Areva PIX

VCB Cassette
Switchgear

DESCRIPTION AND
GUIDE TO OPERATIONS
Actions and Information
Red arrow/text indicates an instruction

Blue arrow/text indicates additional information


INDEX SCREEN
Click on the link to move to the required section

General description of the switchgear

Procedure to OPEN, establish Points of Isolation and Earth a Feeder


Circuit Breaker

Procedure to remove Circuit Earth, restore Points of Isolation and CLOSE


a Feeder Circuit Breaker

Procedure to Earth a Busbar

Procedure to remove a Busbar Earth

Procedure to earth a circuit through a test cassette


GENERAL DESCRIPTION
OF THE SWITCHGEAR
FRONT PANELS

This illustration shows a typical PIX Feeder


Circuit Breaker, comprising three main
panels. The upper panel contains the
protection equipment, controls and lamp
indications. The centre panel comprises a
door over the VCB cassette housing
together with mechanical OPEN and
CLOSE buttons (the CLOSE button is
permanently disabled), facilities for VCB
cassette racking and emergency
mechanism manual charging. The lower
panel is a removable door which covers the
VT compartment (not all units are fitted with
a VT). Note that although local operating
facilities are provided, it is company
policy to open and close Circuit
Breakers remotely
UPPER PANEL

The upper panel contains the


local/remote and CB trip/close
rotary controls, together with CB
ON, CB OFF, Trip Circuit Healthy
and CB Tripped indicator lamps.
An Areva M231 display unit is
located at the centre of the panel
whilst the protection relays are
located at the top (layout of
controls and indications varies)
CENTRE PANEL

The centre panel door contains


a viewing window, allowing
observation of the mechanical
ON/OFF semaphore, operations
counter and the mechanism
spring condition indicator, all of
which are located on the VCB
cassette. This panel also
contains the VCB cassette
racking socket and the socket
cover control, together with
mechanical CLOSE and TRIP
buttons (LOCAL CLOSE
BUTTONS ARE
INOPERATIVE!)
CENTRE PANEL WINDOW

The spring condition semaphore for


the operating mechanism is located on
the right hand side of the window.
When the arrow points to the right, the
mechanism spring is charged. A
charged mechanism has enough
energy for one CLOSE and one OPEN
operation
CENTRE PANEL WINDOW

The same window also allows


viewing of the VCB cassette
status semaphore. OPEN is
indicated by a black horizontal
line on a white background
CENTRE PANEL WINDOW

CLOSED is indicated by a black


vertical line on a white background
HANDLE AND KEY

The upper handle is used to


raise and open the centre panel
door and is retained when the
door is lifted off its latches. The
lower D ring key is used to
unlock the centre panel door
and is retained when the door is
unlocked. Both are stored in the
substation
KEY CABINET

This key cabinet is one of three that are located adjacent to each other
within the substation. They are used to store operational keys for the
switchgear
CENTRE PANEL

Company policy is to trip and


close Circuit Breakers remotely,
however a local mechanical trip
button is provided for
emergency use (the close
button is permanently
inoperative). Both buttons are
protected by hinged and
lockable plastic covers,
however locks are not applied in
normal service. The lever on the
left is held in the up position as
shown by gravity acting on the
heavier internal part of the
mechanism; it must be pressed
down for the trip button to be
effective
BUTTON EXTENSION
MECHANISM

This mechanism is located on the


rear of the centre panel door,
controlled by the lever identified on
the previous screen. It is shown in
the lowered (retracted) position.
When raised (extended), it allows
the mechanical trip button on the
front panel door to connect to the
equivalent button on the front of the
VCB cassette
SHUTTER MECHANISM

Automatic shutter operating


mechanisms are located
within the centre housing. The
circuit shutter mechanism is
on the left hand side and the
busbar shutter on the right
hand side. Both mechanisms
are provided with locking
points (arrowed) – it is vital
that locks are removed
before inserting VCB
cassettes
VCB CASSETTE

This illustration shows a VCB


cassette fully removed from its
housing. The socket for the
secondary wiring (Harting) plug is
located at the upper left. Always
move the VCB cassette using the
folded metal grips on either side
of the blue panel, never by
gripping the polymeric moulded
cases or the bushings
HARTING PLUG AND SOCKET

