You are on page 1of 35

Technical

Presentation
ASPE
Cleveland, OH
March 10th, 2010
Viking TotalPac2
FireFlex Dual / 1230

Systems Inc.

www.fireflex.com
INTEGRATED SPRINKLER SYSTEMS
History:

1990 1991 2002


Power Light & Ordinary Second
Plants Unit Hazard Generation
INTEGRATED SPRINKLER SYSTEMS
Expanding the concept:

Extended range of configurations:

Skid unit Remote controlled unit Self-contained unit


ICAF SYSTEM
Description: Typical System Layout

Air Cylinders
Piping Network

Distribution
Nozzles

Integrated Cabinet
Foam Tank
(water tank also available)
CAF TECHNOLOGY
Description: Compressed Air Foam (CAF)

• Uniform & stable


• High momentum
• Excellent quality
• 10:1 expansion
Integrated Clean Agent Systems

• Clean Agent Integrated Fire Suppression Systems


using 3M™ Novec™ 1230 Fire Protection Fluid

• Combined Automatic Sprinkler and Clean Agent


Integrated Fire Suppression Systems using 3M™
Novec™ 1230 Fire Protection Fluid
CLEAN AGENT
3M Novec 1230:
Integrated Clean Agent Systems
FireFlex 1230
Extinguishing Mechanism

The Fire Tetrahedron


chain
Removing one of the
reaction
required components
for fire or disrupting
the balance between
them can cause a fire
to extinguish
heat
fuel
Novec 1230 Fluid
oxygen
extinguishes primarily via
cooling – removing heat
from the fire
Compatible with
fire system materials
 Non-corrosive
 Long term testing of compatibility with materials of
construction (system hardware)
 Compatability with plastics confirmed
 30 year shelf life in properly maintained and
installed systems
3M NOVEC 1230

Environmental Properties

Properties Novec 1230 Halon 1301 FM-200 ECARO-25


(FK-5-1-12) (HFC-227ea) (HFC-125)
Ozone Depletion 0 10 0 0
Potential
Global Warming 1 6900 3220 3500
Potential
Atmospheric 0.014 65 29 33
Lifetime (years)
EPA's SNAP Yes N/A Yes Yes
Conformance
3M NOVEC 1230

Physical Properties

Properties Novec 1230 Halon 1301 FM-200 ECARO-25


(FK-5-1-12) (HFC-227ea) (HFC-125)

Design % 4-6% 5% 6.25-8.7 % 8-11.3 %

NOAEL % 10 5 9 7.5

Occupants
67-150 % Nil 3-44 % Nil
Safety Margin %

(NOAEL) No Observable Adverse Effects Level for acute toxicity, including cardiac
senisitization
3M NOVEC 1230

• Site refilling option


3M NOVEC 1230

If Novec 1230 fluid is banned from or restricted in use as a fire


protection agent due to ozone depletion potential or global
warming potential, 3M will refund the purchase price of the fluid.
CLEAN AGENT
3M Novec 1230:

Pre-Engineered Discharge Nozzles:


• Available: 1", 1½" & 2" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• No piping below 8,500 cu.ft. !
FIREFLEX 1230

Engineered Systems:
• Larger or multiple room hazards or volumes
• Need some calculations/software required
• Re-use existing Halon 1301 piping at 500psi
CLEAN AGENT
3M Novec 1230:

Engineered Discharge Nozzles:


• Available: ½", 1", 1½", 2" & 2½" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• Re-use existing Halon 1301 piping at 500psi
FIREFLEX 1230
Product Description:

• Fully Integrated
• Clean Agent System Only
• Factory Built & Tested
FIREFLEX 1230
Product Description:

• Sturdy Cabinet with Lock


• Competitively Priced
• Eliminates Site Coordination Issues
FIREFLEX 1230
Product Description:
Integrated Potter
PFC-4410 RC
Releasing panel

Detailed Instructions
& Unit Serial Number
Clean Agent
Cylinder from
40 to 601 lbs
cap.

