You are on page 1of 45

DOC. NO.

: R1713001-M1016-51-0000-0013

JOB NO.: AATH1301

DEVICE DATASHEET (For Storage Tank)

PROJECT: LINEAR ALKYL BENZENE PROJECT

LOCATION : SRIRACHA, THAILAND

OWNER : LABIX COMPANY LIMITED

PO NO.: R1713001-PO-M1016

A2 Oct. 5, 15 Final Punlop M. J.H.Lee B.O.Lee


A1 July 22, 14 For Approval Punlop M. J.H.Lee B.O.Lee
A June 28, 14 For Approval Punlop M. J.H.Lee B.O.Lee

Rev. DATE DESCRIPTION PREPARED CHECKED APPR'D

BJC Heavy Industries PCL.


Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-3665 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 10 m
Tank Hight or Length, H 8.1 m
Tank Volume, Vtk 636 m3 Use maximum capacity
Pump-in Rate, Vpf 100.0 m3/h
Latitude 23 ° Below 42°
Design Pressure 0.637 kPa(g) (= 63.7 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 254 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 100.0 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 106.7 Nm3/h

Total Normal Required Outbreathing 206.7 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 254 m2
Emergency Outbreathing, q 19506 Nm3/h

Corrected Emergency Outbreathing, q 19463 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58201 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.1 m
Tank Hight or Length, H 6 m
Tank Volume, Vtk 175 m3 Use maximum capacity
Pump-in Rate, Vpf 19.2 m3/h
Latitude 23 ° Below 42°
Design Pressure 103.4 kPa(g) (= 10340 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 115 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 19.2 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 33.5 Nm3/h

Total Normal Required Outbreathing 52.7 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 115 m2
Emergency Outbreathing, q 14631 Nm3/h

Corrected Emergency Outbreathing, q 14599 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58201 Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.1 m
Tank Hight or Length, H 6 m
Tank Volume, Vtk 175 m3 Use maximum capacity
Pump-Out Rate, Vpe 19.2 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 115 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 19.2 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 241.90 Nm3/h
User Input
Total Normal Required Inbreathing 261.1 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58202 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.6 m
Tank Hight or Length, H 7 m
Tank Volume, Vtk 239 m3 Use maximum capacity
Pump-in Rate, Vpf 19.2 m3/h
Latitude 23 ° Below 42°
Design Pressure 1.448 kPa(g) (= 144 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 145 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 19.2 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 44.3 Nm3/h

Total Normal Required Outbreathing 63.5 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 145 m2
Emergency Outbreathing, q 16142 Nm3/h

Corrected Emergency Outbreathing, q 16106 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58202 Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.6 m
Tank Hight or Length, H 7 m
Tank Volume, Vtk 239 m3 Use maximum capacity
Pump-Out Rate, Vpe 19.2 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 145 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 19.2 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 300.89 Nm3/h
User Input
Total Normal Required Inbreathing 320.1 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58203 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.7 m
Tank Hight or Length, H 6 m
Tank Volume, Vtk 212 m3 Use maximum capacity
Pump-in Rate, Vpf 26.1 m3/h
Latitude 23 ° Below 42°
Design Pressure 103.4 kPa(g) (= 10340 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 126 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 26.1 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 39.6 Nm3/h

Total Normal Required Outbreathing 65.7 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 126 m2
Emergency Outbreathing, q 15606 Nm3/h

Corrected Emergency Outbreathing, q 15572 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58203 Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 6.7 m
Tank Hight or Length, H 6 m
Tank Volume, Vtk 212 m3 Use maximum capacity
Pump-Out Rate, Vpe 19.2 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 126 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 19.2 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 275.86 Nm3/h
User Input
Total Normal Required Inbreathing 295.1 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58210 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 16 m
Tank Hight or Length, H 12 m
Tank Volume, Vtk 2413 m3 Use maximum capacity
Pump-in Rate, Vpf 16.0 m3/h
Latitude 23 ° Below 42°
Design Pressure 5.6 kPa(g) (= 560 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 459 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 16.0 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 354.3 Nm3/h

Total Normal Required Outbreathing 370.3 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 459 m2
Emergency Outbreathing, q 19910 Nm3/h

Corrected Emergency Outbreathing, q 19867 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58210 Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 16 m
Tank Hight or Length, H 12 m
Tank Volume, Vtk 2413 m3 Use maximum capacity
Pump-Out Rate, Vpe 16.0 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 459 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 16 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 1,515.90 Nm3/h
User Input
Total Normal Required Inbreathing 1,531.9 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58501 Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 10.9 m
Tank Hight or Length, H 11 m
Tank Volume, Vtk 1026 m3 Use maximum capacity
Pump-in Rate, Vpf 21.6 m3/h
Latitude 23 ° Below 42°
Design Pressure 1.44 kPa(g) (= 144 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 313 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 21.6 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 164.2 Nm3/h

Total Normal Required Outbreathing 185.8 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 313 m2
Emergency Outbreathing, q 19910 Nm3/h

Corrected Emergency Outbreathing, q 19867 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58501 Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 10.9 m
Tank Hight or Length, H 11 m
Tank Volume, Vtk 1026 m3 Use maximum capacity
Pump-Out Rate, Vpe 9.3 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 313 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 9.3 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 833.39 Nm3/h
User Input
Total Normal Required Inbreathing 842.7 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58510A/B Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 10 m
Tank Hight or Length, H 10.5 m
Tank Volume, Vtk 825 m3 Use maximum capacity
Pump-in Rate, Vpf 120.0 m3/h
Latitude 23 ° Below 42°
Design Pressure 5.6 kPa(g) (= 560 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 287 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 120.0 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 134.8 Nm3/h

Total Normal Required Outbreathing 254.8 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 287 m2
Emergency Outbreathing, q 19910 Nm3/h

Corrected Emergency Outbreathing, q 19867 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet

Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21


Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58510A/B Page : 2 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Inbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 10 m
Tank Hight or Length, H 10.5 m
Tank Volume, Vtk 825 m3 Use maximum capacity
Pump-Out Rate, Vpe 100.0 m3/h
Latitude 23 ° Below 42°
Avg. Storage Temp. 25 °C ≥25°C
VP range Vp≥Hexane

Ins. Thickness, lin 0 m


Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tanks: 4 W/m2-K)
Total surface area, Atts 287 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Inbreathing due to Liquid movement out 100 Nm3/h

Thermal Inbreathing
C-Factor 6.5
Reduction factor, Ri 1.00
Thermal inbreathing, Vit 715.00 Nm3/h
User Input
Total Normal Required Inbreathing 815.0 Nm3/h Calculated

NOTES

1. Hexane Vapor Pressure


25 C 0.208 kg/cm2A

KPQ-807-001(Rev.0) KSPC
Tank Venting Calculation Sheet
Project Name : LINEAR ALKYLBENZENE PROJECT Date : 14, Jul. 21
Client : BJC Heavy Industries PCL Prep'D : H.J.Jeong
Item Number : T-58511A/B Page : 1 of 2

API STD 2000 6th Edition, Calculation for max. flow rates for Normal Outbreathing and
Emergency Outbreathing
(Refer Section 4.3.2, 'Calculation of maximum flow rates for normal outbreathing & normal inbreathing)

A. Inputs
Tank Diameter, D 28 m
Tank Hight or Length, H 12.5 m
Tank Volume, Vtk 7697 m3 Use maximum capacity
Pump-in Rate, Vpf 450.0 m3/h
Latitude 23 ° Below 42°
Design Pressure 0.367 kPa(g) (= 63.7 mmH2O)
Ins. Thickness, lin 0 m
Insulation Type -
Selected Thermal Cond. Of Insulation, λin,s 0 W/m-K
Inside heat transfer coefficient, h 4 W/m2-K (Typical value for tank: 4 W/m2-K)
Latent Heat 80 kcal/kg (= 334,900 J/kg)
Mol. Weight 86.17 (Default = 86.17)
Inert Gas 0 m3/h (As per the Inst. D/S)
Protection Factor 1
Total surface area, Atts 804 m2
Insulated surface area, Ainp 0 m2 (Enter 0 if tank uninsulated)
Uninsulated

B. Calculations

Outbreathing due to liquid movement in. 450.0 Nm3/h

Thermal Outbreathing
Y-Factor 0.32
Reduction factor, Ri 1
Thermal Outbreathing, Vot 1006.5 Nm3/h

