Class Presentation in
Explanatory Example on
Ductile Detailing
According to IS1893-Part I
Presented By
Amrit Regmi
Msc in Structural Engineering(2019)
Roll no: 1
From the problem, we see that:
1. The building is located in seismic zone 5.
2. It is an official building.
3. The building is located at type II (Medium Soil)
4. Building is required to be provided with moment resisting frame.
Hence, Z=0.36
2. It is an official building.
From table 6 of IS1893-Part1
Hence, I= 1.0
3. The building is located at type II (Medium Soil)
i) First we find the Fundamental Natural period of the building
From Clause 7.6.2 of IS1893
h=13.8m
Hence,
Hence, R= 5.0
Finally, Design Horizontal Seismic Coefficient Ah
can be found
From clause 6.4.2 of IS1893
Since,
Z=0.36 Hence,
R=5
Sa/g=2.5
Now, we find the seismic weight of the structure:
Hence,
W=15,600KN
Finally, Design Base Shear can be calculated:
From clause 7.5.3 of IS1893
Hence,
VB= 1440KN in both X & Y direction
Lateral Force Distribution With Height by static method:
Conclusion: