Professional Documents
Culture Documents
Design of a 60 MW
Coal Power Plant
A Feasibility Study
Presented to
In partial fulfillment
Of the requirements for the course
Power Plant Design Engineering
October 2020
ii
ABSTRACT
A site in Agusan del Sur was evaluated for its feasibility in putting up a coal-powered
thermal station to supply the energy demand of the province as well as the neighboring province
of Surigao del Sur. The plant was to supply the base-load requirement of 60 MW providing
Efficiency of the conversion of fuel into desirable work was determined and the designs for
components such as condenser, heater, pumps and exhaust system were carefully considered.
iii
TABLE OF CONTENTS
Page
TITLE PAGE…………………………………………………………………………..i
ABSTRACT…………………………………………………………………………...ii
DEDICATION………………………………………………………………………..iii
CHAPTER
1 INTRODUCTION 1
2. METHODOLOGY
REFERENCES
1
CHAPTER 1
INTRODUCTION
Agusan del Sur consists of 13 municipalities and 1 city while Surigao del Sur has 17
municipalities and 2 cities. Approximate land area of Agusan del Sur is 9,990 square kilometers
and for Surigao del Sur, only 4,933 square kilometers. Former of the provinces is currently
served by Agusan del Sur Electric Cooperative, Inc. (ASELCO) distribution utility while the
latter is served by two utilities namely: Surigao del Sur I Electric Cooperative, Inc. (SURSECO
ASELCO is serving the whole Agusan del Sur province and mostly comprises of
the second district from Barobo municipality down to Lingig. SURSECO II on the other hand
extends its service from Lianga municipality up to Carrascal. Both provinces are also
The site will be located behind the premises of Philippine Normal University, Agusan
Campus in Bahbah, Prosperidad, Agusan del Sur and is situated alongside the Gibong River.
The estimated land area is 10 hectares and the perimeter is 1.39 kilometers. The selection of
Heat sink for the coal power plant is chosen to be the Gibong River due to its moderate
volume and continuous flow to the east ocean of Lianga. Bays of eastern Surigao del Sur are
The feedwater is selected to be natural water treated with chlorine collected from Mt.
Magdiwata as managed by the San Francisco Water District. The treatment of chlorine prevents
The source of coal that will be fed into the furnace is outsourced from Lingig, Surigao
del Sur which has abundant deposits of coal. Sub-bituminous type of coal is more common to
the area.
Desired location is not densely populated compared to other municipalities and the
nearby presence of forest is very ideal to the circulation of the combustion gases.
3
CHAPTER 2
METHODOLOGY
The power plant is to supply 60 MW rated load and is composed of steam generator,
turbine, surface condenser, one open feedwater heater, four closed feedwater heaters and four
traps. States are labelled in Figure 2.1 and corresponding mass fractions are designated by the
use of unity and variables. Heat and work input are also identified in the figure and the direction
𝑾̇𝑻,𝒂𝒄𝒕𝒖𝒂𝒍
1
Turbine
(1-v-w-x-y-z)
(1)
7
2
(v)
3
𝑸̇𝒊𝒏 6 𝑸̇𝒐𝒖𝒕
Steam (w) 5 (z) Condenser
Generator 4
(y)
(x)
(1) (1-v-w-x)
8
15
(1)
14 13 12 11 10 9
Open
Heater
2a 2b 3a 𝑾̇𝑷𝟏 3b 5a 5b 6a 𝑾̇𝑷𝟐 6b
(y) (v+w) (y) (y+z)
Steam was used as a working fluid in the design for the Rankine cycle. Certain
considerations were made upon designing the system. It is noted that the turbine should not
accumulate 10 percent moisture in the exhaust. According to Frederick Morse in his book
entitled ‘Power Plant Engineering,’ for a 60 000 kW turbine-generator rating, the preferred
standard throttle pressure and temperature are 59.8 kg/cm2 and 482°C, respectively and the
98.0665 𝑘𝑃𝑎
𝑇ℎ𝑟𝑜𝑡𝑡𝑙𝑒 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒: 𝑃1 = 59.8 𝑘𝑔/𝑐𝑚2 ( ) + 101.325 𝑘𝑃𝑎
1 𝑘𝑔/𝑐𝑚2
𝑃1 = 5965.70 𝑘𝑃𝑎
0.1333224 𝑘𝑃𝑎
𝐸𝑥ℎ𝑎𝑢𝑠𝑡 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒: 𝑃7 = 38.1 𝑚𝑚 𝐻𝑔 ( ) = 5.08 𝑘𝑃𝑎
1 𝑚𝑚 𝐻𝑔
In order to simplify the analysis, assumptions were also provided relating to the
function of individual components. The operation is assumed to be steady state such that there
should be no changes in the amount of working fluid flowing around the cycle. Blade efficiency
for pressure compounded staging is 90 percent with velocity ratio of 0.45. The rotation and
leakage allowance was assumed to be uniform at averaged value of 3.5 percent. Using the blade
efficiency and rotation and leakage allowance, the stage efficiency was determined as:
Pump efficiencies were also assumed as 75 percent for pump 1 and 40 percent for pump
2. Throttling was held as isenthalpic process implying that the enthalpy for the steam entering
the trap is the same as enthalpy leaving. For closed heaters, terminal temperature differences
(TTD) were provided to account for the anticipated temperature difference of liquid exiting the
5
small tubes and the liquid exiting the heater surface. From left to right, the TTD of the closed
heaters are -2.5°C, -1.5°C, -0.5°C and 0.5°C. Referring to Figure 2.2, it is also assumed that
the states 8, 6a, 5a, 12, 3a and 2a are at the saturated liquid curve.
