MEASUREMENT LIGHTNING

PROTECTION AT WELL PAD A, B AND C

BANYU URIP PROJECT


EPC1 - Production Processing Facilities
Contract No. C-3207067
Location of Lighting protection been installed
and tested

1. Near Shelter at Well Pad A


2. Near Shelter at Well Pad B
3. Near Shelter at Well Pad C
Certificate of Equipment for testing and photographs of
equipment
Result of Measurement Lightning Protection

No Location Standard Result


1 Near Shelter at Well Pad A Not more than 5 Ω 00.9 Ω
2 Near Shelter at Well Pad A 00.8 Ω
3 Near Shelter at Well Pad A 00.7 Ω