Sturdy Cabinet
FIREFLEX 1230
Available Configurations:

• Clean Agent Only – No Sprinklers


• Self-contained or Remote Controlled (no panel)
• Master-Salve Cylinders Available
• Main-Reserve Arrangement Available
• Pre-Engineered or Engineered Piping System
FIREFLEX 1230
System dimensions and Capacity Table:
FireFlex® 1230 Cabinets Capacity (# of cylinders) & dimensions

Cylinder Size (lbs) Dimensions

Cabinet Size 40 76 164 322 601 A B C

24" 1 1 1 1 -- 23" 25" 77⅛"

36" 2 2 2 -- 1 35¾" 25" 77⅛"

48" -- -- -- 2 2 46" 25" 77⅛"


Integrated Clean Agent Systems
FireFlex DUAL
FIREFLEX DUAL
Product Description:

• Fully Integrated System


• Combines Preaction & Clean
Agent
• Factory Built & Tested
•Serialized
FIREFLEX DUAL
Product Description:

• Sturdy Cabinet with Lock


• Competitively Priced
• Eliminates Site Coordination
Issues
FIREFLEX DUAL
Product Description:
Air Compressor
Optional Common
Integrated Potter
PFC 4410RC
Releasing Panel

Detailed Instructions
& Unit Serial Number

Viking Preaction 2” & 3”

Clean Agent Cylinder


FIREFLEX DUAL
Available Configurations:

• Preaction Single or Double Interlock


• 2" or 3" dia. Sprinkler Valve
• Self-contained or Remote Controlled (no panel)
• Pre-engineered or Engineered Piping System
FIREFLEX DUAL
System dimensions and Capacity Table:

FireFlex® DUAL Cabinets Capacity (# of cylinders) & dimensions

Cylinder Size (lbs) Dimensions

Cabinet Size 40 76 164 322 601 A B C

36" 1 1 -- -- -- 35¾" 25" 77⅛"

48" -- -- 1 1 1 46" 25" 77⅛"


Standards, Approvals and Listings for Novec 1230 Fluid

U.S EPA SNAP approved as alternative to halon in occupied spaces

NFPA 2001 Standard on Clean Agent Fire Protection Systems

ISO 14520 Standard on Gaseous Media Fire Extinguishing Systems

UL Listed FM Approved IMO Recognized

VdS Approved LPCB Approved DNV Approved

CNPP Approved Lloyds Approved Bureau Veritas


Approved
LISTINGS & APPROVALS
Clean Agent
(Sevo Equipment):

UL & ULC Listed:


• 360 psi Pre-engineered Systems
• Engineered Systems by Mid-2010

FM Approved:
• 500 psi Pre-Engineered Systems
• Engineered Systems early 2010
LISTINGS & APPROVALS
Potter Releasing Panel &
Viking Preaction System:

• UL & ULC Listed


• FM Approved
• CSFM Approved
• NYC Accepted
LISTINGS & APPROVALS
FIREFLEX DUAL & 1230
(Assembled Units):

• Pre-engineered System: c-UL-us


(early 2010)
• FM Approved 500 psi

• Engineered System: c-UL-us & FM


(early 2010)

• CSFM & NYC (early 2010)


APPLICATIONS

• Cable racks • IT Systems

• Clean Rooms • Mix rooms

• Clinical / Diagnostic • Pump Stations


equipment • Switch Rooms & UPS
• Control Rooms • Telecommunications
• Data Centers • Testing / Imaging
• Electric Utility facilities equipment

• Generator & turbine • Transformer Vaults


enclosures • Etc…
Information required for design
• Obtain specifications
• Approvals required, AHJ
• Determine if a reserve is required
• Identify hazard normal ambient temperature
• Obtain location altitude
• Obtain drawings, sketches of dimensions
• Qualify room size when quoting a job
• Obtain hazard areas, length, width, ceiling height
• Determine system location
Thank you ! Systems Inc.

FIREFLEX DUAL
&
FIREFLEX 1230
by the same people who first
brought you integrated fire
protection systems
www.fireflex.com