T (°C)
1
482.00
2
5965.7 kPa 2s
275.21
15 3054.6 kPa
234.86 3
2a 3s
14 3054.6 kPa
194.52 13 3a 2b
13s 4s 4
12 531.89 kPa
154.18
3b
11 162.88 kPa
113.84 5
5a 5s
10 36.24 kPa
73.50
9 6a 5b 6s 6
9s
5.08 kPa
33.16
8 6b 7s 7
s (kJ/kg-K)
Uniform distribution of the temperature across the steam generator, heaters and the
condenser is preferred and the optimum fraction saturation temperature was determined. Using
The kinetic energy from the turbine is converted to electrical energy by the use of
generator. To calculate the desired generator efficiency, assuming full load operation, the
0.055 𝑅𝑎𝑡𝑖𝑛𝑔
𝜂𝑔𝑒𝑛 = 0.98 − 𝑥
3 𝑅𝑎𝑡𝑒𝑑 𝑘𝑊 𝐿𝑜𝑎𝑑
√
1000
0.055 60
𝜂𝑔𝑒𝑛 = 0.98 − 𝑥 = 0.9660
3 60000 60
√
1000
Power that is generated by the generator is the finished output of the whole thermal
plant. However, this does not mean that this is equal to the power produced by the steam
system. The losses should be accounted for the efficiency of the generator as well as the
Generator
Mechanical
ngen= 96.6 %
𝑾̇𝑻,𝑨𝒄𝒕𝒖𝒂𝒍 =
𝑾̇𝑩𝒓 = 62.1118 MW 𝑾̇𝒆 = 60 MW
62.4991 MW
5.0 5.0
𝐹𝑟𝑖𝑐𝑡𝑖𝑜𝑛 = %(𝑛𝑜𝑟𝑚𝑎𝑙 𝑟𝑎𝑡𝑖𝑛𝑔) = %(60) = 0.3873 𝑀𝑊
√𝑅𝑎𝑡𝑒𝑑 𝑘𝑊 √60 000
( 1000 ) ( 1000 )
Referring again to Figure 2.2, the properties of the individual state points are required
in order to determine the heat and work inputs and outputs. Pressure (kPa), temperature (°C),
specific enthalpy (kJ/kg) and specific entropy (kJ/kg-K) are usually present in the compressed
liquid and superheated vapor region and a property which is quality (x) is added for the state
A detailed list of the five properties are provided in Table 2.1 for all the states. The
processes indicated by the dashed lines are for isentropic turbines and pumps. The states
7
resulting from these processes are labeled with letter ‘s’ in the subscript. Instead of plotting
with these states, it is recommended to use actual state points which considers the efficiency
The actual turbine has stage efficiency while bleeding some of the steam through the
heaters, whereas the isentropic turbine does not consider this effect. When the process ends up
inside the saturation curve, a moisture penalty is introduced that is going to be subtracted from
the stage efficiency. Calculation for the enthalpies of the actual turbine processes are shown in
the following:
ℎ1 − ℎ2 3380.4 − ℎ2
𝜂𝑠 = → 0.811 = → ℎ2 = 3213.58 𝑘𝐽/𝑘𝑔
ℎ1 − ℎ2𝑠 3380.4 − 3174.7
ℎ 2 − ℎ3 3213.58 − ℎ3
𝜂𝑠 = → 0.811 = → ℎ3 = 3040.69 𝑘𝐽/𝑘𝑔
ℎ2 − ℎ3𝑠 3213.58 − 3000.4
ℎ 3 − ℎ4 3040.69 − ℎ4
𝜂𝑠 = → 0.811 = → ℎ4 = 2863.01 𝑘𝐽/𝑘𝑔
ℎ3 − ℎ4𝑠 3040.69 − 2821.6
ℎ4 − ℎ5𝑠
𝑀𝑜𝑖𝑠𝑡𝑢𝑟𝑒 𝑝𝑒𝑛𝑎𝑙𝑡𝑦: ∆𝜂𝑠 = (1 − 𝑥5𝑠 ) +
3490
2863.01 − 2639.9
∆𝜂𝑠 = (1 − 0.9743) + = 0.0896
3490
ℎ 4 − ℎ5 2863.01 − ℎ5
𝜂𝑠 = → 0.7214 = → ℎ5 = 2702.06 𝑘𝐽/𝑘𝑔
ℎ4 − ℎ5𝑠 2863.01 − 2639.9
9
ℎ5 − ℎ6𝑠
𝑀𝑜𝑖𝑠𝑡𝑢𝑟𝑒 𝑝𝑒𝑛𝑎𝑙𝑡𝑦: ∆𝜂𝑠 = (1 − 𝑥6𝑠 ) +
3490
2702.06 − 2460.9
∆𝜂𝑠 = (1 − 0.9263) + = 0.1428
3490
ℎ 5 − ℎ6 2702.06 − ℎ6
𝜂𝑠 = → 0.6682 = → ℎ6 = 2540.92 𝑘𝐽/𝑘𝑔
ℎ5 − ℎ6𝑠 2702.06 − 2460.9
ℎ6 − ℎ7𝑠
𝑀𝑜𝑖𝑠𝑡𝑢𝑟𝑒 𝑝𝑒𝑛𝑎𝑙𝑡𝑦: ∆𝜂𝑠 = (1 − 𝑥7𝑠 ) +
3490
2540.92 − 2270.8
∆𝜂𝑠 = (1 − 0.8801) + = 0.1973
3490
ℎ 6 − ℎ7 2540.92 − ℎ7
𝜂𝑠 = → 0.6137 = → ℎ7 = 2375.15 𝑘𝐽/𝑘𝑔
ℎ6 − ℎ7𝑠 2540.92 − 2270.8
Likewise, the pumps considered in the design are not isentropic but rather have their
efficiencies. Noting that the efficiencies for pumps 1 and 2 are 0.75 and 0.40, respectively, the
efficiencies for the actual state points of the pumping processes are calculated as:
Given the complete data for properties of individual states, the mass flow rates can be
determined by first getting the mass fractions labelled as variables. Using energy balance for
each heater from left to right, the mass fractions were gradually identified.
(1)
ℎ15 − ℎ14 1025.3 − 836.45
(1) 𝑣= =
ℎ2 − ℎ2𝑎 3213.58 − 1013.1
15 14
𝑚̇2
2a (v) 𝑣 = 0.0858 =
𝑚̇1
14 13 − (0.0858 + 𝑤)(827.77)
(v) 2b
𝑚̇3
3a (v+w) 𝑤 = 0.0702 =
𝑚̇1
3b (v+w)
𝑚̇4
𝑥 = 0.0487 =
𝑚̇1
5a (y) − 480.02)
10 9 + 2540.92𝑧 + (0.0622)(477.64)
In order to get the mass flow rate of state 1, we consider control volume for turbine and
equate the actual work produced to the enthalpies entering and leaving the system.
1 𝑾̇𝑻,𝒂𝒄𝒕𝒖𝒂𝒍
Turbine
(1)
2 3 4 5 6 7
(1-v-w-x-y-z)
(v) (w) (x) (y) (z)
𝑊̇𝑇,𝐴𝑐𝑡𝑢𝑎𝑙
= ℎ1 − 𝑣ℎ2 − 𝑤ℎ3 − 𝑥ℎ4 − 𝑦ℎ5 − 𝑧ℎ6 − (1 − 𝑣 − 𝑤 − 𝑥 − 𝑦 − 𝑧)ℎ7
𝑚̇1
12
62499.1
= 3380.4 − (0.0858)(3213.58) − (0.0702)(3040.69) − (0.0487)(2863.01)
𝑚̇1
− (0.0622)(2702.06) − (0.0545)(2540.92)
Hence, with the use of the mass fractions and the initial mass flow rate, the other mass
flow rates can now be determined. Solutions were straightforward and the results are tabulated
as follows:
The performance of the steam cycle is assessed by determining the thermal efficiency.
