CONTROL (CMC)
By
V.Hariayyappan
EHTC
Electro-Hydraulic Turbine Controller
ESSENTIALLY CONSISTS OF THE FOLLOWING CONTROL
LOOPS:
1. SPEED CONTROL LOOP.
2. LOAD CONTROL LOOP.
3. PRESSURE CONTROL LOOP.
ONE OF THESE THREE LOOPS ACT SELECTIVELY ON
THE SUBORDINATE VALVE LIFT CONTROL.
THE VALVE LIFT CONTROLLER ACTUATES THE
PLUNGER COIL OF THE ELECTRO-HYDRAULIC
CONVERTER WHICH ACTS AS AN INTERFACE BETWEEN
THE ELECTRICAL AND THE HYDRAULIC SYSTEM.
SPEED CONTROLLER
Speed Control
REALISES THE FOLLOWING OPERATIONS:
1. START-UP AND SHUTDOWN OF TURBINE
2. SYNCHRONISATION OF THE GENERATOR
Grid
MS Pr. Set point
PD
BOILER Turbine
PID
EHG Pr G
Ctrlr
+ +
Fuel Ctrl Air Ctrl
LOAD
MS Pressure
Actual
PR. Tx.
GRID
Boiler Pr. Set Point
EHG
PI Controller
Turbine Generator
Fuel & Air
CHARACTERISTICS OF TURBINE FOLLOW MODE
master control).
Furnace pressure control in auto (IGV and
CMC MODE…
OTHER CONDITIONS
Select the LP mode (from EHTC page).
PA header pressure control in auto.
Both HPBP should be closed.
Load deviation within limits (i.e. the deviation between load SP and
actual load should be less than 4.2MW).
MS pressure deviation within limits (difference between MS set point
and actual MS pressure should not be high preferably within +
2kg/cm2).
HPCV should be throttled (i.e. turbine should not be running under
valve wide open condition).
Unit should be running under steady state (MW and fuel flow are
reasonably steady for about 10-15 minutes).
CMC MODE…
Ensuring all these conditions and auto loop status
proceeding to the next step
Put the CMC on(i.e. from the popup given on EHTC
page )
Now put the boiler master in auto
The selection of plant mode control will be in manual.
Then select the coordinate control from the popup given
on the load page (CMC page).
SALIENT FEATURES OF CMC
DOWN
RUN
Run down is switched ON automatically when the Process
error(negative) i.e. Feed water, Air flow etc. becomes excessive
AND(&) the controller output of the particular loop(feed water, air
flow, furnace pressure and fuel) goes to maximum position making
process uncontrollable. Under the situation, Unit load demand is
reduced to a value as Permitted by the Process to get over the
blockage.
INCREASE BLOCKED
In this if any of the condition comes i.e. if process error (negative)
OR the controller output goes to maximum then Incr. blocked will
come and it will hold the unit load demand till process recovers
within limits.
FEATURES OF CMC…
CONDITIONS FOR RUN DOWN/INC.
BLOCKED