• Outside state: 28°C dry-bulb, 19.5°C wet-bulb (sling), 10.65 g.kg-1.

• Room state: 22°C dry-bulb, 50% saturation, 8.366 g.kg-1.


• Sensible heat gain = 1250
• Latent heat gain = 134
Cooling load
Qr = [Qs + Ql + Qfa + Qsf + Qsa + Qra + Qrh]fp where
• Qr = design refrigeration load [kW]
• Qs = sensible heat gain [kW]
• Ql = latent heat gain [kW]
• Qfa = fresh air load [kW]
• Qsf = supply fan power [kW]
• Qsd = supply duct heat gain [kW]
• Qra = return air load (recirculation fan power and heat gain through extract
ventilated luminaires)
• Qrh = reheat load
• fp = factor to cover chilled water pump power and heat gain to pipes