Given the values of the enthalpies and the mass flow rates, the heat and work inputs and outputs
Turbine Work:
− (0.0622)(2702.06) − (0.0545)(2540.92)
𝑤𝑇 = 833.4647 𝑘𝐽/𝑘𝑔
𝑤𝑃 = 15.3908 𝑘𝐽/𝑘𝑔
Thermal Efficiency:
𝑤𝑇 − 𝑤𝑃 833.4647 − 15.3908
𝜂𝑚 = = = 34.74 %
𝑞𝑖𝑛 2355.1
Combined Efficiency:
𝜂𝑐 = 𝜂𝑠 𝑥 𝜂𝑚 𝑥 𝜂𝑔𝑒𝑛
𝜂𝑐 = 0.811(0.3474)(0.9660)
𝜂𝑐 = 27.22 %
14
Common design for power plant condenser is composed of shell and tube assembly in
which the tubes are aligned parallel to the axis of the elongated shell and are attached in flanges.
This is known as surface condenser and it is a type of heat exchanger that cools down the steam
from the turbine exhaust into liquid condensate in the hotwell below the atmospheric pressure.
Cooling water is introduced into the tubes and the number of these affects the rate of heat
dissipation.
For the condensing unit, certain parameters are to be defined first prior to the
determination of the size. Table 2.3 presents the quantities and assumptions that will be used
including the specification of the tube according to the standard sizes provided by Morse.
The hot and cold stream temperature difference cannot be arithmetically averaged due
to the fact that this is exponentially decreasing (Cengel, 2006). Thus, the log mean temperature
difference is used to avoid averaging error. Figure 2.10 shows the variation of the temperature
difference inside the condenser. Note that the cooling water outlet temperature is obtained by
20
𝜃𝑚𝑖𝑛 = 33.16 − 28.76 = 4.4°𝐶
𝑡𝑖
𝜃𝑚𝑎𝑥 − 𝜃𝑚𝑖𝑛 13.16 − 4.4
x 𝜃= = = 8.00°𝐶
𝜃𝑚𝑎𝑥 13.16
Figure 2.10 Temperature Difference Variation ln 𝜃 ln 4.4
𝑚𝑖𝑛
The condenser is a counterflow heat exchanger with the same steam inlet and outlet
temperatures, designated 𝑡𝑖 ′ and 𝑡𝑜 ′ . The cooling water enters the condenser at temperature 𝑡𝑖
and leaves the condenser at temperature 𝑡𝑜 . Note that the direction of the arrows is opposite
The heat rejected is calculated by considering condenser as the control volume and
𝑞 = 𝑚̇ 7 ℎ7 + 𝑚6𝑏
̇ ℎ6𝑏 − 𝑚̇ 8 ℎ8
̇
𝑞 = 50.8862 (2375.15) + 8.7510(307.69) − 59.6372(138.95)
1 𝑘𝑐𝑎𝑙 3600 𝑠
𝑞 = 1.1525 𝑥 105 𝑘𝐽/𝑠 ( )( ) = 9.9138 𝑥 107 𝑘𝑐𝑎𝑙/ℎ𝑟
4.1858 𝑘𝐽 1 ℎ𝑟
which the heat is progressively transferred. The mediums include vapor, condenser tube, scale
and cooling water. Solutions for these coefficients are presented with particular formulas from
Morse’ book.
111910
𝑉𝑎𝑝𝑜𝑟: 𝑈𝑣 =
𝑞 0.188
(𝐴 )
𝑣
16
For condenser tubes, assume the material to be made of copper alloy with thermal
An average value for the coefficient of conductance of scale is 14 650 𝑘𝑐𝑎𝑙/(ℎ 𝑚2 °𝐶)
The formula for solving the coefficient of conductance for condensing water is
𝐽0.24
𝑈𝑤 = 𝑏𝑉𝑤 0.73 ; 𝑏 = 1379.7
𝑑𝑤 0.27
20 + 28.76
𝑇𝑎𝑣𝑒 = = 24.38 °𝐶
2
At an average temperature of 24.38 °C, the interpolated dynamic viscosity from Table
12-8 of Morse’ book is 0.9414 cP. Therefore, the conductance coefficient for cooling water can
now be solved.
1 1
𝐽= = = 1.0622 𝑐𝑃−1
𝑣 0.9414 𝑐𝑃
(1.0622)0.24
𝑏 = 1379.7 = 4235.04
(16.57 𝑥 10−3 )0.27
Taking into consideration the effects of the four mediums mentioned earlier, a
theoretical formula involving the log mean temperature difference, heat transfer, conductance
𝑞 1 2𝑑𝑣 𝑑𝑣 𝑑𝑣
𝜃= [ + + + ]
𝐴𝑣 𝑈𝑣 𝑈𝑡 (𝑑𝑤 + 𝑑𝑣 ) 𝑈𝑠 𝑑𝑤 𝑈𝑤 𝑑𝑤
𝐴𝑣 is the total surface area required for the dissipation of heat of the condensing steam.
Substituting the available quantities on the above equation, it is more convenient to solve for
𝑞
the expression 𝐴 first.
𝑣
𝑞 0.188
𝑞 ( 𝐴𝑣 ) 2(19.1) 19.1 19.1
8.00 = [ + + + ]
𝐴𝑣 111 910 75 564.52(16.57 + 19.1) 14 650(16.57) 7024.40(16.57)
𝑞
= 25 234.36 𝑘𝑐𝑎𝑙/(𝑚2 ℎ)
𝐴𝑣
Introducing the cooling water mass flow rate equation from page 421 of Morse’ book,
𝑞
𝜔𝑤 = ; 𝑐 = 1 𝑓𝑜𝑟 𝑤𝑎𝑡𝑒𝑟
𝑐(𝑡𝑜 − 𝑡𝑖 )
9.9138 𝑥 107
𝜔𝑤 = = 1.1317 𝑥 107 𝑘𝑔/ℎ𝑟
1(28.76 − 20)
The number of tubes per pass from the same reference on page 420 is obtained as
𝜔𝑤 1.1317 𝑥 107
𝑛= = = 7290 𝑡𝑢𝑏𝑒𝑠/𝑝𝑎𝑠𝑠
(3600 𝑥 103 )𝑎𝑤 𝑉𝑤 (3600 𝑥 103 )(2.156 𝑥 10−4 )(2)
18
𝐴𝑣 3928.65
𝐿= = = 8.98 𝑚
𝑎𝑣 𝑛 (0.06)(7290)
Due to the large number of tubing, the condenser is decided to be only one-pass.
