You are on page 1of 16

MINDANAO STATE UNIVERSITY -

ILIGAN INSTITUTE OF TECHNOLOGY


COLLEGE OF ENGINEERING AND TECHNOLOGY
Andres Bonifacio Avenue, Tibanga, 9200 Iligan City, Philippines

THERMAL COMFORT EVALUATION OF ST. MICHAEL’S


CATHEDRAL CHURCH (ILIGAN CITY) FOR INSTALLATION OF
OPTIMIZED HVAC SYSTEM

Christian Jay A. Uayan


Jimmy A. Tizon
Joshua S. Faustino
Judy Mark T. Ortega
Vincent Rey A. Bandoles

In partial fulfillment to the course


ME 162: Air Conditioning Engineering

Napoleon A. Enteria, Ph.D


Professor
Department of Mechanical and Engineering Science
Abstract—The study recorded the indoor According to the handbook of ASHRAE
thermal environment of St. Michael’s Standard 55-2017 under Section 5 which
Cathedral Church and analyzed the variation discusses the conditions that provide thermal
of temperature and humidity with respect to comfort, there are six factors to be considered
the zone position and time of the day. A when defining conditions for acceptable thermal
systematic simulation of church model comfort: metabolic rate, clothing insulation, air
reflected the regions of high temperature and temperature, radiant temperature, air speed and
humidity and led to the proposal of a suitable humidity.
air distribution system. Common heating, ventilating and air-
conditioning (HVAC) systems nowadays are
configured just to decrease or increase
INTRODUCTION temperature for cooling and heating requirements
Background of the Study as well as decrease or increase the humidity for
In year 2019, Iligan City experienced a year dehumidifying or humidifying the moisture
average temperature of 28.33 ºC with highest in existing in air. Hence the researchers only
the month of May with an average of 31 ºC and focused to determine the appropriate temperature
year average humidity of 78.16 percent with 83 and humidity conditions for human comfort
percent as the highest in the month of January as although the air can further be filtered from
shown in the figures below. unwanted particulates and contaminants.

Figure 1: Iligan City Temperature Plot during 2019

Figure 3: Acceptable Ranges of Operative Temperature


and Humidity (ASHRAE Standard 55-1992)

Shown in the above figure is the acceptable


ranges of operative temperature and humidity for
people in typical summer and winter clothing
during light and primarily sedentary activity (≤
1.2 met). The ranges are considered at general
thermal comfort whereby the effects of thermal
radiation asymmetry, drafts, vertical air
temperature differences, and floor surface
temperatures are not covered, as how the local
thermal comfort is described.
Figure 2: Iligan City Humidity Plot during 2019
Statement of the Problem occupants, a process, or a product in the
It was reported that the average temperature space.
around Iligan City on 2019 is 28.33 ºC and this
indicates that the value did not fall on the Air Handler - contains heating and/or cooling
acceptable range even at the summer conditions coils, fans for moving the air, and filters.
of operative temperature, with value at maximum
of around 27 ºC. Besides, the 78.16 percent All-air System – the airstream provides both
average humidity is critical on the plot of relative energy and ventilation (as well as moisture
humidity for acceptable range. control) to the conditioned space
In response to this problem, the researchers
proposed an air distribution system for Iligan ASHRAE Handbook - consists of four volumes
City Cathedral Church that will significantly entitled HVAC Systems and Equipment,
improve the temperature as well as relative Fundamentals, Refrigeration, and HVAC
humidity and will be suited on the average Applications.
conditions for tropical season of the country.
Cleaning - implies filtering, although it also may
be necessary to remove contaminant gases or
Objectives of the Study
odors from the air.
The main goal is to design a promising air
distribution system that will mitigate the thermal Cooling - transfer of energy from a space, or from
discomfort experienced by the church-goers of air supplied to a space, to make up for the
St. Michael’s Cathedral. Specifically, it aims: energy being gained by that space.
1. To determine the variation of temperature Cooling Load - rate at which energy must be
and humidity of different locations of the removed from a space to maintain the
entire zone within the church. temperature and humidity at the design
2. To model the structure of the church such values.
that the indoor conditions can be
simulated and examined. Dehumidification - reducing the amount of water
vapor in an airstream for the purpose of
Significance of the Study maintaining desired humidity levels in a
conditioned space.
The study is driven to provide the blueprint
of an air conditioning system that will be Demand Charge - charge for maximum power or
beneficial to the church attendants and Catholic rate of use.
ministry of St. Michael’s Cathedral.
Heat Extraction Rate - rate at which energy is
Scope and Limitations removed from the space by the cooling and
dehumidifying equipment.
The vicinity considered in the conduct of the
study will encompass only to the indoor Heat Gain - rate at which energy is transferred to
environment of the church and does not include or generated within a space and has two
the outside surroundings. Furthermore, the study components: sensible heat and latent heat.
mainly focused on the air temperature and
humidity distribution among the six thermal Heating - to bring a space up to a higher
comfort conditions. temperature than existed previously or to
replace the energy being lost to colder
Definition of Key Terms surroundings by a space.
Air Conditioning – refers to the control of Humidifying - water vapor transferred to the
temperature, moisture content, cleanliness, heated supply air
air quality, and air circulation as required by
Latent Cooling - the energy involved in the Radiant Temperature
moisture removal only.
Radiant temperature refers to the amount of
Peak Demand Period – critical period when heat emitted by a body. Radiant heat can be
demand charges are the highest present from any sources such as the sun, light
bulb, wall surfaces, etc.
Sensible Heat Transfer - manifested solely in Radiant temperature asymmetry is calculated
raising or maintaining the temperature of the to determine the effect of radiant temperature on
air thermal comfort. ANSI/ASHRAE standard 55 set
the calculation at waist level in 0.6m (24 in.) in
Zone – a conditioned space under the control of
sitting position and 1.1m (43 in.) in standing
a single thermostat.
position. ANSI/ASHRAE recommended that the
radiant temperature asymmetry should not
exceed at the temperatures shown in Figure 4.
REVIEW OF THE RELATED LITERATURE