Total Normal Required Outbreathing 1456.5 Nm3/h

Emergency Outbreathing
Wetted Area, Atws 804 m2
Emergency Outbreathing, q 19910 Nm3/h

Corrected Emergency Outbreathing, q 19867 Nm3/h User Input


Calculated

NOTES

KPQ-807-001(Rev.0) KSPC
Pressure and/or Vacuum Relief Valve
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ NO. * PAGE 1 OF 2

GENERAL SPECIFICATION
1 TAG NO. OR ITEM NO. 582-PVV-200 582-PVV-201 582-PVV-202
2 QUANTITY 1 1 1
3 TANK NO. OR EQUIPMENT NO. T-58201 T-58202 T-58203
4 SERVICE
5 FLUID AND STATE N-PENTANE ISO-OCTANE N-PENTANE & ISO-OCTANE
6 FLASH / BOILING POINT ˚C > 38 > 38 > 38
7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70
8 DESIGN PRESSURE / VACUUM barg 1.034 -0.007584 0.01448 -0.007584 1.034 -0.007584
9 OPERATING PRESSURE / VACUUM barg 0.48 ATM 0.014
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS IN

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 API 2000 API 2000
14 FILLING FLOW RATE Nm3/h 19.2 19.2 26.1
15 TOTAL NORMAL REQUIRED OUTBREAHTING Nm3/h 52.70 63.50 65.70
15.1 CONTROL VALVE FAILURE Nm3/h TBA TBA N/A
16 VALVE OUTBREATHING CAPACITY Nm3/h 1810 849 3150
17 PRESSURE SET POINT barg 0.9 0.012 0.9
18 ALLOWABLE OVER PRESSURE barg 0.99 0.0132 0.99
19 EMPTYING FLOW RATE Nm3/h 19.2 19.2 19.2
20 TOTAL NORMAL REQUIRED INBREATHING Nm3/h 261.10 320.10 295.10
21 VALVE INBREATHING CAPACTIY Nm3/h 283 551 551
22 VACUUM SET POINT barg -0.0025 -0.0025 -0.0025
23 ALLOWABLE OVER VACUUM barg -0.005 -0.005 -0.005
24 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE TO THE ATMOSPHERE
25 SIZING WITH FLAME ARRESTER NO NO NO

PRESSURE AND/OR VACUUM RELIEF VALVE SPECIFICATION


26 MATERIALS
(A) BODY MATERIAL A216-WCB A216-WCB A216-WCB
(B) SEAT MATERIAL A351-CF8 A351-CF8 A351-CF8
(C) DISC MATERIAL SS304 SS304 SS304
(D) DIAPHRAGM MATERIAL FEP FEP FEP
(E) SPRING MATERIAL N/A N/A N/A
27 SIZE INLET/OUTLET 3" 4" 4"
28 FLANGE CONNECTION
(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150 ANSI CLASS 150
(B) TYPE OF FLANGE FACING RAISED FACE RAISED FACE RAISED FACE
29 MODEL KSBS KSBB KSBS
30 TYPE SPRING LOADED WEIGHT LOADED SPRING LOADED
31 SERVICE PRESSURE & VACUUM RELIEF PRESSURE & VACUUM RELIEF PRESSURE & VACUUM RELIEF

32 CONNECTION & SPARE PARTS


(A) GASKET NO NO NO
(B) BOLTS AND NUTS NO NO NO
(C) OTHERS NO NO NO
33 DRAWING NO. BS-80A-2001 BB-100A-2001 BS-100A-2001

NOTES
1) FLOW CAPACITY OF NO.16 & 21 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Pressure and/or Vacuum Relief Valve
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ NO. * PAGE 2 OF 2

GENERAL SPECIFICATION
1 TAG NO. OR ITEM NO. 582-PVV-120 585-PVV-120 585-PVV-200/201
2 QUANTITY 1 1 2
3 TANK NO. OR EQUIPMENT NO. T-58210 T-58501 T-58510A/B
4 SERVICE
5 FLUID AND STATE N-PENTANE AROMATICES HDROCARBON LINER ALKYL BENZENE
6 FLASH / BOILING POINT ˚C > 38 > 38 > 38
7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70
8 DESIGN PRESSURE / VACUUM barg 56 mbarg -6 mbarg 0.01448 -0.007584 56 mbarg -6 mbarg
9 OPERATING PRESSURE / VACUUM barg ATM ATM ATM
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS IN