The design for the closed feedwater heaters is almost identical to the condenser except
for the log mean temperature difference. Note that the cooling water outlet temperatures for
condensers 1, 2 and 3 underwent negative TTD and exceeded the saturation temperature of the
Tube specifications and water velocity from the condenser analysis will be preserved
such that only the heat transfer, dynamic viscosity and log mean temperature difference will
vary.
1 (8.0710)0.24
𝐽= = 8.0710 𝑐𝑃−1 𝑏 = 1379.7 = 6890.17
0.1239 𝑐𝑃 (16.57 𝑥 10−3 )0.27
1 𝑘𝑐𝑎𝑙 3600 𝑠
𝑞 = 14 157.67 𝑘𝐽/𝑠 ( )( ) = 1.2176 𝑥 107 𝑘𝑐𝑎𝑙/ℎ𝑟
4.1858 𝑘𝐽 1 ℎ𝑟
1.2176 𝑥 107
𝜔𝑤 = = 2.9453 𝑥 105 𝑘𝑔/ℎ𝑟
1(237.36 − 196.02)
T (°C)
𝐿𝑜𝑔 𝑀𝑒𝑎𝑛 𝑇𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒:
𝑡𝑜 ′ 𝑡𝑖 ′
392.54
237.36 𝜃𝑚𝑖𝑛
234.86 𝑡𝑜
𝜃𝑚𝑎𝑥 = 234.86 − 196.02 = 38.84°𝐶
𝜃𝑚𝑎𝑥
196.02 𝜃𝑚𝑖𝑛 = 392.54 − 237.36 = 155.18°𝐶
𝑡𝑖
𝑞 0.188
𝑞 𝐴𝑣 )
( 2(19.1) 19.1 19.1
83.99 = [ + + + ]
𝐴𝑣 111 910 75 564.52(16.57 + 19.1) 14 650(16.57) 11428.31(16.57)
𝑞
= 290 785.19 𝑘𝑐𝑎𝑙/(𝑚2 ℎ)
𝐴𝑣
2.9453 𝑥 105
𝑛= = 190 𝑡𝑢𝑏𝑒𝑠/𝑝𝑎𝑠𝑠
(3600 𝑥 103 )(2.156 𝑥 10−4 )(2)
41.87
𝐿= = 3.67 𝑚
(0.06)(190)
Closed heater 1 is to be designed with 190 tubes of 3.67 m length with only one pass.
20
(6.5147)0.24
𝑏 = 1379.7 = 6544.89
(16.57 𝑥 10−3 )0.27
1 𝑘𝑐𝑎𝑙 3600 𝑠
𝑞 = 12 841.43 𝑘𝐽/𝑠 ( )( ) = 1.1044 𝑥 107 𝑘𝑐𝑎𝑙/ℎ𝑟
4.1858 𝑘𝐽 1 ℎ𝑟
1.1044 𝑥 107
𝜔𝑤 = = 2.8217 𝑥 105 𝑘𝑔/ℎ𝑟
1(196.02 − 156.88)
T (°C)
𝐿𝑜𝑔 𝑀𝑒𝑎𝑛 𝑇𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒:
𝑡𝑜 ′ 𝑡𝑖 ′
299.66
196.02 𝜃𝑚𝑖𝑛
194.52 𝑡𝑜
𝜃𝑚𝑎𝑥 = 194.52 − 156.88 = 37.64 °𝐶
𝜃𝑚𝑎𝑥
156.88 𝜃𝑚𝑖𝑛 = 299.66 − 196.02 = 103.64 °𝐶
𝑡𝑖
𝑞 0.188
𝑞 𝐴𝑣 )
( 2(19.1) 19.1 19.1
65.16 = [ + + + ]
𝐴𝑣 111 910 75 564.52(16.57 + 19.1) 14 650(16.57) 10855.61(16.57)
21
𝑞
= 224 939.95 𝑘𝑐𝑎𝑙/(𝑚2 ℎ)
𝐴𝑣
2.8217 𝑥 105
𝑛= = 182 𝑡𝑢𝑏𝑒𝑠/𝑝𝑎𝑠𝑠
(3600 𝑥 103 )(2.156 𝑥 10−4 )(2)
49.10
𝐿= = 4.50 𝑚
(0.06)(182)
49.10
𝑛2−𝑝𝑎𝑠𝑠 = 2(182 𝑡𝑢𝑏𝑒𝑠) = 364 𝑡𝑢𝑏𝑒𝑠 𝐿2−𝑝𝑎𝑠𝑠 = = 2.25 𝑚
(0.06)(364)
Closed heater 2 is to be designed with 364 tubes of 2.25 m length with two passes.
5a T5a = 113.84 °C
𝑚̇5𝑎 = 4.6642 𝑘𝑔/𝑠
1
𝐽= = 3.3058 𝑐𝑃−1
0.3025 𝑐𝑃
Figure 2.15 Closed Heater 3 with Labels
(3.3058)0.24
𝑏 = 1379.7 = 5561.53
(16.57 𝑥 10−3 )0.27
1 𝑘𝑐𝑎𝑙 3600 𝑠
𝑞 = 10 375.14 𝑘𝐽/𝑠 ( )( ) = 8.9231 𝑥 106 𝑘𝑐𝑎𝑙/ℎ𝑟
4.1858 𝑘𝐽 1 ℎ𝑟
22
8.9231 𝑥 106
𝜔𝑤 = = 2.1585 𝑥 105 𝑘𝑔/ℎ𝑟
1(114.34 − 73)
T (°C)
𝐿𝑜𝑔 𝑀𝑒𝑎𝑛 𝑇𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒:
𝑡𝑜 ′ 𝑡𝑖 ′
116.28
114.34 𝜃𝑚𝑖𝑛
113.84 𝑡𝑜
𝜃𝑚𝑎𝑥 = 113.84 − 73 = 40.84 °𝐶
𝜃𝑚𝑎𝑥
73.00 𝜃𝑚𝑖𝑛 = 116.28 − 114.34 = 1.94 °𝐶
𝑡𝑖
𝑞 0.188
𝑞 𝐴𝑣 )
( 2(19.1) 19.1 19.1
12.77 = [ + + + ]
𝐴𝑣 111 910 75 564.52(16.57 + 19.1) 14 650(16.57) 9224.57(16.57)
𝑞
= 44 846.72 𝑘𝑐𝑎𝑙/(𝑚2 ℎ)
𝐴𝑣
2.1585 𝑥 105
𝑛= = 139 𝑡𝑢𝑏𝑒𝑠/𝑝𝑎𝑠𝑠
(3600 𝑥 103 )(2.156 𝑥 10−4 )(2)
198.97
𝐿= = 23.86 𝑚
(0.06)(139)
198.97
𝑛5−𝑝𝑎𝑠𝑠 = 5(139 𝑡𝑢𝑏𝑒𝑠) = 695 𝑡𝑢𝑏𝑒𝑠 𝐿5−𝑝𝑎𝑠𝑠 = = 4.77 𝑚
(0.06)(695)
Closed heater 31 is to be designed with 695 tubes of 4.77 m length with five passes.