Thermal Comfort

Thermal comfort refers to individual’s state


of mind with regards to the satisfaction of the
thermal environment. Several factors are
considered in contributing thermal comfort, one
is from environmental factors and the other is Figure 4: Allowable Radiant Temperature Asymmetry
personal factors. Air Velocity
Environmental factors include the following Air velocity is described as the air movement
parameters: across an object. This is considered greatly since
heat can be transferred in air by convection. By
• Air temperature standards for average speed for occupant without
• Radiant temperature control, three limits are applied:
• Air velocity
a) Average air speed shall be 0.8 m/s (160 fpm)
• Humidity
for operating temperatures above 25.5 °C
While personal factors include the following: (77.9 °F).
b) At operating temperature between 23.0 °C
• Clothing insulation (73.4 °F) and 25.0 °C (77.9 °F), average air
• Metabolic heat speed can be calculated by determining the
curve shown in Figure 5 and using the
These factors may vary with time and as a equation:
result individual may feel uncomfortable when 𝑉𝑎 = 50.49 − 4.4047(𝑡0 ) + 0.096425(𝑡0 )2
entering a space as they experience different
environmental conditions. where unit of air speed and operating
temperature is in m/s and °C respectively. In
Air Temperature terms of fpm and °F units,
Air temperature determines the amount of
𝑉𝑎 = 31375.7 − 857.295(𝑡0 ) + 5.86288(𝑡0 )2
heat present in the air and measured either in
Fahrenheit (°F) or in Celsius (°C). To avoid c) Average air speed shall be 0.2 m/s (40 fpm)
thermal discomfort, ANSI/ ASHRAE set a at operating temperature below 23.0 °C (73.4
standard where the air temperature difference °F).
should not exceed 3°C (5.4°F) while sitting and
4°C (7.2°F) while standing.
Figure 5: Acceptable Ranges of t0 and va at 1.0 and 0.5 clo
Comfort Zones
Figure 6: Clothing Insulation Values for Typical
Humidity Ensembles

Humidity is defined as the amount of


moisture present in the air. High humidity means
that more saturated water vapor is present. For
humid weather or location, people tend to be
uncomfortable as less sweat evaporate for body
cooling.

According to Health and Safety Executive


(HSE), relative humidity has no major impact on
thermal comfort between 40% and 70%.
Humidity may be higher than 70% for non-
airconditioned workplaces or locations in which
weather from outdoors can influence. Indoor
environment has varying humidity depending on
wither drying process is present.

Clothing Insulation

ANSI/ASHRAE provides the values of


insulation to sensible heat through clothing and
garment, expressed in units of clo, shown in Figure 7: Garment Insulation Values
Figure 6 and 7.

Figure 8 shows added insulation when sitting


on chair which is only applicable for clothing
ensembles with standing insulation values of
between 0.5 clo and 1.2 clo.

Metabolic Rate

Metabolic rate is the rate at which chemical


energy is converted into heat and mechanical Figure 8: Added Insulation When Sitting on a Chair
energy individual activities, expressed in met.
Figure 9 shows different task with measured and the delivering method such as air handling
metabolic rate. equipment, fan coils, air ducts, and water pipes.

HVAC System Selection

System selection depends on three main


factors including the building configuration, the
climate conditions, and the owner desire. The
design engineer is responsible for considering
various systems and recommending more than
one system to meet the goal and satisfy the owner
of a building. Some criteria can be considered
such as climate change (e.g., temperature,
humidity, and space pressure), building capacity,
spatial requirements, cost such as capital cost,
operating cost, and maintenance cost, life cycle
analysis, and reliability and flexibility.

However, the selection of a system has some


constraints that must be determined. These
constraints include the available capacity
according to standards, building configuration,
available space, construction budget, the
available utility source, heating and cooling
building loads.

Basic Components of an HVAC System


Figure 9: Measured Metabolic Rate at Different Activities
The basic components or equipment of an
HVAC system that delivers conditioned air to
Types of HVAC Systems satisfy thermal comfort of space and occupants
and the achieve the indoor air quality are listed
Heating, ventilation, and air conditioning below:
(HVAC) system is designed to achieve the
environmental requirements of the comfort of • Mixed-air plenum and outdoor air control
occupants and a process. • Air filter
• Supply fan
HVAC systems can be classified according to • Exhaust or relief fans and an air outlet
necessary processes and distribution process. The • Outdoor air intake
required processes include the heating process, • Ducts
the cooling process, and ventilation process. • Terminal devices
Other processes can be added such as • Return air system
humidification and dehumidification process.
• Heating and cooling coils
These processes can be achieved by using
suitable HVAC equipment such as heating • Self-contained heating or cooling unit
systems, air-conditioning systems, ventilation • Cooling tower
fans, and dehumidifiers. The HVAC systems • Boiler
need the distribution system to deliver the • Control
required amount of air with the desired • Water chiller
environmental condition. The distribution system • Humidification and dehumidification
mainly varies according to the refrigerant type equipment
Classification of HVAC Systems Maintenance Accessible to the Accessible to
cost equipment room for equipment to be
maintenance and located in the
The major classification of HVAC systems is saving equipment in basement or the
central system and decentralized or local system. excellent condition, living space.
which saves However, it is
Types of a system depend on addressing the maintenance cost difficult for roof
primary equipment location to be centralized as location due to bad
weather
conditioning entire building as a whole unit or Reliability Central system Reliable equipment,
decentralized as separately conditioning a equipment can be an although the
specific zone as part of a building. Therefore, the attractive benefit estimated equipment
when considering its service life may be
air and water distribution system should be long service life less
designed based on system classification and the Flexibility Selecting standby Placed in numerous
equipment to provide locations to be more
location of primary equipment. The criteria as an alternative source flexible
mentioned above should also be applied in of HVAC or backup
selecting between two systems. Table 1 shows
the comparison of central and local systems Table 1: Comparison of Central and Local HVAC
systems
according to the selection criteria.
Central HVAC systems
Criteria Central system Decentralized A central HVAC system may serve one or
system
Temperature, Fulfilling any or all of Fulfilling any or all
more thermal zones, and its major equipment is
humidity, the design parameters of the design located outside of the served zone(s) in a suitable
and space parameters central location whether inside, on top, or
pressure
requirements adjacent to the building. Central systems must
Capacity Considering HVAC Maximum capacity condition zones with their equivalent thermal
requirements diversity factors to is required for each load. Central HVAC systems will have as several
reduce the installed equipment
equipment capacity control points such as thermostats for each zone.
Significant first cost Equipment sizing
The medium used in the control system to
and operating cost diversity is limited provide the thermal energy sub-classifies the
Redundancy Standby equipment is No backup or
central HVAC system, as shown in Figure 10.
accommodated for standby equipment
troubleshooting and
maintenance
Special An equipment room is Possible of no
requirements located outside the equipment room is
conditioned area, or needed
adjacent to or remote
from the building
Installing secondary Equipment may be
equipment for the air located on the roof
and water distribution and the ground
which requires adjacent to the
additional cost building
First cost High capital cost Affordable capital
cost
Considering longer
equipment services
life to compensate the
high capital cost
Operating More significant Less energy efficient Figure 10: Horizontal Hierarchy Representation of The
cost energy efficient primary equipment Main Types of Central HVAC Systems
primary equipment
A proposed operating Various energy
system which saves peaks due to Variable Air Volume
operating cost occupants’
preference Some spaces require different airflow of
Higher operating
cost supply air due to the changes in thermal loads.
Figure 11: All-Air HVAC Systems with VAV Terminal Units

