0.139 N per unit. The air flow was blown with velocity 0.927 m/s
are the surface temperatures of window and room. to an angle of 26 compared to the vertical direction. The inlet
The ratio of convection and radiation heat transfer was esti- jet temperature was defined to be the same for all beams. It was
mated to be 36%/64% in the summer case, 29%/71% in the spring/ calculated from Equation (7) to give the correct cooling power to
autumn case and 40%/60% in the winter case. These values are, the room.
however, rough estimates, because they are based on only a few
P
measurement points. Ti ¼ To  ; (7)
Q rcp
The heat loads in the three test cases are presented in Table 1.
where To is the mean room air temperature at outlets, P is the
3.2. CFD-modelling cooling power, Q is the inlet jet flow rate, r is the air density and cp
is the specific heat capacity of air. The cooling powers of the beams
The CFD-simulations were carried out by using Ansys CFX 11.0 may differ due to the different room air temperatures close to
software with SST turbulence model. The grid was unstructured induction outlets of the beams.

Fig. 5. Modelled air speed contours at 0.1 m (left) and 1.1 m (right) levels in the summer case.
H. Koskela et al. / Building and Environment 45 (2010) 1923e1931 1927

Fig. 6. Measured air speed contours at 0.1 m (left) and 1.2 m (right) levels in the summer case.

3.3. Summer case 100 W/m2 3.5. Winter case 45 W/m2

The main flow patterns detected from the smoke experiments The longitudinal circulation in the winter case was also weaker
are shown in Fig. 4 together with the flow patterns from the CFD- compared to the summer case. The heaters under the windows
simulation. Fig. 5 shows the distribution of air speed at two hori- created upward plumes as in the summer case. These plumes
zontal planes at 0.1 m and 1.1 m heights. Corresponding measure- turned the inlet jets somewhat towards the corridor wall in the
ment results in the central part of the office module are shown in experiments. This phenomenon was not seen in the CFD-results
Fig. 6 for air speed and in Fig. 7 for air temperature. (Figs. 12e15).
The inlet jets from the chilled beam first attached to the ceiling
and then collided with the jet from the neighbouring beam or 3.6. Mean and maximum air speed
with a wall. After the collision, the jets turned downwards to the
occupied zone. Local speed maxima from these collided jets can Figs. 16 and 17 show the comparison of measured and simulated
be seen in the modelled air speed contours at 1.1 m level in Fig. 5 mean and maximum air speeds in the three test cases. The values
and also in the corresponding measurement results at 1.2 m level were calculated in same area of the occupied zone in the central
in Fig. 6. part of the office module. The results are compared with the target
A clockwise circulation was formed in the room in the longitu- values of ISO 7730 for summer and winter conditions. The standard
dinal direction. This was caused by the asymmetric layout of the does not give target values of air speed for spring or autumn
chilled beams in relation to the workstations. The larger cooling conditions. Categories A, B and C correspond to draught risk levels
power in the right side of the room created stronger downward flow. of 10%, 20% and 30%. The mean air speed at the floor level was
In the left side of the room, the plumes from the workstation heat highest (0.24 m/s) in the summer case compared to the values of
sources were stronger than the downward buoyancy from the chilled 0.17e0.18 m/s in the other cases. The same was true with the
beam. This strong circulation caused high air velocities especially on maximum speed (0.29 m/s), but the difference to other test cases
at the floor level. The circulation was somewhat stronger in the CFD- was smaller. The CFD-simulation gave systematically higher speeds
simulation than detected in experiment (Figs. 4e7). in at the floor level.
The warm windows created upward thermal plumes that The measured mean air speed on at the 1.2 m level was low
continued along the ceiling colliding with the inlet jets from the (0.11e0.13 m/s) in all cases and CFD-simulation predicted it correctly.
chilled beams. This turned the inlet jets towards the corridor wall However, the local maximum values of air speed were notably higher,
and also caused a second circulation perpendicular to the main 0.27 m/s in the summer case and 0.20e0.21 m/s in the other cases.
circulation. This circulation was stronger in the experiments visu- CFD-results again overestimated the maximum air speed.
alized by smoke than in the CFD-results. Fig. 18 shows the measured mean and maximum draught rates in
the test cases calculated from Equation (1). The mean draught rates at
3.4. Spring/autumn case 45 W/m2 0.1 m level fall into ISO 7730 category B (20e30%) and at 1.2 m level
into category A or B. The maximum draught rates fall into category C,
The longitudinal circulation was weaker compared to the except in the summer case at the 0.1 m level, where it is above
summer case. This is natural, because of weaker buoyancy category C. The results differ from the velocity based categories in
forces. Also the downward plumes from the cool window were Figs. 16 and 17. In Fig. 18 the result is based on local temperature and
weak (Figs. 8e11). turbulence intensity values, whereas in Figs. 16 and 17 the categories

Fig. 7. Measured air temperature contours at 0.1 m (left) and 1.2 m (right) levels in the summer case.
1928 H. Koskela et al. / Building and Environment 45 (2010) 1923e1931

Fig. 8. Flow pattern in the spring/autumn case, experimental and CFD-results.

Fig. 9. Modelled air speed contours at 0.1 m (left) and 1.1 m (right) levels in the spring/autumn case.

are based on the lower value of recommended temperature range open, which made the large scale circulation flow along the floor
and the turbulence intensity is assumed to be 40%. possible. In real offices there are usually more flow obstacles, which
prevent the large scale circulation and reduce the air speed. If the
4. Discussion screens block the flow totally under the tables, this type of circu-
lation is not possible.
Heat sources had a notable effect on the flow pattern of the The air speed measurements were carried out only in the central
office module. The main effect was the strong circulation in the part of the room in the occupied zone. This area was selected,
longitudinal direction of the room, which was caused by the because it was considered more representative to an open-plan
asymmetry of the heat loads and the cooling devices. The second office than the ends of the test room. It was not possible to cover
effect was the transverse circulation caused by the heat load of the the whole test room with measurements. In the CFD-simulations,
windows or the heaters below the windows. It had the effect of highest velocities were found in the area, where the cool air was
turning the inlet jets towards the inner wall. In this case, however, flowing downwards along the wall.
the transverse circulation was overridden by the stronger longitu- The CFD-simulation was able to predict the main features of the
dinal circulation. flow pattern in the room. However, the CFD-results typically
The office module had only few flow obstacles in the longitu- somewhat overestimated the air speed compared to the
dinal direction of the room. The space under the tables was mainly measurements. This is probably due to the inability of the steady

Fig. 10. Measured air speed contours at 0.1 m (left) and 1.2 m (right) levels in the spring/autumn case.
H. Koskela et al. / Building and Environment 45 (2010) 1923e1931 1929

Fig. 11. Measured air temperature contours at 0.1 m (left) and 1.2 m (right) levels in the spring/autumn case.

Fig. 12. Flow pattern in the winter case, smoke experiments and CFD-results.

Fig. 13. Modelled air speed contours at 0.1 m (left) and 1.1 m (right) levels in the winter case.

Fig. 14. Measured air speed contours at 0.1 m (left) and 1.2 m (right) levels in the winter case.
1930 H. Koskela et al. / Building and Environment 45 (2010) 1923e1931

Fig. 15. Measured air temperature contours at 0.1 m (left) and 1.2 m (right) levels in the winter case.

Fig. 16. Mean and maximum air speed in the measurement plane at 0.1 m level compared to ISO 7730 design criteria.

Fig. 17. Mean and maximum air speed in the measurement plane at 1.2 m level compared to ISO 7730 design criteria (CFD-results at 1.1 m height).

Fig. 18. Mean and maximum draught rates in the measurement planes at 0.1 m and 1.2 m levels. ISO 7730 categories A, B and C correspond to draught rates 10%, 20% and 30%.
H. Koskela et al. / Building and Environment 45 (2010) 1923e1931 1931

state RANS-simulation to correctly describe the time-dependent room is not stable and the position of draught risk areas can change
fluctuations of the flow pattern. Therefore, the buoyancy induced in time and also due to changes in room heat sources. The second
flows develop stronger than in reality. The convergence in all the phenomenon can cause more constant high air speeds on at the
CFD-simulation cases was poor due to the fluctuating flow field. floor level. In practice, offices often have obstacles on the floor,
Therefore, the flow pattern of the CFD-results was dependent on reducing or blocking such strong circulation flows.
the truncation point of the iteration. CFD-simulation was able to predict the general flow pattern but
somewhat overestimated the air speed compared to measurements.
5. Conclusions
Acknowledgements
The heat sources had a notable influence on the flow pattern in
the room causing large scale circulation and affecting the direction The financial support of National Technology Agency of Finland
of inlet jets. The maximum air speed in the occupied zone was high is greatly appreciated.
compared to the recommendations. The mean air speed was also
high on at the floor level but low on at the head level. The air speed
References
was highest in the summer case with high cooling load. Results
indicate that especially with high heat loads, it may be difficult to [1] Flexibility Ltd., Cambridge, UK, at, http://www.flexibility.co.uk/.
fulfill the targets of the existing standards in open-plan offices in [2] Müller D, Gores I, Zielinski R. Impact of the thermal load on the room airflow
practice. pattern. In: Proceedings of Roomvent 2004, 9th International Conference on Air
Distribution in Rooms; September 5e8 2004, Coimbra, Portugal.
Two main causes of draught risk were found: [3] Kosonen R, Melikov A, Yordanova B, Bozkhov L. Impact of heat load distribution
and strength on airflow pattern in rooms with exposed chilled beams. In:
a) downfall of colliding inlet jets causing local maxima of air Proceedings of Roomvent 2007, 10th International Conference on Air Distri-
bution in Rooms, 13e15 June 2007, Helsinki, Finland. FINVAC 2007.
speed and
[4] ISO. ISO standard 7730, ergonomics of the thermal environment e analytical
b) large scale circulation caused by asymmetric room layout of determination and interpretation of thermal comfort using calculation of the
chilled beams and heat sources. PMV and PPD indices and local thermal comfort criteria. Genève: International
Organisation for Standardisation; 2005. 52 p.
[5] Mills AF. Heat and mass transfer. USA: Richard D. Irwin Inc; 1995.
The first phenomenon can cause local draught risk if the [6] Koskela H, Heikkinen J, Niemelä R, Hautalampi T. Turbulence correction for
workstation is located in the downfall area. The flow pattern in the thermal comfort calculation. Building and Environment 2001;36(2):247e55.

You might also like