Low voltage supply and control


connections between the
housings and the VCB cassettes
are implemented by this plug and
socket. The plug must be
disconnected before a VCB
cassette can be removed from its
housing and reconnected when a
VCB cassette is restored. Note
the interlocked over clip
TEST CASSETTE

A special test cassette is


required to make contact
with the circuit isolating
contacts. It is inserted and
removed using the special
trolley in a similar manner to
a standard VCB cassette.
The test cassette may be
reconfigured for busbar
testing by inverting the
horizontal bars
CASSETTE TROLLEY

VCB and test cassettes must be


inserted and removed from
housings using this special
trolley, which is normally stored
in the substation. Note the
braked wheels. The handle is
used to raise and lower twin
spigots at the front of the trolley,
which lock into matching
sockets at the edge of the
housing. The button is used to
release the cassette from the
trolley when re-inserting
EARTHING PANEL

Between the centre


and lower panels is an
area containing an
earth switch (on the
left) and its associated
semaphore (on the
right). A circuit live
indicator system to
IEC 61598 is located
at the centre
EARTHING PANEL

This enlarged view of a


feeder earthing panel
shows two keys – the
Proof of Isolation key on
the right is not released
unless the VCB cassette
is racked to the isolated
position. The Proof of
Earthing key on the left
may be removed only
when the earth switch is
closed
EARTHING PANEL

Some Circuit Breaker


earthing panels are fitted
with an additional
Permissive Earth lock at
the location arrowed.
When the key is present, it
allows the earth shutter to
open. The key is normally
located at the remote end
of the circuit but it is not
interlocked. The remote
end must be isolated and
the key collected, before
earth on the PIX Circuit
Breaker may be applied
and the key should be
returned to the remote end
when not in use
EARTH SWITCH
HANDLE

Earthing operations are carried out using this handle, which


is stored in the substation
LOWER PANEL

If a VT is fitted it will be
located inside the lower
compartment – note that
units fitted with a VT do not
have a window in the lower
panel. Under safe
operational circumstances
the panel may be
unfastened and lifted off to
reveal the VT fuses,
instruction labels, locks
and withdrawal handles.
The function of the handles
and locks is explained in
the operational sections of
this presentation
REMOTE CONTROL
PANEL

It is company policy to open and


close Circuit Breakers remotely
from control panels located in an
adjacent room. Incomer and
Interconnector Circuit Breaker
remote control panels are
additionally fitted with an
emergency trip button, which trips
both the specified local Circuit
Breaker and an associated Circuit
Breaker on another switchboard.
These trip buttons must be rotated
to release after use
KEY EXCHANGE BOX

Certain procedures require use of key exchange boxes, as described


in the operational sections of this presentation. They are mounted on
the substation wall
Operating Instructions

Areva PIX

Procedure to OPEN, establish Points of


Isolation and Earth a Feeder Circuit Breaker
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that you have


identified the correct Panel by
reference to the nameplate.
The Circuit Breaker ON lamp
indicator on the upper panel
and the Neon indicators
between the centre and lower
panels should both be
illuminated
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the VCB status


semaphore through the
viewing window and ensure
that it indicates CLOSED
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Post HV Warning
notices on the
local/remote controls
of adjacent Panels
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that the rotary


LOCAL/REMOTE control of
the Circuit Breaker to be
opened is selected to
REMOTE. This is the normal
setting for the control. Post a
HV Prohibition notice
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 In an adjacent room,
identify the correct remote
control panel for the
Circuit Breaker to be
opened. Apply a HV
Prohibition notice over the
trip/close control of the
Circuit Breaker to be
opened and HV Warning
notices over the trip/close
controls of the adjacent
Circuit Breakers
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Trip the Circuit Breaker at


the remote position
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that the green CB


OPEN lamp indicator is
illuminated
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 On the upper panel of the


selected Circuit Breaker
ensure that the green
OPEN lamp indicator is
illuminated. Note that the
M231 display unit may still
indicate voltage present
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that the Neon indicators


between the centre and lower
panels have extinguished
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 In the viewing window


of the centre panel,
ensure that the
mechanical semaphore
indicates OPEN
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the local/remote


control on the upper panel
and select it to local
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the racking


handle socket on the
centre panel
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Open the socket shutter by rotating the


adjacent button
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Open the socket shutter by rotating the


adjacent button
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Insert the racking handle and