Therefore, a variable-air-volume (VAV) all-air inside the zone itself, such as small houses and
system is the suitable solution for achieving residential apartments. This type of system is
thermal comfort. The previous four types of all- considered as local HVAC systems since each
air systems are constant volume systems. The equipment serving its zone without crossing
VAV system consists of a central air handling boundaries to other adjacent zones (e.g., using an
unit which provides supply air to the VAV air conditioner to cool down a bedroom, or using
terminal control box that located in each zone to an electrical heater for the living room).
adjust the supply air volume, as shown in Figure
11. The temperature of supply air of each zone is Therefore, a single zone requires only one-
controlled by manipulating the supply air flow point control point connected to a thermostat to
rate. activate the local HVAC system. Some buildings
have multiple local HVAC systems as proper
The main disadvantage is that the controlled equipment serving specific single zones and
airflow rate can negatively impact other adjacent controlled by the one-point control of the desired
zones with different or similar airflow rate and zone. However, these local systems are not
temperature. Also, part-load conditions in connected and integrated to central systems, but
buildings may require low air-flow rate which still part of a large full-building HVAC systems.
reduces the fan power resulting in energy There are many types of local HVAC systems as
savings. It may also reduce the ventilation flow shown in Figure 12.
rate, which can be problematic to the HVAC
system and affecting the indoor air quality of the
building.

Local HVAC systems

Some buildings can have multiple zones or


have a large, single zone, which needs central
HVAC systems to serve and provide the thermal
needs. However, other building may have a Figure 12: Horizontal Hierarchy Representation of the
Main Types of Local HVAC Systems
single zone which needs equipment located
Unitary Air-conditioner Careful and precise evaluation of the site is
required in order to achieve the proper
This system is a packaged device consisting distribution of temperature and humidity. The
of a vapor compression refrigeration cycle that prrevious diagram shows the steps that will be
contains a compressor, a condenser, an expansion undertaken:
valve, and an evaporator, in addition to a fan, a
filter, control system and housing. It is installed
on the exterior wall of the building and generally METHODOLOGY
located near the floor-wall intersection, as shown
in Figure 13. Every single zone will contain one The initial step of the process flowchart is to
unitary air-conditioner as in each guest room in gather information regarding the system and this
many hotels. requires three different approaches: field
measurement, subjective assessment and fluid
simulation. Considering the first approach, the
researchers are to measure the indoor
temperature and relative humidity at different
nodes of the zone.

Devices for Field Measurement

o Laser Distance Meter

It is used for accurately determining the


distance of an object or span without contact by
way of a laser. The basic measuring principle is
based on measuring the transit time of laser
pulses between the laser distance meter and the
Figure 13: Unitary Air-conditioner Package object to be measured.

THEORETICAL FRAMEWORK

Field Measurement •Globe Thermometer


of Atmospheric •Digital Anemometer
Quantities

Subjective •Survey Questionnaire


Assessment of
Indoor Conditions

Structural Design •3d Modeling via Solidworks


and Fluid •Computational Fluid
Simulation Dynamics

Analysis of Results •Theoretical Equations Figure 15: Laser Distance Meter


and Comparative •Tabular Presentations
Study •Graphical Presentations o Globe Thermometer

Proposal of an •Central System The globe thermometer was introduced by


Appropriate HVAC •Local System Vernon in 1930 as a means of assessing the
System combined effects of radiation, air temperature
and air velocity on human comfort.
Figure 14: Flowchart of the System of Study
Figure 16: Globe Thermometer Set-up Figure 17: 3 in 1 Digital Anemometer

It consists of a hollow copper sphere painted • Days of the week when attending mass
matt black to absorb radiant heat, with a • Time schedule
temperature sensor at its center. When it reaches • Seated position
a steady state (after 15 minutes or so depending • Comfortability
on the size of the globe and the environmental • Suggestions
conditions) the heat exchanges by convection and
radiation will be in equilibrium, and the The results of the survey will be discussed
temperature recorded by the sensor will be after this chapter. A copy of the survey
somewhere between the air and radiant questionnaire is provided at the Appendix
temperature. This is referred to as the globe section.
temperature (tg) or black globe temperature and
resembles the thermal conditions felt by the System of Interest
human body.
This study will focus on the evaluation of a
o Digital Anemometer specific system of interest, the St. Michael’s
Cathedral Church which is located at Obach
Digital Anemometer allows measuring Street Corner, Manuel L. Quezon Avenue,
atmospheric effects, namely wind velocity, Poblacion, Iligan City 9200, Philippines. Mass is
temperature, and humidity for better data held every day at different time frames and the
analysis. It also possesses various features such church is most crowded on Sunday masses.
as Beaufort scale, switch between Celsius and
Fahrenheit, switch between metric and imperial
system, or the battery status indicator. The device
is capable of displaying minimum, average, and
maximum wind velocity value. Its compact
design makes the digital Anemometer suitable
for both outdoor and indoor use.

