VCB Cassette
Switchgear
DESCRIPTION AND
GUIDE TO OPERATIONS
Actions and Information
Red arrow/text indicates an instruction
This key cabinet is one of three that are located adjacent to each other
within the substation. They are used to store operational keys for the
switchgear
CENTRE PANEL
If a VT is fitted it will be
located inside the lower
compartment – note that
units fitted with a VT do not
have a window in the lower
panel. Under safe
operational circumstances
the panel may be
unfastened and lifted off to
reveal the VT fuses,
instruction labels, locks
and withdrawal handles.
The function of the handles
and locks is explained in
the operational sections of
this presentation
REMOTE CONTROL
PANEL
Areva PIX
Post HV Warning
notices on the
local/remote controls
of adjacent Panels
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
In an adjacent room,
identify the correct remote
control panel for the
Circuit Breaker to be
opened. Apply a HV
Prohibition notice over the
trip/close control of the
Circuit Breaker to be
opened and HV Warning
notices over the trip/close
controls of the adjacent
Circuit Breakers
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Procedure to OPEN, establish Points of Isolation and Earth a Feeder
Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 lock and
open it. Place the key to the isolock/lock retaining the VCB cassette, the
Proof of Isolation key, the Proof of Earthing key, the key removed from the
earth shutter lock and the key removed from the VT lock (if a VT is fitted)
inside complete with their identity discs. Remove the LOB XX lock and key
stored inside the box and use it and the LOB 500 lock to secure the door
Operating Instructions
Areva PIX
Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Identify the lock out box in the Substation, remove the LOB 500 and LOB
XX locks and open it. Remove the key to the isolock/lock retaining the VCB
cassette, the Proof of Isolation key, the Proof of Earthing key, the key for the
earth shutter lock and the key for the VT lock (if a VT is fitted) inside
complete with their identity discs. Replace the LOB XX lock inside the box
and secure the door with a LOB 500 lock
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Obtain the D ring key from storage and insert it into the keyway at
the base of the centre panel door. Rotate the key anticlockwise to
unlock the centre panel door
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Rotate the D ring key clockwise to lock the centre panel door,
remove it on completion and return it to storage
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Remove the HV
Prohibition notice from the
rotary trip/close control
and close the CB to ON
Remove the HV
Warning notices from
the local/remote
controls of adjacent
Circuit Breakers on
completion
Procedure to remove Circuit Earth, restore Points of Isolation and
CLOSE a Feeder Circuit Breaker
Remove the HV
Warning notices from
the local/remote
controls of adjacent
Circuit Breakers on
completion