Professional Documents
Culture Documents
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
J. Hoogmartens, L.Helsen
- 262 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
- 263 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Parameter changes Instead of using the lower heating curve during night,
Ten variations on the implemented reference control the higher one is used for the whole period.
strategy were simulated. All new implemented As sixth parameter change, a switch between the
control strategies were chosen such that the reference high (day) heating curve and low (night)
minimum requirement of thermal comfort is reached. heating curve is applied, which means that the High
An automated, optimal tuning of control parameters HC is used during night and the Low HC is used
has not been executed. during the day. In this way the thermal mass of the
The ten control strategies simulated are listed below. building is optimally used and the heat pump can
perform longer during night at lower energy prices
1. Higher heating curves (HC Higher)
(on/off peak electricity tariffs are used). Moreover,
2. Lower heating curves (HC Lower) internal gains and solar gains during the day are used
3. Room thermostat combined with heating in a more useful way. At night the whole structure is
curve heated to a higher temperature. Together with
4. Room thermostat combined with heating internal and external gains during the day, , a
curve and room temperature compensation minimum temperature can be maintained sometimes
(mainly in spring and autumn) even without using the
5. Constant water supply temperature
heat pump during the day.
6. Night increase
The next change is applied to the set point of the
7. Higher domestic hot water temperature domestic hot water tank. Instead of heating the
8. Larger dead band storage tank at night to 53°C, the heat pump will heat
9. Inclusion of legionella program the storage tank to 56°C. During the day, the upper
tank set point temperature is increased from 43°C to
10. Smart control of circulation pump 48°C.
By implementing the first two variations, the A dead band of ±2°C was implemented in the
influence of increasing or decreasing the requested reference case. This dead band is broadened to ±3°C
indoor air temperature on the yearly energy use can as next parameter change.
be studied. Both changes can not be evaluated with
respect to thermal comfort because these are typical In the second last parameter change a legionella
changes depending on user’s behaviour. Shifting the programme is installed for domestic hot water
heating curves (Viessmann, 2006) results in an production. On a weekly frequency the heat pump
increase or decrease of the yearly average indoor will heat the storage tank to the set point temperature
temperature with 1°C. of 53°C, afterwards an electric back-up heater will
heat the storage tank to 60°C. From the legal point of
Next two control strategies use a room thermostat to view it is not an obligatory control strategy (and
define whether the heat pump should be switched on therefore not implemented in the reference case), but
or off. The reference living room temperature is set most heat pump installers implement it to minimise
to 22°C with a dead band of ±1°C during the day; at the risk of legionellosis infection.
night the set point temperature is decreased to 20°C
with a dead band of ±1°C. When the room thermostat Finally, an advanced control of the circulation pump
gives a heating signal to the heat pump it switches on of the floor heating system is simulated. Instead of
based on the implemented heating curve of the turning on the circulation pump during the whole
reference case until the room temperature reaches the heating season (as it is done in most of the real
upper limit of the living room set point temperature cases), the circulation pump will be normally
or the return floor heating temperatures reaches the switched off except during one quarter each hour.
upper limit of the implemented dead band of the During this quarter the real (measured) return water
heating curve. The circulation pump for floor heating temperature is compared to the implemented set point
switches on/off together with the heat pump unit. In of the return water temperature of the floor heating
the fourth parameter change, an extra room (derived from the HC). Only if the return water
thermostat compensation is implemented. If the temperature drops below the lower limit of the dead
deviation from the set point room temperature is band, heating is necessary and therefore the heat
much larger than the tolerated dead band limit pump (and circulation pump) will work until the
(because e.g. domestic hot water production or after a return temperature of the floor heating reaches the
holiday), the heating curve is increased by a certain upper limit of the dead band after which the heat
proportion depending on the deviation to fasten the pump and circulation pump switch off again.
reheating of the house.
To check the statement (often encountered on the
street) that a constant temperature to the floor heating
system is economically more interesting than night
set back, the fifth parameter change is simulated.
- 264 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
- 265 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
No overheating has been detected in the other rooms. influences the indoor air temperature, the evaluation
The average yearly amount of Kh subcooling is 92. of thermal comfort does not make sense. By
The largest part of this subcooling takes place in the changing this parameter of the control strategy only
living room and the kitchen and is completely the potential energy savings or extra energy need is
situated in summer. During summer the indoor studied. Increasing or decreasing the heating curves
temperature always stays around 20-21°C but the results in a positive or negative shift of 1°C of the
thermal comfort limit for subcooling raises to 23°C. yearly average indoor temperature in all heated
The total amount of hours during which the indoor rooms. Point 2 (HC Lower) in Fig. 5 shows that large
air temperature exceeds the comfort limits is on a energy savings (730 kWh/year) are possible by
yearly basis only 0.07% for overheating and 1.96% decreasing the heating curves. On the other hand, by
for subcooling. The operating cost for this GCHP increasing the heating curves (point 1 (HC Higher) in
system is calculated on a yearly basis, using peak (19 Fig. 5), 780 kWh/year extra electrical energy is
c"/kWh) and base (13 c"/kWh) load tariffs. For the needed. This extra energy use translates itself to a
reference case the total operating cost is " 753. This lower SPF of the heat pump system (-4%). Thus
can be compared to a static calculation of a adapting yourself (e.g. by using warmer clothing) to
condensing gas boiler with a seasonal efficiency of a somewhat lower indoor temperature has a
85% and a natural gas price of 5 c"/kWh, for which significant beneficial effect on the yearly electrical
the total operating cost is " 1,353. Large savings on energy use.
operating costs are possible by using GCHP systems. Both room thermostat controls (points 3 and 4 in Fig.
Also the savings regarding CO2–emissions are 5) result in important energy savings while
substantial. The dynamic simulation of the reference maintaining the same level of thermal comfort in all
heat pump system in TRNSYS gives a total yearly rooms of the building. The reason is that the room
CO2-emisison of 3,499 kg. This result can be thermostat turns off the heat pump earlier than the
compared to a static calculation of a gas condensing heating curve does. Since the circulation pump is
boiler with a nominal CO2-emission of 201 g/kWh switched off together with the heat pump unit, large
(EPB, 2010) leading to a total emission of 5,440 kg. energy savings were reached. The amount of
Besides large operating cost savings, also large CO2 overheating is lower compared the reference case.
emission savings are possible by using GCHP However, subcooling increases slightly due to the
systems. fixed set points during night and day, summer and
All other control strategies are compared to this winter. Similar to the reference scenario, subcooling
reference case. A first adaptation is a positive and is mainly observed during summer.
negative shift of the heating curves. As this control
strategy is related to user preferences and directly
Figure 4: SPF boundary (denoted by dash-dotted line) European standard prEN 15316-4-2. 1. Heat source; 2.
Source pump; 3. Heat pump; 4. DHW pump; 5. DHW storage; 6. DHW back-up heater; 7. primary pump; 8.
DHW hot water outlet; 9. SH storage; 10. SH back-up heater; 11. SH circulation pump; 12 Heat emission
system; 13. DHW cold water inlet
- 266 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Figure 5: Trade-off between energy use (kWh/year) and average thermal discomfort (Kh) of reference case and
10 control adaptations
The extra implemented room temperature Moreover, due to the night increase the heat pump
compensation leads to an extra electrical energy works with higher water supply temperatures (which
saving, however at the expense of a larger thermal represents less performing operating conditions) at
discomfort. The compensation control provides a night, when the electricity tariff is lower, thus saving
faster heating when the real indoor air temperature money. The higher discomfort is caused by increased
deviates significantly from the set point temperature. overheating at night in de bedrooms, similar to the
The parameters, however, are not yet fully optimised. previous simulation results (constant temperature) on
the one hand, and by the increased number of hours
The constant water supply temperature control subcooling in the living room and kitchen in summer
(presented by point 5 in Fig. 5), combined with the on the other hand.
use of the reference higher (day) heating curve for A higher set point for domestic hot water production
the whole period, results in higher energy demand for (point 7 in Fig. 5) results in a similar result as the
an almost equal (slightly lower) indoor thermal reference case. Extra electrical energy input, to
comfort. The number of overheating hours is higher deliver slightly higher set point temperatures, is
compared to the reference case, raising from 0.07% compensated by energy savings for the circulation
to 0.34% due to overheating in the bedrooms during pump. To heat the storage tank to 56°C, the heat
the winter nights. The larger thermal energy demand pump has to heat up the water in the condenser to
may also cause a decrease of the ground temperature higher temperatures (order of 60°C, which is a safety
and as a consequence of the GCHP performance limit for the heat pump). When the heat pump
(when the borefield sizing is not adjusted), which delivers water of 60°C the heat pump and circulation
may even further increase the energy demand pumps are switched off for 20 minutes. Moreover,
compared to the reference case. while the heat pump is operating for DHW
production it can not generate space heating.
The next implemented control strategy is the However, this causes no problems with respect to
application of night increase, where the high (day) thermal discomfort.
heating curve and lower (night) heating curve of the
reference case are switched (point 6 in Fig. 5). This A larger dead band around both high (day) and low
change results in a lower energy demand at the (night) heating curves (point 8 in Fig. 5) results in a
expense of a slightly higher discomfort. The lower larger energy use and larger thermal discomfort.
energy demand can be explained by raising the Because of the larger band, the heat pump will have
indoor temperature at night and using external and to operate for longer periods. The larger band around
internal heat gains useful during the day, therefore the heating curve causes a larger amount of hours
the heat pump is switched off for a longer time overheating and subcooling. This control strategy
compared to the reference case. In some periods of has, evidently, a large impact on the amount of on/off
the year, the heat pump only works at night, while switching, which decreases substantially.
external and internal heat gains keep the indoor
temperature on a minimum level during daytime.
- 267 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
'()%!&%
*((+%,$-.+(/,0,1!&%
7"#$,%"54.-0/-%
8-0:%;05:%
&(5/,05,%,-+2-.0,3.-%
*((+%,$-.+(/,0,1!&1.((+%
8!9%$"#$%/-,%2("5,%
=+0.,%4(5,.(<%4".43<06(5%23+2%
,-+2-.0,3.-%4(+2-5/06(5%
Figure 6: Relative comparison to reference case. Black bar: energy use; Gray bar: working cost; White bar:
CO2-emission
- 268 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
- 269 -