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 API 2000 API 2000
14 FILLING FLOW RATE Nm3/h 16.0 21.6 120.0
15 TOTAL NORMAL REQUIRED OUTBREAHTING Nm3/h 370.30 185.80 254.80
15.1 CONTROL VALVE FAILURE Nm3/h TBA N/A N/A
16 VALVE OUTBREATHING CAPACITY Nm3/h 7216 1542 3820
17 PRESSURE SET POINT barg 0.05 0.012 0.05
18 ALLOWABLE OVER PRESSURE barg 0.055 0.0132 0.055
19 EMPTYING FLOW RATE Nm3/h 16.0 9.3 100.0
20 TOTAL NORMAL REQUIRED INBREATHING Nm3/h 1531.90 842.70 815.00
21 VALVE INBREATHING CAPACTIY Nm3/h 1952 1132 1132
22 VACUUM SET POINT barg -0.0025 -0.0025 -0.0025
23 ALLOWABLE OVER VACUUM barg -0.005 -0.005 -0.005
24 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE TO THE ATMOSPHERE
25 SIZING WITH FLAME ARRESTER NO NO NO

PRESSURE AND/OR VACUUM RELIEF VALVE SPECIFICATION


26 MATERIALS
(A) BODY MATERIAL A216-WCB A216-WCB A216-WCB
(B) SEAT MATERIAL A351-CF8 A351-CF8 A351-CF8
(C) DISC MATERIAL SS304 SS304 SS304
(D) DIAPHRAGM MATERIAL FEP FEP FEP
(E) SPRING MATERIAL N/A N/A N/A
27 SIZE INLET/OUTLET 8" 6" 6"
28 FLANGE CONNECTION
(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150 ANSI CLASS 150
(B) TYPE OF FLANGE FACING RAISED FACE RAISED FACE RAISED FACE
29 MODEL KSBB KSBB KSBB
30 TYPE WEIGHT LOADED WEIGHT LOADED WEIGHT LOADED
31 SERVICE PRESSURE & VACUUM RELIEF PRESSURE & VACUUM RELIEF PRESSURE & VACUUM RELIEF

32 CONNECTION & SPARE PARTS


(A) GASKET NO NO NO
(B) BOLTS AND NUTS NO NO NO
(C) OTHERS NO NO NO
33 DRAWING NO. BB-200A-2001 BB-150A-2001 BB-150A-2002

NOTES
1) FLOW CAPACITY OF NO.16 & 21 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Rim Vent with Flame Arrester
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ. NO. * PAGE 1 OF 1

GENERAL SPECIFICATION
1 TAG NO.- RELIEF VALVE
TAG NO.- FLAME ARRESTER
2 QUANTITY 1 1
3 TANK NO. OR EQUIPMENT NO. T-58202 T-58501
4 SERVICE
5 FLUID AND STATE ISO-OCTANE AROMATICES HDROCARBON

6 FLASH / BOILING POINT ˚C > 38 > 38


7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70
8 DESIGN PRESSURE / VACUUM barg 0.01448 -0.007584 0.01448 -0.007584
9 OPERATING PRESSURE / VACUUM barg ATM ATM
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 / EN12874 / ISO 16852 API 2000 / EN12874 / ISO 16852

14 FILLING FLOW RATE Nm3/h


15 TOTAL NORMAL REQUIRED OUTBREAHTING Nm3/h
16 VALVE OUTBREATHING CAPACITY Nm3/h 268 268
17 PRESSURE SET POINT barg 0.0025 0.0025
18 ALLOWABLE OVER PRESSURE barg 0.0038 0.0038
19 EMPTYING FLOW RATE Nm3/h
20 TOTAL NORMAL REQUIRED INBREATHING Nm3/h
21 VALVE INBREATHING CAPACTIY Nm3/h 246 246
22 VACUUM SET POINT barg -0.0025 -0.0025
23 ALLOWABLE OVER VACUUM barg -0.0038 -0.0038
24 EXPLOSION GAS GROUP NEC / IEC D / IIA D / IIA
25 TYPE OF FLAME ARRESTER DEFLAGRATION PROOF DEFLAGRATION PROOF
26 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE
27 SIZING WITH FLAME ARRESTER YES YES