Subjective Assessment

Survey among the church attendants will be


conducted in order to verify or support the results
of the direct measurement. Questionnaires will
be handed to the respondents to be answered with Figure 18: Satellite View of St. Michael’s Cathedral
their preference such as the following: Church, Iligan City (Photo retrieved from:
https://www.google.com.ph/maps)
Site Evaluation

The researchers conducted a site evaluation


to gather on-site data on February 11, 2020. The
building parameters were measured using a laser
distance meter and a steel tape. The mean radiant
temperature was measured through a 6 in
diameter black globe thermometer while the air
temperature and relative humidity were
measured using a 3 in 1 digital device
(anemometer, hygrometer, thermometer). These
were measured in three different levels which are
the ankle, waist and head, 0.1, 0.6 and 1.1 for Figure 21: Right Side View of the Model
seated occupants, respectively as stated in
ASHRAE Standard 55-2017.

Figure 21: Angled View of the Model

PRELIMINARY RESULTS AND DISCUSSION


Figure 19: Top View of the Model Field Measurements

The table in Table 2 shows the measured and


calculated values of thermal comfort parameters.
Of the 9 test points, it can be seen that the air
temperature is within 27.4ᵒC and 30.7ᵒC while
the mean radiant temperature is within 29ᵒC and
29.2ᵒC. Moreover, the wind speed and relative
humidity are 0.8mph and 78.65% respectively.
Also, the table shows the data measured outside
the church which are the right wing (RW), the left
wing (LW) and the front side (F).

Subjective Assessment

The results obtained through survey are


presented both in tabular and graphical form.
Figure 20: Front View of the Model
Table 2: Data of Thermal Comfort Parameters

Figure 22: Location of Nodes Inside the Church


Question 1 Question 5
Preferred Day
Weekdays 6 1 0
7
Saturday 3 2 1 6
6
Sunday 6 3 0
5
4 1
4
3 3 3
Question 2a 5 0
3
2 2
Monday 3 6 3 2
1
Tuesday 2 7 4 1
Wednesday 3 8 1 0
Thursday 1 Saturday Sunday Monday
Friday 2 Question 6
Tuesday Wednesday Thursday
Yes 2
Friday
Question 3a No 8
5:30am - 7:00am 1 Figure 23: Preferred Day of the Respondents
7:30am - 9:00 am 1 Question 7
12:00pm - 1:30pm 2 Yes 7
5:30pm - 7:00pm 2 No 3
Preferred Time (Weekdays)
Question 3b Question 8 2.5

5:30am - 7:00am 0 Yes 10 2

7:30am - 9:00 am 1 No 0 1.5

5:30pm - 7:00pm 2 1

Question 8a 0.5
Question 3c Hot 0 0
5:30am - 7:30am - 12:00pm - 5:30pm -
4:30am - 6:00 am 1 Muggy 0
7:00am 9:00 am 1:30pm 7:00pm
6:15am - 7:45am 2 Congested 0
8:00am - 9:30am 0 No Wind 0 Figure 24: Preferred Time to Attend Mass on Weekdays
1:30pm - 3:00pm 1 Other 0
3:15pm - 4:45pm 0
5:00pm - 6:30pm 3 Question 9
Preferred Time (Saturday)
More Electric Fans 2
2.5
Question 4 Install Aircon 1
morning mass 4 More Space 5 2

