IR-CFBC BOILER

DRIVE START/STOP LOGIC


ASHVANI SHUKLA
RELIANCE
C&I
MAIN EQUIPMENT

 I.D. FAN
 P.A. FAN
 S.A. FAN
 COAL FEEDER
 GRAVIMETRIC COAL FEEDER
 BED MATERIAL RAV
 LIME STONE RAV
 HP DOSING PUMP

I D FAN

 
 START PERMISSIVE
 DRIVE AVAILABLE FOR DCS CONTROL
 ID FAN INLET DAMPER IN CLOSE POSITION
 ID FAN BEARING TEMPERATURE NORMAL
 ID FAN MOTOR BEARING TEMPERATURE NORMAL
 FURNACE PRESSURE NORMAL
 FLUE GAS PATH SHOULD BE THROUGH
I D FAN
 TRIP INTERLOCK
 ID FAN BEARING TEMPERATURE VERY HIGH
 ID FAN MOTOR BEARING TEMPERATURE VERY HIGH
 ID FAN DE VIBRATION X-AXIS HIHI
 ID FAN DE VIBRATION Y-AXIS HIHI
 ID FAN NDE DE VIBRATION X-AXIS HIHI
 ID FAN NDE VIBRATION Y-AXIS HIHI
 ID FAN MOTOR DE VIBRATION X-AXIS HIHI
 ID FAN MOTOR DE VIBRATION Y-AXIS HIHI
 ID FAN MOTOR NDE DE VIBRATION X-AXIS HIHI
 ID FAN MOTOR NDE VIBRATION Y-AXIS HIHI
 FURNACE PRESSURE VERY LOW
 OUT OF FIVE THREE TRANSFORMER TRIPPED FIELD-1
 OUT OF FIVE THREE TRANSFORMER TRIPPED FIELD-
PA FAN

 PA FAN START PERMISSIVE


 DRIVE AVAILABLE FOR DCS CONTROL
 PA FAN INLET DAMPER IN CLOSE POSITION
 PA FAN BEARING TEMPERATURE NORMAL
 PA FAN MOTOR BEARING TEMPERATURE NORMAL
 FURNACE PRESSURE NORMAL
 WIND BOX PURGE COMPLETED OR PA FAN RUNING OR BED TEMPERATURE<200
 ID FAN RUNNING
 DRUM LEVEL NORMAL
 PA FAN PRESSURE AFTER APH NORMAL