Professional Documents
Culture Documents
AND AMPLIFIERS
10-1 SOLENOID VALVES
• Floating control
• Measured value is too low, valve is open
• Measured value is too high, valve is closed
• Measured value is between differential gap, valve not driven and
same position
10-3 PROPORTIONAL-POSITION
ELECTRIC MOTOR-DRIVEN
VALVES
Shane M. Acana
10.7.1 On-Off Control of Current to a Load
• The only difference between a relay and a contactor is in the current-
carrying and interrupting capability of the contacts.
• Contactors are capable of handling large currents , whereas relays
can handle only relatively small currents.
10.7.2 Relay Hysteresis
10.7.3 A Three-Phase Contactor Switching between Delta
and Wye
To prove that the delta configuration delivers more power to the three
phase heating element than that of the wye configuration…..
10.8 thyristors
Shane M. Acana
• In modern control systems, power thyristors, namely
SCRs and triacs, are used as final correcting devices.
• Thyristors lend themselves quite well to proportional
control of temperature.
• In a thyristor open-loop system, current to the load is
continuously variable, but there is no built-in
comparison between measured value and set point to
bring about automatic adjustment of current.
• For example,
• The most important use of thyristor is in varying the
current through a motor winding to adjust the speed
of the motor.
SPLIT-PHASE AC
MOTORS April Rose P. Siton
➢Split-phase motors are motors for opening and closing
flow-control valves.
• When a rotor is inserted into our split-phase motor, forces will be exerted on
it to make it follow the rotating field. If the field rotates clockwise, the rotor
will rotate clockwise. If the field rotates counterclockwise, the rotor will
rotate counterclockwise.
➢ Creating the Phase Difference between the Two Winding Currents