PRESSURE/VACUUM RELIEF V/V WITH F/ARRESTER SPECIFICATION


28 MATERIALS
(A) BODY MATERIAL B26-319.F B26-319.F
(B) SEAT MATERIAL B26-319.F B26-319.F
(C) DISC MATERIAL SS304 SS304
(D) DIAPHRAGM MATERIAL FEP FEP
(E) FLAME ELEMENT MATERIAL SS316L SS316L
(F) SPRING MATERIAL N/A N/A
29 SIZE INLET/OUTLET 4" 4"
30 FLANGE CONNECTION
(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150
(B) TYPE OF FLANGE FACING FLAT FACE FLAT FACE
31 MODEL KSBBFI KSBBFI
32 TYPE WEIGHT LOADED WEIGHT LOADED
33 SERVICE PRESSURE & VACUUM RELIEF PRESSURE & VACUUM RELIEF

34 CONNECTION & SPARE PARTS


(A) GASKET NO NO
(B) BOLTS AND NUTS NO NO
(C) OTHERS NO NO
35 DRAWING NO. BBFI - 100A-1111 BBFI - 100A-1111

NOTES
1) FLOW CAPACITY OF NO.16 & 21 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Emergency Manhole Vent Cover
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ NO. * PAGE 1 OF 3

GENERAL SPECIFICATION
TAG NO. OR ITEM NO. 36-RV-102 582-RV-200 582-RV-201
2 QUANTITY 1 1 1
3 TANK NO. OR EQUIPMENT NO. T-3665 T-58201 T-58202
4 SERVICE
5 FLUID AND STATE LINEAR ALKYL BENZENE N-PENTANE ISO-OCTANE
6 FLASH / BOILING POINT ˚C > 38 > 38 > 38
7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70
8 DESIGN PRESSURE / VACUUM mbarg 6.37 -3.7 1.034 barg -0.007584 barg 0.01448 barg -0.007584
9 OPERATING PRESSURE / VACUUM mbarg ATM 0.48 barg ATM
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS IN

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 API 2000 API 2000
14 WETTED AREA m2 254 115 145
15 EMERGENCY OUTBREATHING Nm3/h 19,506 14,631 16,142
16 ENVIRONMENTAL FACTOR 1 1 1
17 CORRECTED OUTBREATHING Nm3/h 19,463 14,599 16,106
18 VALVE CAPACITY PRESSURE Nm3/h 26,036 19,450 26,885
VACUUM Nm3/h
19 SETTING PRESSURE / VACUUM mbarg 5.5 1.034 barg 0.01448 barg
20 ALLOWABLE OVER PRESS/VAC % 10 10 10
21 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE TO THE ATMOSPHERE

EMERGENCY VENT MANHOLE COVER SPECIFICATION


22 MATERIALS
(A) BODY MATERIAL A216-WCB A216-WCB A216-WCB
(B) DISC MATERIAL SS304 CARBON STEEL SS304
(C) DIAPHRAGM MATERIAL FEP/TEFLON FEP/TEFLON FEP/TEFLON
(D) WEIGHT MATERIAL CS N/A CS
(E) SPRING MATERIAL N/A SS304 N/A
23 SIZE (PRESSURE/VACUUM) 24" 24" 24"
24 FLANGE CONNECTION
(A) TYPE AND CLASS API 650 DRILLING('11 EDITION) API 650 DRILLING('11 EDITION) API 650 DRILLING('11 EDITION)
(B) TYPE OF FLANGE FACING FLAT FACE FLAT FACE FLAT FACE
25 MODEL KSEPK KSES KSEPK
26 TYPE WEIGHT LOADED SPRING LOADED WEIGHT LOADED
27 SERVICE PRESSURE RELIEF PRESSURE RELIEF PRESSURE RELIEF
28 CONNECTION & SPARE PARTS
(A) GASKET NO NO NO
(B) BOLTS AND NUTS NO NO NO
(C) OTHERS NO NO NO
29 DRAWING NO. EPK-600A-2001 ES-600A-2001 EPK-600A-2002

NOTES
1) FLOW CAPACITY OF NO.18 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Emergency Manhole Vent Cover
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ NO. * PAGE 2 OF 3