23
(1.9242)0.24
𝑏 = 1379.7 = 4884.13
(16.57 𝑥 10−3 )0.27
1 𝑘𝑐𝑎𝑙 3600 𝑠
𝑞 = 9919.45 𝑘𝐽/𝑠 ( )( ) = 8.5312 𝑥 106 𝑘𝑐𝑎𝑙/ℎ𝑟
4.1858 𝑘𝐽 1 ℎ𝑟
8.5312 𝑥 106
𝜔𝑤 = = 2.1451 𝑥 105 𝑘𝑔/ℎ𝑟
1(73 − 33.23)
T (°C)
𝐿𝑜𝑔 𝑀𝑒𝑎𝑛 𝑇𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒:
′ ′
𝑡𝑜 𝑡𝑖
73.50
𝜃𝑚𝑖𝑛 𝜃𝑚𝑎𝑥 = 73.5 − 33.23 = 40.27 °𝐶
73.00 𝜃𝑚𝑎𝑥 𝑡𝑜
32.23
𝜃𝑚𝑖𝑛 = 73.5 − 73 = 0.5 °𝐶
𝑡𝑖
𝜃𝑚𝑎𝑥 − 𝜃𝑚𝑖𝑛 40.27 − 0.5
x 𝜃= = = 9.06 °𝐶
𝜃 40.27
Figure 2.18 Closed Heater 4 Temperature Difference ln 𝜃𝑚𝑎𝑥 ln 0.5
𝑚𝑖𝑛
𝑞 0.188
𝑞 𝐴𝑣 )
( 2(19.1) 19.1 19.1
9.06 = [ + + + ]
𝐴𝑣 111 910 75 564.52(16.57 + 19.1) 14 650(16.57) 8101.01(16.57)
24
𝑞
= 30 465.50 𝑘𝑐𝑎𝑙/(𝑚2 ℎ)
𝐴𝑣
2.1451 𝑥 105
𝑛= = 138 𝑡𝑢𝑏𝑒𝑠/𝑝𝑎𝑠𝑠
(3600 𝑥 103 )(2.156 𝑥 10−4 )(2)
280.03
𝐿= = 33.82 𝑚
(0.06)(138)
280.03
𝑛6−𝑝𝑎𝑠𝑠 = 6(138 𝑡𝑢𝑏𝑒𝑠) = 828 𝑡𝑢𝑏𝑒𝑠 𝐿6−𝑝𝑎𝑠𝑠 = = 5.64 𝑚
(0.06)(828)
Closed heater 4 is to be designed with 828 tubes of 5.64 m length with six passes.
The Department of the Interior – U.S. Geological Survey had conducted feasibility
study for introducing coal-water-mix fuels to the Philippines coordinating with the National
Economic and Development Authority (Landis et. al, 1985). The specific site of coal reserve
is chosen to be Bislig City as it is closer to the proposed power plant. Ultimate analysis of the
Coal Quality
Ultimate Analysis
C 50.29
H 5.83
O 27.88
N 0.94
S 0.57
A 14.49
Composition of air was determined through volumetric and weight analyses. Through
volumetric analysis, the mole fraction of Nitrogen gas is found to be 0.79 while for Oxygen it
is 0.21. The ratio of the two quantites is 3.76 moles N2/moles O2. On the other hand, through
weight analysis it was examined that Nitrogen is 77 percent while Oxygen is 23 percent by
mass. Note also that the molecular weight of air is 29 kg/kmol. For standard air, the relative
following equations and the mass fraction of each element in the ultimate analysis is multiplied
by the corresponding mass fraction of the oxygen and that particular element in the reaction.
Carbon Dioxide:
𝐶 + 𝑂2 → 𝐶𝑂2
12 𝑘𝑔 + 32 𝑘𝑔 = 44 𝑘𝑔
26
1 𝑘𝑔 + 2.67 𝑘𝑔 = 3.67 𝑘𝑔
Water:
2𝐻2 + 𝑂2 → 2𝐻2 𝑂
4 𝑘𝑔 + 32 𝑘𝑔 = 36 𝑘𝑔
1 𝑘𝑔 + 8 𝑘𝑔 = 9 𝑘𝑔
Sulfur Dioxide:
𝑆 + 𝑂2 → 𝑆𝑂2
32 𝑘𝑔 + 32 𝑘𝑔 = 64 𝑘𝑔
1 𝑘𝑔 + 1 𝑘𝑔 = 2𝑘𝑔
For 1 kg of coal,
2.67 𝑘𝑔 𝑂2
𝐶: 0.5029 𝑘𝑔 𝐶 ( ) = 1.3427 𝑘𝑔 𝑂2
1 𝑘𝑔 𝐶
8 𝑘𝑔 𝑂2
𝐻: 0.0583 𝑘𝑔 𝐻 ( ) = 0.4664 𝑘𝑔 𝑂2
1 𝑘𝑔 𝐻
1 𝑘𝑔 𝑂2
𝑆: 0.0057 𝑘𝑔 𝑆 ( ) = 0.0057 𝑘𝑔 𝑂2
1 𝑘𝑔 𝑆
Air-Fuel Ratio
A 15 percent excess air was considered in the design of the exhaust gas system.
Multiplying this to the theoretical air-fuel ratio will obtain the actual air-fuel ratio.
