Lightning protection was installed and tested near shelters at well pads A, B, and C. Measurements were taken at three locations near shelter A and found resistance levels below 1 ohm, meeting the standard of not more than 5 ohms. Certificates and photos documented the testing equipment.
Original Description:
Original Title
08. Measurment and Testing of Lightning Protection at Well Pad A, B and C
Lightning protection was installed and tested near shelters at well pads A, B, and C. Measurements were taken at three locations near shelter A and found resistance levels below 1 ohm, meeting the standard of not more than 5 ohms. Certificates and photos documented the testing equipment.
Lightning protection was installed and tested near shelters at well pads A, B, and C. Measurements were taken at three locations near shelter A and found resistance levels below 1 ohm, meeting the standard of not more than 5 ohms. Certificates and photos documented the testing equipment.
EPC1 - Production Processing Facilities Contract No. C-3207067 Location of Lighting protection been installed and tested
1. Near Shelter at Well Pad A
2. Near Shelter at Well Pad B 3. Near Shelter at Well Pad C Certificate of Equipment for testing and photographs of equipment Result of Measurement Lightning Protection
No Location Standard Result
1 Near Shelter at Well Pad A Not more than 5 Ω 00.9 Ω 2 Near Shelter at Well Pad A 00.8 Ω 3 Near Shelter at Well Pad A 00.7 Ω