GENERAL SPECIFICATION
TAG NO. OR ITEM NO. 582-RV-202 582-RV-123 585-RV-123
2 QUANTITY 1 1 1
3 TANK NO. OR EQUIPMENT NO. T-58203 T-58210 T-58501
4 SERVICE
5 FLUID AND STATE N-PENTANE & ISO-OCTANE N-PENTANE AROMATICES HDROCARBON

6 FLASH / BOILING POINT ˚C > 38 > 38 > 38


7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70
8 DESIGN PRESSURE / VACUUM mbarg 1.034 barg -0.007584 barg 56.00 -6.0 0.01448 barg -0.007584
9 OPERATING PRESSURE / VACUUM mbarg 0.014 barg ATM ATM
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS IN

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 API 2000 API 2000
14 WETTED AREA m2 126 459 313
15 EMERGENCY OUTBREATHING Nm3/h 15,606 19,910 19,910
16 ENVIRONMENTAL FACTOR 1 1 10
17 CORRECTED OUTBREATHING Nm3/h 15,572 19,867 19,867
18 VALVE CAPACITY PRESSURE Nm3/h 19,450 49,525 26,885
VACUUM Nm3/h
19 SETTING PRESSURE / VACUUM mbarg 1.034 barg 56 0.01448 barg
20 ALLOWABLE OVER PRESS/VAC % 10 10 10
21 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE TO THE ATMOSPHERE

EMERGENCY VENT MANHOLE COVER SPECIFICATION


22 MATERIALS
(A) BODY MATERIAL A216-WCB A216-WCB A216-WCB
(B) DISC MATERIAL CARBON STEEL SS304 SS304
(C) DIAPHRAGM MATERIAL FEP/TEFLON FEP/TEFLON FEP/TEFLON
(D) WEIGHT MATERIAL N/A CS CS
(E) SPRING MATERIAL SS304 N/A N/A
23 SIZE (PRESSURE/VACUUM) 24" 24" 24"
24 FLANGE CONNECTION
(A) TYPE AND CLASS API 650 DRILLING('11 EDITION) API 650 DRILLING('11 EDITION) API 650 DRILLING('11 EDITION)
(B) TYPE OF FLANGE FACING FLAT FACE FLAT FACE FLAT FACE
25 MODEL KSES KSEPK KSEPK
26 TYPE SPRING LOADED WEIGHT LOADED WEIGHT LOADED
27 SERVICE PRESSURE RELIEF PRESSURE RELIEF PRESSURE RELIEF
28 CONNECTION & SPARE PARTS
(A) GASKET NO NO NO
(B) BOLTS AND NUTS NO NO NO
(C) OTHERS NO NO NO
29 DRAWING NO. ES-600A-2001 EPK-600A-2003 EPK-600A-2002

NOTES
1) FLOW CAPACITY OF NO.18 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Emergency Manhole Vent Cover
Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ NO. * PAGE 3 OF 3

GENERAL SPECIFICATION
TAG NO. OR ITEM NO. 585-RV-200/201 585-RV-230/231
2 QUANTITY 2 2
3 TANK NO. OR EQUIPMENT NO. T-58510A/B T-58511A/B
4 SERVICE
5 FLUID AND STATE LINER ALKYL BENZENE LINER ALKYL BENZENE
6 FLASH / BOILING POINT ˚C > 38 > 38
7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70
8 DESIGN PRESSURE / VACUUM mbarg 56.00 -6.0 6.37 -3.7
9 OPERATING PRESSURE / VACUUM mbarg ATM ATM
10 LATENT HEAT BTU/LB
11 MOLECULAR WEIGHT
12 INSULATION THICKNESS IN

VENTING CAPACITY REQUIREMENTS


13 CODE OR STANDARD API 2000 API 2000
14 WETTED AREA m2 287 804
15 EMERGENCY OUTBREATHING Nm3/h 19,910 19,910
16 ENVIRONMENTAL FACTOR 1 1
17 CORRECTED OUTBREATHING Nm3/h 19,867 19,867
18 VALVE CAPACITY PRESSURE Nm3/h 48,525 26,036
VACUUM Nm3/h
19 SETTING PRESSURE / VACUUM mbarg 56 5.5
20 ALLOWABLE OVER PRESS/VAC % 10 10
21 VENT GAS DISCHARGE TO TO THE ATMOSPHERE TO THE ATMOSPHERE

EMERGENCY VENT MANHOLE COVER SPECIFICATION


22 MATERIALS
(A) BODY MATERIAL A216-WCB A216-WCB
(B) DISC MATERIAL SS304 SS304
(C) DIAPHRAGM MATERIAL FEP/TEFLON FEP/TEFLON
(D) WEIGHT MATERIAL CS CS
(E) SPRING MATERIAL N/A N/A
23 SIZE (PRESSURE/VACUUM) 24" 24"
24 FLANGE CONNECTION
(A) TYPE AND CLASS API 650 DRILLING('11 EDITION) API 650 DRILLING('11 EDITION)
(B) TYPE OF FLANGE FACING FLAT FACE FLAT FACE
25 MODEL KSEPK KSEPK
26 TYPE WEIGHT LOADED WEIGHT LOADED
27 SERVICE PRESSURE RELIEF PRESSURE RELIEF
28 CONNECTION & SPARE PARTS
(A) GASKET NO NO
(B) BOLTS AND NUTS NO NO
(C) OTHERS NO NO
29 DRAWING NO. EPK-600A-2003 EPK-600A-2001

NOTES
1) FLOW CAPACITY OF NO.18 HAS BEEN TESTED USING THE AIR AT STANDARD CONDITON.(AIR DENSITY= 1, 15.56℃, 1 ATM)

Korea Steel Power Corp


Gauge Hatch Cover Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ. NO. * PAGE 1 OF 2

GENERAL SPECIFICATION

1 TAG NO. OR ITEM NO.

2 QUANTITY 1 1 1

3 TANK NO. OR EQUIPMENT NO. T-3665 T-58202 T-58210

4 SERVICE

5 FLUID AND STATE LINEAR ALKYL BENZENE ISO-OCTANE N-PENTANE

7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70

8 DESIGN PRESSURE / VACUUM mbarg 6.37 -3.7 0.01448 barg -0.007584 56.00 -6.0

9 OPERATING PRESSURE / VACUUM mbarg ATM ATM ATM

10 BREATHER VALVE SETTING PRESSURE mbarg

GAUGE HATCH COVER SPECIFICATION

11 MATERIALS

(A) BODY AND COVER/PADDLE MATERIAL A216-WCB A216-WCB A216-WCB

(B) SEAL GASKET MATERIAL TEFLON TEFLON TEFLON

12 SIZE 8" 8" 8"

13 FLANGE CONNECTION

(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150 ANSI CLASS 150

(B) TYPE OF FLANGE FACING RAISED FACE RAISED FACE RAISED FACE

14 MODEL KSGH KSGH KSGH

15 TYPE NON-SPARK & LOCK DOWN NON-SPARK & LOCK DOWN NON-SPARK & LOCK DOWN

FOOT OPERATED FOOT OPERATED FOOT OPERATED

16 CONNECTION & SPARE PARTS

(A) GASKET NO NO NO

(B) BOLTS AND NUTS NO NO NO

(C) OTHERS NO NO NO

17 DRAWING NO. GH-200A-2001 GH-200A-2001 GH-200A-2001

NOTES

Korea Steel Power Corp


Gauge Hatch Cover Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ. NO. * PAGE 2 OF 2