27
1.8148 𝑘𝑔 𝑂2 1 𝑘𝑔 𝑎𝑖𝑟
(𝐴/𝐹 ) 𝑇ℎ𝑒𝑜𝑟𝑒𝑡𝑖𝑐𝑎𝑙 = ( ) = 7.89 𝑘𝑔 𝑎𝑖𝑟/ 𝑘𝑔 𝑐𝑜𝑎𝑙
𝑘𝑔 𝑐𝑜𝑎𝑙 0.23 𝑘𝑔 𝑂2
The overall chemical balance is presented on the following equation. Note that the left
side of the equation is composed of the fuel added with air and ignited inorder to produce the
CO2:
H2O:
0.013 𝑘𝑔 𝑚𝑜𝑖𝑠𝑡𝑢𝑟𝑒
𝐻2 𝑂𝑀𝑒𝑐ℎ. 𝑀𝑜𝑖𝑠𝑡𝑢𝑟𝑒 = (𝐴/𝐹 )𝐴𝑐𝑡𝑢𝑎𝑙 ( )
𝑘𝑔 𝑎𝑖𝑟
SO2:
N2:
1.8148 𝑘𝑔 𝑂2 0.77 𝑘𝑔 𝑁2
𝑁2 𝑎𝑖𝑟 = ( ) = 6.0756 𝑘𝑔 𝑁2 /𝑘𝑔 𝑐𝑜𝑎𝑙
𝑘𝑔 𝑐𝑜𝑎𝑙 0.23 𝑘𝑔 𝑂2
1.8456 𝑘𝑔
𝜂𝐶𝑂2 = = 0.0419 𝑘𝑚𝑜𝑙 𝐶𝑂2
44 𝑘𝑔/𝑘𝑚𝑜𝑙
0.6427 𝑘𝑔
𝜂𝐻2 𝑂 = = 0.0357 𝑘𝑚𝑜𝑙 𝐻2 𝑂
18 𝑘𝑔/𝑘𝑚𝑜𝑙
0.0114 𝑘𝑔
𝜂𝑆𝑂2 = = 0.0002 𝑘𝑚𝑜𝑙 𝑆𝑂2
64 𝑘𝑔/𝑘𝑚𝑜𝑙
29
6.085 𝑘𝑔
𝜂𝑁2 = = 0.2173 𝑘𝑚𝑜𝑙 𝑁2
28 𝑘𝑔/𝑘𝑚𝑜𝑙
Amounts of combustion gases in mass and molar bases were determined from section
2.4.2. The table below summarizes the results including the percentage of the combustion gases
The coal system is responsible for feeding up fuel into the furnace. It is necessary to
investigate for the amount of fuel being utilized in combustion as well as the mode of transport
of these from the coal piles, into the bunker, pulverizer and finally the furnace.
Acquiring a precise value of the heating value is important in determining the mass of
fuel burnt per unit of time. Citing from the book of Philip Potter entitled ‘Power Plant Theory
and Design,’ a useful empirical formula for estimating the higher heating value of fuel is
𝑂2
𝐻𝐻𝑉 = 14 600𝐶 + 62 000 (𝐻2 − ) + 4050𝑆
8
Where C, H2, O2 and S are the mass fractions of the corresponding elements involved.
Recalling Table 2.5 for the ultimate analysis of the coal sample, the mass fractions were
substituted on the above equation and the higher heating value denoted by HHV was obtained.
0.2788
𝐻𝐻𝑉 = 14 600(0.5029) + 62 000 (0.0583 − ) + 4050(0.0057)
8
Converting the higher heating value into SI units, it can also be expressed as:
The generator efficiency is related to the heat input to the boiler and the heat generated
74.9871𝑘𝑔/𝑠(3380.4 − 1025.3)𝑘𝐽/𝑘𝑔
𝑚̇𝑓 = = 8.9120 𝑘𝑔/𝑠
0.9660(20 513.62 𝑘𝐽/𝑘𝑔)
Thus, the rate of coal feeding was determined to be 8.9120 kg/s. Using the air-fuel mass
ratio, the rate of air required in combustion was also determined as follows:
A flight conveyor is selected as a transport mechanism for coal to be delivered from the
pile into the bunker. The maximum capacity is simply the fuel mass flow rate expressed in
tonnes per hour. For the design, the working area of each flight is to be determined.
𝑇
𝑇 = 48.055𝐴𝑆 → 𝐴 =
48.055𝑆
Where 𝑇 is the maximum capacity of flight conveyor (tonnes/hr), 𝐴 is the working area
of each flight (m2) and S is the lineal speed of the conveyor (m/min). Assuming that the lineal
speed is kept at 1.5 m/s or 60 m/min, the flight area can then be calculated.
32.0832
𝐴= = 0.0111 𝑚2
48.055(60)
The horsepower required to driveshaft was also determined using the following
relationship:
ℎ𝑝 = 0.000198𝑤𝑓 𝐿𝑆 + 0.002567𝑇𝐿
Where 𝑤𝑓 is the weight of single strand of chains and flight (kg/m), 𝐿 is the conveyor
length (m) and T is the conveyor capacity (tonnes/hr). Suppose the strand weight is selected to
ℎ𝑝 = 0.000198(5)(10)(90) + 0.002567(32.0832)(10)
ℎ𝑝 = 1.7146 ℎ𝑝
32
0.7457 𝑘𝑊
𝑊̇𝐶𝑜𝑛𝑣𝑒𝑦𝑜𝑟 = 1.7146 ℎ𝑝 ( ) = 1.2786 𝑘𝑊
1 ℎ𝑝
A ball mill from Henan ZOOMJO Mining Machine Manufacturing Co., Ltd. Was
selected and the specifications for the model are stated as follows:
Feeding Size ≤ 25 mm
Using a bagtest, sample of gas will be collected to determine the amount of dust and
Outlet dimension 90 cm x 90 cm
Coefficient 60 %
𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚
𝑁𝑜𝑡𝑒: [ ]
𝑑𝑜𝑤𝑛𝑠𝑡𝑟𝑒𝑎𝑚
1000 6000
𝑉̇ = 𝐴𝑣 → 𝑉𝑠𝑢𝑝𝑝𝑙𝑦
̇ = 6 𝑐𝑚2 [ ] 𝑐𝑚/𝑠 = [ ] 𝑐𝑚3 /𝑠
700 4200
The apparatus must be adjusted for manometer readings indicated by the following
formula:
2
𝑦 = 114 050(𝑉̇𝑜𝑟𝑖𝑓𝑖𝑐𝑒 ) 𝑐𝑚 𝑤𝑎𝑡𝑒𝑟
−6 2
2.3756]
𝑦 = 114 050 [4563.93 𝑥 10−6 ] 𝑐𝑚 𝑤𝑎𝑡𝑒𝑟 = [ 𝑐𝑚 𝑤𝑎𝑡𝑒𝑟
3194.75 𝑥 10 1.1640
Suppose the collection of dust samples in upstream and downstream taken from 30 mins
0.0816 − 0.0154
𝐶𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟 𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = = 81.13 %
0.0816
1 81.6
𝑚̇𝑆𝑎𝑚𝑝𝑙𝑒𝑟 = [ ] 𝑔 = [0.0453] 𝑔/𝑠
60 𝑠 15.4 0.0086
30 𝑚𝑖𝑛𝑠 (1 𝑚𝑖𝑛)
Gas Density:
0.0453 𝑔/𝑠
𝐸𝑛𝑡𝑒𝑟𝑖𝑛𝑔 𝐶𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟: 3 = 7.55 𝑔/𝑚3
1
6000 𝑐𝑚3 ( )
100 𝑐𝑚
0.0086 𝑔/𝑠
𝐿𝑒𝑎𝑣𝑖𝑛𝑔 𝐶𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟: 3 = 2.05 𝑔/𝑚3
1
4200 𝑐𝑚3 (100 𝑐𝑚)
1𝑚 2
2
1 𝑘𝑔 60 𝑠
𝑚̇ 𝑇𝑜𝑡𝑎𝑙 = 𝑣𝐴𝜌 = 10 𝑚/𝑠 [(30 𝑥 180)𝑐𝑚 ( ) ] [7.55 𝑔/𝑚3 ( )( )]
100 𝑐𝑚 1000 𝑔 1 𝑚𝑖𝑛
Hopper Collection:
60 𝑚𝑖𝑛
𝑚̇𝐻𝑜𝑝𝑝𝑒𝑟 = 2.45 𝑘𝑔/𝑚𝑖𝑛 ( ) (0.8133)
ℎ𝑟
The feedwater system is responsible for maintaining the mass flow rate of water of the
steam cycle. Assuming that the losses mainly originated from the deconcentration of the
unwanted impurities such as scales, make-up water should be introduced into the feedwater.
Diagram for the feedwater system is provided as follows with heat saving equipment attached
during blowdown to recuperate the rejected heat into the feedwater being introduced.
35
WS
WS + WB
Upper
Drum
Scales and
Impurities
Feedwater
WB
Make-up Water
ti’ to’
Heat-saving
to Equipment ti Lower
Cooled
Blowdown Drum
hydrometer
Initially, the natural water to be used as feedwater is treated with chlorine. Due to the
lack of chemical processes to further remove the other unnecessary compounds that may cause
scaling inside the steam drum at higher temperatures, the design is to incorporate blowdown or
deconcentration.
Notation:
Balance of Solids:
𝑆𝑏 𝑊𝐵 = 𝑆𝑓 (𝑊𝑆 + 𝑊𝐵 )
𝑆𝑏 𝑊𝐵 = 𝑚𝑆𝑚 (𝑊𝑆 + 𝑊𝐵 )
The concentration of ground water or make-up water from San Francisco Water District
was measured as 𝑆𝑚 = 300 𝑝𝑝𝑚 (ℎ𝑎𝑟𝑑𝑛𝑒𝑠𝑠). Suppose the rate of blowdown is:
Two pumps were used in the steam system to circulate the steam inside the major
components and the pipes. Pump 1 is responsible for delivering steam of 100 percent mass flow
rate into the steam generator that passes through closed heaters 1 and 2 and also raising the
37
pressure. Pump 2 is responsible for bringing up the low pressure of the condensate into a
specified pressure inside the heater, passing closed heaters 3 and 4. Mass fraction of the steam
𝑏𝑝
𝑏𝑝 = 𝜀 𝑖𝑝 → 𝑖𝑝 = ; 𝜀 − 𝑝𝑢𝑚𝑝 𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
𝜀
̇
𝑃𝑢𝑚𝑝 1: 𝑊𝑃1 = 𝑚̇1 (ℎ13 − ℎ12 )
̇
𝑃𝑢𝑚𝑝 2: 𝑊𝑃2 = 𝑚̇8 (ℎ9 − ℎ8 )
For Pump 1:
A multistage boiler feed pump from Zoom Pumps website of model 600 – 60 x 8 was
Therefore, the power requirement for pump 1 can be solved directly represented as
indicated power.
900 𝑘𝑊
𝑖𝑝𝑃1 = = 1200 𝑘𝑊 ≅ 1113.5584 𝑘𝑊
0.75
38
For Pump 2:
Likewise, a multistage boiler feed pump from Zoom Pumps was selected but of
18.5 𝑘𝑊
𝑖𝑝𝑃2 = = 46.25 𝑘𝑊 ≅ 40.5533 𝑘𝑊
0.40
the air using the combustion gases which are ducted to a heat exchanging system before
introducing into the combustion chamber. Installment of such device is to be taken into
consideration because of the first cost and the arrangement of the equipment.
If permitted, the design of the air preheater will consist of 50 m thin-walled tubes of
length of 4 m each. 48 tubes will be installed at a center distance 10 mm relative to each other.
The air passage will be baffled with 5 passes and the heat transfer is via counterflow with the
𝑚̇𝑎 = 0.9𝑚̇𝑔
( 𝑡𝑖 ′ − 𝑡𝑜 ′ ) = 140 °𝐶
Air In
Specific Heats:
To Chimney
𝐶𝑝𝑔 = 0.25 𝑘𝑐𝑎𝑙/𝑘𝑔 °𝐶
Figure 2.22 Schematic Diagram for the Proposed Air Preheater
From Eq. 9-14 of Morse’ book, an empirical method of solving for the heat transfer
𝐴 = 1.95 𝐵 = 0.00045
140 0.25
(𝑡𝑜 − 𝑡𝑖 ) = ( ) = 162 °𝐶
0.9 0.24
T (°C)
𝐿𝑜𝑔 𝑀𝑒𝑎𝑛 𝑇𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒:
𝑡𝑜 ′ 𝑡𝑖 ′
370.00
𝜃𝑚𝑖𝑛
230.00 𝜃𝑚𝑎𝑥 = 230 − 16 = 214 °𝐶
178.00
𝜃𝑚𝑎𝑥 𝑡𝑜
16.00 𝜃𝑚𝑖𝑛 = 370 − 178 = 192 °𝐶
𝑡𝑖
370 + 230
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑔𝑎𝑠: 𝑡 ′ 𝑎𝑣𝑒 = = 300 °𝐶
2
1 ℎ𝑟 𝑚3
𝐺𝑎𝑠 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦: 𝑉𝑔 = 26 860 𝑘𝑔/(ℎ𝑟 𝑚2 ) ( )( ) = 12.09 𝑚/𝑠
3600 𝑠 0.617 𝑘𝑔
𝑚 1
𝑚̇𝑔 = 0.617 𝑘𝑔/𝑚3 (12.09 ) [ 𝜋(0.05)2 (48)] = 0.7030 𝑘𝑔/𝑠
𝑠 4
41
Initial assumption of the flue gas temperature difference in the inlet and outlet was
From the analysis of the preheater device, the outlet temperature of the preheated air
was determined to be 𝑡𝑜 = 178 °𝐶. The following quantities were also calculated to be used
16 + 178
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑎𝑖𝑟: 𝑡𝑎𝑣𝑒 = = 97 °𝐶
2
2
997 𝑘𝑔 1𝑚 3
𝑝𝑎 = 𝑝𝑎𝑡𝑚 + 𝑦𝜌 = 1.03323 𝑘𝑔/𝑐𝑚 + 15 𝑐𝑚 ( )( )
𝑚3 100 𝑐𝑚
𝑝𝑎 = 1.0482 𝑘𝑔/𝑐𝑚2
42
Density of Air:
𝑝𝑎
𝑝𝑎 = 𝜌𝑎 𝑅𝑎 𝑡𝑎𝑣𝑒 → 𝜌𝑎 =
𝑅𝑎 𝑡𝑎𝑣𝑒
100 𝑐𝑚 2
2
1.0482 𝑘𝑔/𝑐𝑚 ( 1 𝑚 )
𝜌𝑎 = = 0.9680 𝑘𝑔/𝑚3
𝐽 1
(287 𝑘𝑔 − 𝐾 ) ( 𝑚 ) (97 + 273.15)𝐾
9.81 2
𝑠
Velocity Head:
Note that the initial velocity of air from the forced draft fan is 0 m/s. The air then travels
through the fan at uniform velocity of 21.19 m/s passing the air preheater and arriving into the
𝑉1 2 (21.19 𝑚/𝑠)2
𝐻= = = 22.89 𝑚
2𝑔 2(9.81 𝑚/𝑠 2 )
𝑘𝑔 1
𝑑1 = 𝐻𝜌𝑠 = 22.89 𝑚 (0.9680 ) ( ) = 2.2158 𝑐𝑚, 𝑤𝑎𝑡𝑒𝑟
𝑚3 10
100 𝑐𝑚 3 1 𝑖𝑛𝑐ℎ 3 1 𝑓𝑡 3
60 𝑠
𝑄1 = 84.76 𝑚3 /𝑠 ( ) ( ) ( ) ( )
1𝑚 2.54 𝑐𝑚 12 𝑖𝑛𝑐ℎ𝑒𝑠 1 𝑚𝑖𝑛
ℎ𝑝1 = 884.35 ℎ𝑝
0.7457 𝑘𝑊
𝐼𝑛 𝑡𝑒𝑟𝑚𝑠 𝑜𝑓 𝑘𝑊: 𝑊̇𝐹1 = 884.35 ℎ𝑝 ( ) = 659.46 𝑘𝑊
1 ℎ𝑝
It was assumed that the maintained static draft for the chimney system is 𝑑2 = 2.00 𝑐𝑚,
𝑤𝑎𝑡𝑒𝑟. Different from the forced draft fan, the configuration selected for the induced fan is
ℎ𝑝2 = 798.22 ℎ𝑝
44
0.7457 𝑘𝑊
𝐼𝑛 𝑡𝑒𝑟𝑚𝑠 𝑜𝑓 𝑘𝑊: 𝑊̇𝐹2 = 798.22 ℎ𝑝 ( ) = 595.23 𝑘𝑊
1 ℎ𝑝
The structure that ejects the flue gases into the atmosphere is called the chimney. It also
produces draft by heating cold stream of air initially coming from the forced draft fan and the
heated air rises naturally by the convection principle. When the chimney is made of steel, it is
The following parameters derived from previous calculations as well as data coming
from the Engineering Toolbox website will be used in the design of the chimney.
Material Brick
Let V be the velocity of gas in the chimney. By Eq. 12-14 of Morse’ book, the required
Draft of Chimney:
𝑉5
𝐷30 = 𝐾(𝜌𝑎 − 𝜌𝑔 ) − 0.007578𝜌𝑔 √ ; 𝐾 = 2.7 (𝐵𝑟𝑖𝑐𝑘 𝑚𝑎𝑡𝑒𝑟𝑖𝑎𝑙)
𝑄2
45
5
0.007578(0.548)𝑉 2
𝐷30 = 2.7(1.184 − 0.548) − 1
84.762
5
𝐷30 = 1.7172 − 4.5107 𝑥 10−4 𝑉 2
Chimney Height:
𝑑𝑟𝑒𝑞
ℎ=
𝐷30
2.00 − 0.002192𝑉 2
ℎ= 5 𝑥 30 𝑚 [𝐸𝑞𝑢𝑎𝑡𝑖𝑜𝑛 1]
1.7172 − 4.5107 𝑥 10−4 𝑉 2
4𝑄2 𝑄2 84.76
𝑑𝑖 = √ = 1.13√ = 1.13√
𝜋𝑉 𝑉 𝑉
1
𝑑𝑖 = 10.4034𝑉 −2 [𝐸𝑞𝑢𝑎𝑡𝑖𝑜𝑛 2]
Chimney Specifications:
Assuming that the velocity is the same as the air inlet velocity, 𝑉 = 𝑉1 = 21.19 𝑚/𝑠,
2.00 − 0.002192(21.19)2
𝐹𝑟𝑜𝑚 𝐸𝑞𝑢𝑎𝑡𝑖𝑜𝑛 1: ℎ = 5 𝑥 30 𝑚
1.7172 − 4.5107 𝑥 10−4 (21.19)2
ℎ = 38.83 𝑚
1
𝐹𝑟𝑜𝑚 𝐸𝑞𝑢𝑎𝑡𝑖𝑜𝑛 2: 𝑑𝑖 = 10.4034(21.19)−2
𝑑𝑖 = 2.26 𝑚
Therefore, the height and inner diameter of the chimney are 38.83 m and 2.26 m,
respectively.
46
REFERENCES
Engineering Toolbox (2001). Tools and Basic Information for Design, Engineering and
toolbox.com/
Henan Zoomjo. Zoomjo - China Mining Machinery Production and Export Base. Retrieved
from http://www.zoomjomac.com/
Landis E. R. et. al. (1985). Introducing Coal-Water-Mix Fuels to the Philippines Assessment
Morse, F. (1953). Power Plant Engineering in MKS Units. Litton Educational Publishing, Inc.
Potter, P. (1959). Power Plant Theory and Design. 2nd Edition of Steam Power Plants. The
San Francisco Water District. Water Analysis and Laboratory Rates. Retrieved from https://
sfwd.gov.ph/services-and-rates/water-analysis-and-laboratory-rates/