afternoon mass 6 More Trees 2 1.5

Others 0 1
0.5
Table 3: Tabular representation of Subjective Assessment
0
5:30am - 7:00am 7:30am - 9:00 5:30pm -
The respondents are asked what day they am 7:00pm
prefer to attend mass. The figure shows that the
respondents prefer most to attend mass on
Figure 25: Preferred Time to Attend Mass on Saturday
Sunday and prefer least on Thursday. The next
graphical representation will emphasize the
preferences.
REFERENCES
Preferred Time (Sunday)
3.5 Seyam, S. (2018). Types of Hvac Systems.
3 Retrieved from: intechopen.com/books/hvac-
2.5 system/types-of-hvac-systems
2
1.5 n.a. (2014). UPMC Health Beat. Effects of
1
humidity on your Body. Retrieved from:
0.5
0 https://share.upmc.com/2014/06/effects-
4:30am - 6:15am - 8:00am - 1:30pm - 3:15pm - 5:00pm - humidity-
6:00 am 7:45am 9:30am 3:00pm 4:45pm 6:30pm
body/?fbclid=IwAR31TVWaGPD_Yb8qPay1b
WttZzLU_EtloEISQZcOjRDy5HKPoHY3AjHn
Figure 26: Preferred Time to Attend Mass on Sunday iyE

n.a. (n.d.). Health and Safety Executive. The six


basic factors. Retrieved from:
Preferred Time Schedule https://www.hse.gov.uk/temperature/thermal/fac
tors.htm?fbclid=IwAR3abDalGpvdfq6f-
8
MX03oxXoodhsNKEhxqUpFB2ouN25MjKjvw
6
FIzy-74A
4
2 Staff, F. (2010). Environmental Monitor. What is
0 Air Temperature?. Retrieved from:
morning mass afternoon mass
https://www.fondriest.com/news/airtemperature.
htm?fbclid=IwAR1IiaHCbgqc9nboazB9szSBrR
Figure 27: Preferred Time Schedule to Attend Mass amLZHyvp4cfEyHVyDbB1gDOKshfcW0BwY

n.a. (2011). Thermal Environmental Conditions


for Human Occupancy. ASHRAE 55. ASHRAE
Comfortableness during Mass Board of Directors. American National Standards
Institute.
15
10 n.a. (2019). Globe temperature Retrieved from:
5 https://www.designingbuildings.co.uk/wiki/Glo
0 be_temperature
Yes No
n.a. (n.d.). Digital Anemometer. Retrieved from:
Figure 28: Comfortableness During Mass https://www.horizoneducational.com/juniorprod
ucts/digital-anemometer/

Recommendation for Indoor


Improvement
6
4
2
0
More Install More More Others
Electric Aircon Space Trees
Fans

Figure 29: Recommendation for Indoor Improvement


APPENDIX

Air Conditioning Survey Questionnaire


5. Please check the box of the location you mostly sit
during mass.

How Are We Doing?


ALTAR
Thank for agreeing to take part in this important
survey regarding comfort during mass held in Saint
Michael’s Cathedral.

Today we will be gaining your thoughts and 1 2 3 4


opinions in improving comfort during mass.

This survey should take about 3-5 minutes to


complete. Rest assured that all answers you
provide will be kept in the strictest confidentiality.

1. Please check the box of the day/s of the week 5 6 7 8


you mostly go to church and attend mass. (You
can select more than one)
 Weekdays  Saturday  Sunday

6. Do you bring a hand fan when attending mass?


 YES  NO
2a. If you check weekdays, check the box of the
day/s you attend mass. Otherwise leave blank.
(You can select more than one) 7. Have you seen individuals bringing hand fan when
attending mass?
 Monday  Tuesday  Wednesday
 YES  NO
 Thursday  Friday

8. Do you feel comfortable during mass?


 YES  NO
3a. If you check weekdays, check the box of the
time you attend mass. Otherwise, leave blank.
8a. If you check NO, please check the box for the reason.
 5:30am-7:00am 12:00pm-1:30pm Otherwise, leave blank. (You can select more than one)
 7:30am-9:00am  5:30pm-7:00pm
Hot (Init) 
Muggy (Igang) 
3b. If you check Saturday, check the box of the Congested (Guot) 
time you attend mass. Otherwise leave blank.
No Wind (Walay Hangin) 
 5:30am-7:00am  5:30pm-7:00pm
 7:30am-9:00am Others: __________________ 

3c. If you check Sunday, check the box of the


time you attend mass. Otherwise leave blank. 9. What can you recommend to improve the indoor
 4:30am-6:00am  1:30pm-3:00pm conditions of the church? (You can select only one)
 6:15am-7:45am  3:15pm-4:45pm Add more ceiling/electric fans 
 8:00am-9:30am  5:000pm-6:30pm
Install air-conditioning units 
Provide more space or widen the church 
4. At what schedule do you think the cathedral is Plant more trees near the location 
crowded during mass?
Others: __________________ 
 morning mass  afternoon mass

You might also like