GENERAL SPECIFICATION

1 TAG NO. OR ITEM NO.

2 QUANTITY 1 2 2

3 TANK NO. OR EQUIPMENT NO. T-58501 T-58510A/B T-58511A/B

4 SERVICE

5 FLUID AND STATE AROMATICES HDROCARBON LINER ALKYL BENZENE LINER ALKYL BENZENE

7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70

8 DESIGN PRESSURE / VACUUM mbarg 0.01448 barg -0.007584 56.00 -6.0 6.37 -3.7

9 OPERATING PRESSURE / VACUUM mbarg ATM ATM ATM

10 BREATHER VALVE SETTING PRESSURE mbarg

GAUGE HATCH COVER SPECIFICATION

11 MATERIALS

(A) BODY AND COVER/PADDLE MATERIAL A216-WCB A216-WCB A216-WCB

(B) SEAL GASKET MATERIAL TEFLON TEFLON TEFLON

12 SIZE 8" 8" 8"

13 FLANGE CONNECTION

(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150 ANSI CLASS 150

(B) TYPE OF FLANGE FACING RAISED FACE RAISED FACE RAISED FACE

14 MODEL KSGH KSGH KSGH

15 TYPE NON-SPARK & LOCK DOWN NON-SPARK & LOCK DOWN NON-SPARK & LOCK DOWN

FOOT OPERATED FOOT OPERATED FOOT OPERATED

16 CONNECTION & SPARE PARTS

(A) GASKET NO NO NO

(B) BOLTS AND NUTS NO NO NO

(C) OTHERS NO NO NO

17 DRAWING NO. GH-200A-2001 GH-200A-2001 GH-200A-2001

NOTES

Korea Steel Power Corp


Slot Dipping Devices Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ. NO. * PAGE 1 OF 2

GENERAL SPECIFICATION

1 TAG NO. OR ITEM NO.

2 QUANTITY 1 1 1

3 TANK NO. OR EQUIPMENT NO. T-58201 T-58202 T-58203

4 SERVICE

5 FLUID AND STATE N-PENTANE ISO-OCTANE N-PENTANE & ISO-OCTANE

7 TEMPERATURE OPER. / MAX. ˚C 40 70 40 70 40 70

8 DESIGN PRESSURE / VACUUM mbarg 1.034 barg -0.007584 barg 0.01448 barg -0.007584 1.034 barg -0.007584 barg

9 OPERATING PRESSURE / VACUUM mbarg 0.48 barg ATM 0.014 barg

10 BREATHER VALVE SETTING PRESSURE mbarg

GAUGE HATCH COVER SPECIFICATION

11 MATERIALS

(A) BODY AND COVER/PADDLE MATERIAL A216-WCB A216-WCB A216-WCB

(B) SEAL GASKET MATERIAL VITON VITON VITON

12 SIZE 4" 4" 4"

13 FLANGE CONNECTION

(A) TYPE AND CLASS ANSI CLASS 150 ANSI CLASS 150 ANSI CLASS 150

(B) TYPE OF FLANGE FACING RAISED FACE RAISED FACE RAISED FACE

14 MODEL KSSD KSSD KSSD

15 TYPE SMAPLING & GUAGEING SMAPLING & GUAGEING SMAPLING & GUAGEING

GAS TIGHT GAS TIGHT GAS TIGHT

16 CONNECTION & SPARE PARTS

(A) GASKET NO NO NO

(B) BOLTS AND NUTS NO NO NO

(C) OTHERS NO NO NO

17 DRAWING NO. SD-100A-2001 SD-100A-2001 SD-100A-2001

NOTES

Korea Steel Power Corp


Slot Dipping Devices Specification Sheet
CLIENT BJC Heavy Industries PCL DOCUMENT NO. KSDO-1403A-0053
PROJECT LINEAR ALKYLBENZENE PROJECT REV. 1
INQ. NO. * PAGE 2 OF 2

GENERAL SPECIFICATION

1 TAG NO. OR ITEM NO.

2 QUANTITY 1

3 TANK NO. OR EQUIPMENT NO. T-58501

4 SERVICE

5 FLUID AND STATE AROMATICES HDROCARBON

7 TEMPERATURE OPER. / MAX. ˚C 40 70

8 DESIGN PRESSURE / VACUUM mbarg 0.01448 barg -0.007584

9 OPERATING PRESSURE / VACUUM mbarg ATM

10 BREATHER VALVE SETTING PRESSURE mbarg

GAUGE HATCH COVER SPECIFICATION

11 MATERIALS

(A) BODY AND COVER/PADDLE MATERIAL A216-WCB

(B) SEAL GASKET MATERIAL VITON

12 SIZE 4"

13 FLANGE CONNECTION

(A) TYPE AND CLASS ANSI CLASS 150

(B) TYPE OF FLANGE FACING RAISED FACE

14 MODEL KSSD

15 TYPE SMAPLING & GUAGEING

GAS TIGHT

16 CONNECTION & SPARE PARTS

(A) GASKET NO

(B) BOLTS AND NUTS NO

(C) OTHERS NO

17 DRAWING NO. SD-100A-2001

NOTES

Korea Steel Power Corp