STANDARD OPERATING PROCEDURE

Jaypee Nigrie Super Thermal Power Plant


2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 1 of 9
Revision Date:

STANDARD OPERATING
PROCEDURE
FOR

TG ELECTRO HYDRAULIC OIL


PUMP

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 2 of 9
Revision Date:

List of Contents

1. Objective
2. Scope
3. Introduction
4. Responsibility
5. Safety Precaution During operation
6. Safety Ppe’s
7. Special Tools/ Equipments
8. Pre checklist by Field engineer
9. Operating Procedure
10. Shutdown Sequence
11. Abbreviations / Notations
References

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 3 of 9
Revision Date:

1. Objective:
For Smooth Operation of EH Oil pump.

2. Scope:
This SOP is applicable for 2 nos. of EH Oil pump.

3. Introduction:

EH oil system is also termed as regulation and safety protection system. The
system is designed to assure the secure and reliable operation of mechanism
of the HP fire-resistant oil in digital electro hydraulic control system
(DEH)The system execute DEH command, completing corresponding task
such as latch, driving valves, shutting of units. The system is common for
supply oil to operation of ESVs, CVs and 2 recirculation pumps for cooling
and filtration of oil. Discharge of recirculation pump partly flows through
cooler and partly through filter. There are 6 accumulators to meet the
sudden pressure demands. Fire resistant oil is used in the system to avoid
fire in case of leak from valves as oil falls on high temp steam lines. Filters
are provided in EH oil pump discharge and recirculation pump discharge to
be observed from local only. One more filter is provided in oil inlet to control
valve filter clogged. Choke indication is provided in local as well as also
provided for filters in CVs, ESVs supply line. Filter is provided after the
cooler also .Thermostatic valve is provided in cooling water inlet to cooler to
control tank temperature.

EH Oil pump Technical Data:


Oil Pump
Make
Type & nos. Axial piston, 2nos. (2x100%)
Capacity 100L/min
Pressure 120kg/cm2(g)
Rated power & Speed 37kw/1000 rpm
Oil Cooler
Type of cooler Shell & tube type

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 4 of 9
Revision Date:

Number of cooler 2
Fluid flow 100L/min
Fluid inlet/outlet temp 65& 60˚C
Ccw Inlet/outlet temp 36&39˚c
Ccw flow 100L/min
Frictional drop on fluid side and water side 0.7kg/cm2
Pressure Data
Min pressure of fire resistance oil required >93kg/cm2
in main pipe
Oil pressure for relief valve 150kg/cm2
Working temperature 30-70˚c
EH emergency trip oil pressure 70kg/cm2
Lubrication oil specification
Type Daphane super turbine32,SP32,New turbo
J32
Kinematic viscosity at 40 ˚c 28.8 to 35.2mm2/s(cst)
Flash point Min200˚c
Pour point Min-12˚c

4. Responsibility:
Unit Control Engineer, Field Engineer and Desk engineer

5. Safety Precautions:
Ensure No Permit To Work Is Pending On Regarding This
System By Checking With EE/MRSE.
6. Safety Ppe’s:
Ear Plugs, Safety Goggles, Hand Gloves, Etc.

7. Special Tools/ Equipments : Nil

8. Pre Checklist by Field engineer:

Sl.N Not
Description Ok Remarks
o Ok

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 5 of 9
Revision Date:

Ensure that the Work permits on various turbine


control oil system such as control fluid tank,
1 governing rack, coolers, accumulator, valve
actuators, pumps and various interconnecting pipe
are closed and men, material are removed from
2 Ensure EH Oil tank level normal

3 Ensure sprinkler system in service.

Ensure local pressure, temperature, level gauges


4 and
transmitters are charged

Put on the power supply to the EH oil pump and


5
circulation pump
Put on the power supply to the local control panel
6 and check the indication bulbs are glowing.

Check the line up of the in line double filters


7
provided in the high pressure control system
Charge the control fluid oil coolers from water
8
side(CCCW Pr.> 0.4kg/cm2)
9 Put accumulator( 6nos.) in service

10 Put EH oil circulation pump in service


Put EH oil heaters in service. heater will start on
11 auto at temp.<30 deg.C and cut off at temp.>70
deg.C
Line up the EH oil to main turbine, TDBFP A&B by
12
opening supply valves.
13 Start EH oil pump

9. Operating Procedure:

Prestart Check
Sl.No Description Ok Not Ok Remarks
1 All permits and cross permits have been returned.
2 EH oil tank level is normal

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 6 of 9
Revision Date:

3 Power supply module is ON. (TURBINE MCC).


4 Keep pumps ON/ OFF selection in ON i.e.
remote.
5 Pump suction valve is in open.
6 CCCW pump is in service
7 EH oil cooler, oil inlet valve is open.
8 EH cooler CW inlet, outlet valves are open.(ccw)
9 EH oil system CW main inlet, outlet valves are open
10 Recirculation filter inlet valve is open.
11 Stroke regulating valve set at %
Start Permissive
12 EH Oil temperature > 30˚c & 70˚c
13 EH oil tank level should be normal

Post start-up of EH oil pump


Check the discharge pressure (>93ks/cm2) and
14
motor current.
Check other EH oil pump availability and keep in
15 standby mode .standby pump starts when pressure
reaches 93 Kg/cm2
Keep the recirculation pump on auto after checking
16
its healthiness.
Trip oil will generate when main turbine is reset or
17
latched.
18 Check filters DP

10. Shutdown Sequence:

Sl.No Description Ok Not Ok Remarks


Planned shutdown
Ensure that Main Turbine, in stopped
1.
condition.
2. Stop EH oil pump

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 7 of 9
Revision Date:

Stop recirculation pump, if shut down is for


3.
long period.
Emergency operation of EH oil pump
If oil pressure goes low <70kg/cm2 other
4
pump start on auto
Check the pump condition and any oil
5
leakage in the system.
If oil pressure goes less than turbine will
6
trip
If oil temperature goes high, check the
7 cooling water pressure should be normal.
Also check heater is cut off.
Emergency shutdown of EH oil pump
8 Stop the pump
Release the interlocking switch of faulted
9 pumps and the operating pump should be
normal
Report to the shift in charge and work order
raised for put it into standby after correcting
10
fault.

11. Abbreviations / Notations

1. SOP: Standard Operating Procedure


2. UCE: Unit Control Engineer
3. DE: Desk Engineer
4. FE: Field Engineer
5. DCS: Distributed Control System
6. EE: Electrical Shift Engineer
7. MFT: Main Fuel Trip.
8. RB: Run Back

References
1. L&T O & M manual

Standard Operating Procedure


STANDARD OPERATING PROCEDURE
Jaypee Nigrie Super Thermal Power Plant
2 X 660 MW IPP
SOP FOR TG ELECTRO HYDRAULIC OIL PUMP
Revision No.: 01
Document No.: PMPL/SOP/08 Effective Date: 1st Jan 2015 Page 8 of 9
Revision Date:

2. EH Oil system drawing & P & I Drawing