rotate it approximately 21
turns anticlockwise to move
the VCB cassette to the
ISOLATED position. The
handle will automatically
ratchet when the VCB
cassette reaches the
ISOLATED position. Remove
the handle on completion
and close the shutter
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Insert the racking handle and


rotate it approximately 21
turns anticlockwise to move
the VCB cassette to the
ISOLATED position. The
handle will automatically
ratchet when the VCB
cassette reaches the
ISOLATED position. Remove
the handle on completion
and close the shutter
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Insert the racking handle and


rotate it approximately 21
turns anticlockwise to move
the VCB cassette to the
ISOLATED position. The
handle will automatically
ratchet when the VCB
cassette reaches the
ISOLATED position. Remove
the handle on completion
and close the shutter
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Obtain the door handle from


storage and insert it into the
lock on the left hand side.
Rotate the handle
anticlockwise to lift the door
from its latches
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Obtain the door handle from


storage and insert it into the
lock on the left hand side.
Rotate the handle
anticlockwise to lift the door
from its latches
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Open the door and identify


the VCB cassette locking
point in the lower left hand
corner
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Fit an isolock, lock and HV


Prohibition notice to the
locking point

 The Point of Isolation is


established. This lock
prevents complete removal
of the VCB cassette
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Latch the door and post a


magnetic HV Prohibition
notice. Remove the handle
on completion
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Latch the door and post a


magnetic HV Prohibition
notice. Remove the handle
on completion
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Latch the door and post a


magnetic HV Prohibition
notice. Remove the handle
on completion
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the D ring key


clockwise to lock the panel
door closed. Remove the key
and return it to storage
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the D ring key


clockwise to lock the panel
door closed. Remove the key
and return it to storage
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the D ring key


clockwise to lock the panel
door closed. Remove the key
and return it to storage
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the Proof of


Isolation key, rotate
and remove it
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the Proof of


Isolation key, rotate
and remove it
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the Proof of


Isolation key, rotate
and remove it

 The VCB cassette


cannot now be racked
into the service
position
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 If the Circuit Breaker is fitted with a VT, identify the


two threaded fasteners at the base of the panel and
release them. Lift and remove the panel
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 If the Circuit Breaker is fitted with a VT, identify the


two threaded fasteners at the base of the panel and
release them. Lift and remove the panel
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the two keys at the top


of the VT compartment
(illustration shown cut away)
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and pull the bronze handle
outward to the notch position to
isolate the VT
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and pull the bronze handle
outward to the notch position to
isolate the VT
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate both keys to the vertical


position and remove the right
hand key
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate both keys to the vertical


position and remove the right
hand key
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate both keys to the vertical


position and remove the right
hand key

 The VT Point of Isolation is


established
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Apply a HV Prohibition notice


to the bronze handle
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that the Proof


of Earthing key is set
to the horizontal
position, if it is not
already horizontal
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 If the Circuit Breaker


requires a Permissive
Earth key, obtain this
from the associated
remote end location,
insert and rotate it to
the horizontal position
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Lift the shutter control


pin and insert the
earth switch operating
handle
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate the handle


clockwise to CLOSE
the earth switch
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Circuit Earth is now


applied

 Rotate the handle


clockwise to CLOSE
the earth switch
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Remove the handle,


allowing the shutter
control pin to drop
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Remove the handle,


allowing the shutter
control pin to drop
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Ensure that the earth


switch semaphore
indicates EARTH ON
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate and remove


the Proof of Earthing
key
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate and remove


the Proof of Earthing
key
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Rotate and remove


the Proof of Earthing
key
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Apply a lock and HV


Prohibition notice to
the earth switch
socket
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Operating Instructions

Areva PIX

To remove Circuit Earth, restore Points of


Isolation and CLOSE a Feeder Circuit Breaker
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the lock and


HV Prohibition notice
fitted to the earth
switch socket, restore
and turn the Proof of
Earthing key
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the lock and


HV Prohibition notice
fitted to the earth
switch socket, restore
and turn the Proof of
Earthing key
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the lock and


HV Prohibition notice
fitted to the earth
switch socket, restore
and turn the Proof of
Earthing key
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Lift the shutter control


pin and insert the
earth switch operating
handle
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the handle


anticlockwise to open
the earth switch
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the handle


anticlockwise to open
the earth switch

 Circuit earth is now


removed
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the handle


and return it to
storage. Allow the
shutter control pin to
drop
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the handle


and return it to
storage. Allow the
shutter control pin to
drop
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Ensure that the earth


switch semaphore
indicates EARTH
OFF
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 If the Circuit Breaker


is fitted with a
Permissive Earth
lock, the key may
now be rotated,
removed and
returned to its original
remote end location
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 If the Circuit Breaker


is fitted with a
Permissive Earth
lock, the key may
now be rotated,
removed and
returned to its original
remote end location
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 If the Circuit Breaker


is fitted with a
Permissive Earth
lock, the key may
now be rotated,
removed and
returned to its original
remote end location
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Insert and rotate the


Proof of Isolation key
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Insert and rotate the


Proof of Isolation key
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV Prohibition


notice from the centre panel
door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV Prohibition


notice from the centre panel
door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Obtain the door handle from


storage and insert it into the
lock on the left hand side.
Rotate the handle
anticlockwise to lift the door
from its latches
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Obtain the door handle from


storage and insert it into the
lock on the left hand side.
Rotate the handle
anticlockwise to lift the door
from its latches
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Open the centre panel door


and identify the isolock, lock
and HV Prohibition notice
fitted to the VCB cassette
locking point. Remove these
items
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Open the centre panel door


and identify the isolock, lock
and HV Prohibition notice
fitted to the VCB cassette
locking point. Remove these
items
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Close the door and rotate the


handle clockwise to lower it
onto its latches. Remove the
handle on completion and
return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Close the door and rotate the


handle clockwise to lower it
onto its latches. Remove the
handle on completion and
return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Close the door and rotate the


handle clockwise to lower it
onto its latches. Remove the
handle on completion and
return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 If the unit is fitted with a VT,


identify the HV Prohibition
notice fitted to the bronze
handle. Remove this item
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 If the unit is fitted with a VT,


identify the HV Prohibition
notice fitted to the bronze
handle. Remove this item
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Insert the right hand key into


the empty lock at the top of the
assembly
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and push the bronze handle
fully inward to restore the VT to
service. Release the keys to
return to the vertical position on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and push the bronze handle
fully inward to restore the VT to
service. Release the keys to
return to the vertical position on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and push the bronze handle
fully inward to restore the VT to
service. Release the keys to
return to the vertical position on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the left hand key


clockwise and the right hand
key anticlockwise. Press down
and push the bronze handle
fully inward to restore the VT to
service. Release the keys to
return to the vertical position on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Restore the front panel and tighten the two


threaded fasteners
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Open the socket shutter by


rotating the adjacent button
and insert the racking handle
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the handle


approximately 21 turns
clockwise to move the VCB
cassette to the SERVICE
position. The handle will
automatically ratchet when
the VCB cassette reaches
the SERVICE position.
Remove the handle on
completion and close the
shutter
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the handle


approximately 21 turns
clockwise to move the VCB
cassette to the SERVICE
position. The handle will
automatically ratchet when
the VCB cassette reaches
the SERVICE position.
Remove the handle on
completion and close the
shutter
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Rotate the handle


approximately 21 turns
clockwise to move the VCB
cassette to the SERVICE
position. The handle will
automatically ratchet when
the VCB cassette reaches
the SERVICE position.
Remove the handle on
completion and close the
shutter
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 On the upper panel, select


the local/remote control to
remote
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Identify the correct unit on


the remote control panel in
an adjacent room by
reference to the
nameplate. Press the trip
circuit healthy push button
to ensure that the trip
circuit is functioning
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON

 The circuit is now


energised
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the Warning


notices from the adjacent
units
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the Warning


notices from the adjacent
units
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 On the upper panel of the


selected Circuit Breaker,
ensure that the red
CLOSED lamp indicator is
illuminated. Remove the
HV Prohibition notice from
the local/remote control
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 On the upper panel of the


selected Circuit Breaker,
ensure that the red
CLOSED lamp indicator is
illuminated. Remove the
HV Prohibition notice from
the local/remote control
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Ensure that the Neon indicators


between the centre and lower
panels have illuminated
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 In the viewing window


of the centre panel,
ensure that the
mechanical semaphore
indicates CLOSED
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV
Warning notices from
the local/remote
controls of adjacent
Circuit Breakers on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker

 Remove the HV
Warning notices from
the local/remote
controls of adjacent
Circuit Breakers on
completion