You are on page 1of 104

Open seminar on

IMPROVEMENT OF CERTAIN POWER QUALITY ISSUES OF TRANSMISSION


SYSTEMS WITH POWER FLOW CONTROLLERS

By
RAJAREDDY. DUVVURU
[Reg. No. 13PH0217]
Under the esteemed Guidance of

Supervisor Co-Supervisor
Dr. B.VENKATA PRASANTH Dr.V.Ganesh
Prof & Head Prof & Head
EEE Department EEE Department
QISCET, Ongole JNTUACEP, Pulivendula

Department of Electrical and Electronics Engineering

JNTUCEA , ANANTAPUR

October -29, 2018


09/25/2020 JNTUA 1
Contents
1. Introduction
2. Problem Definition
3. Objectives
4. Organization of Thesis
5. Conclusions
6. References
7. Publications

09/25/2020 JNTUA 2
Introduction
 Now a days, power system network influences losses of
transmission system (apporx. 30%). These losses can be
reduced by series compensation with capacitor banks or
synchronous phase modifiers.
 Synchronous phase modifiers and capacitor banks are incapable
to supply maximum amount of power transfer to load.
 Now a days these losses can reduced by using custom power
devices like power electronic based Flexible AC Transmission
system (FACTS) control devices.

09/25/2020 JNTUA 3
 Flexible AC Transmission system is a static equipment and it is
a integrated concept based on power electronic switching
converters and dynamic controllers to enhance the system
utilization and power transfer capacity.
 FACTS devices are used to control the interrelated parameters
such as series impedance, shunt impedance, current, voltage
and phase angle which govern the operation of transmission
systems.

09/25/2020 JNTUA 4
FACTS device controllers can be divided into four categories.
1. Series Controllers : series controllers are;
 It has variable impedance and has a function to inject the series voltage.

Thyristor Controlled Series Capacitors (TCSC), Static Synchronous Series


Compensator( SSSC), Distributed Static Series Compensator (DSSSC).

Figure 1: series controller

09/25/2020 JNTUA 5
2. Shunt controllers : shunt controllers are ;
 It has variable impedance and has a function to inject the current into the
system.
Static Var Compensator (SVC), STATCOM

Figure 2: shunt controller


09/25/2020 JNTUA 6
3.Combined series-series controller : Interline Power Flow Controller
(IPFC)

Figure 3: series - series controller

 It has separate but co-ordinated unified(common dc link)


controller and has a capability to compensate reactive power as
well as interline transfer active power.

09/25/2020 JNTUA 7
4. Combined series-shunt controllers : Unified Power
Flow Controller (UPFC)

Figure 4: series - shunt controller


 It has capability to inject voltage & current and has
unified & co-ordinated real power exchange between
series & shunt converter.

09/25/2020 JNTUA 8
 Because of high control capability the Power Electronic based
combined Power Flow Controllers specifically UPFC is
suitable for transmission system of power system.
 The FACTS devices are installed at different locations for
different purposes, each of them is unique. As a result, each
FACTS device requires customer design and manufacturing,
which leads to a long building cycle and high cost, it requires a
large area for installation.

09/25/2020 JNTUA 9
Problem Definition

The UPFC has capability to control power flow but it has own
draw backs of this device are :
1. one of the reasons is high cost for the same ratings of
FACTS devices. This device requires a large number of
power electronic switches in series and parallel connection.

2. To provide voltage isolation, 3-phase high voltage


transformers are essential and series connected transformers
requires an higher rating to handle the fault voltages and
currents.
09/25/2020 JNTUA 10
3. Possibility of faults may occurs in the UPFC are:
a) For a shunt converter, failure results in a disconnection of the
device from the grid which prevents it from providing reactive
compensation.
b) The series converter is directly inserted into transmission lines,
not only the device, but also the transmission lines will be
disconnected from the system during the failure.

 Due to these reasons UPFC cannot manage the all parameters,


so we are focused on advanced UPFC devices.

09/25/2020 JNTUA 11
 The UPFC is further developed into a new combined FACTS
devices such as Distributed Power Flow Controller (DPFC) and
Generalized Unified Power Flow Controller (GUPFC).
 These two controllers will provide better performance compared
to UPFC.
o DPFC and GUPFC can be used to improve the performance of

the system due to the separate controlling capability of real


power, reactive power, phase angle, voltage magnitude, grid
currents and oscillations .

09/25/2020 JNTUA 12
Objectives of work
Main objectives of work are :

1. (a) To Investigate the Power Quality issues in Transmission system


by using DPFC with Proportional Integral Derivative (PID) Controller.

(b) It is also analyze the performance of the DPFC during the failure

of a single series converter.

2. To Examine the capability of the DPFC to damp low frequency

power oscillations and voltages by using Power Oscillation Damping

(POD) controller.

09/25/2020 JNTUA 13
3. (a) To Analyze the Power Quality issues in Transmission
system by providing a GUPFC-PID controller
(b) To Damp out low-frequency power oscillation by using
GUPFC with POD controller.
 These results are analyzed with DPFC and GUPFC and also
performance of these devices are validated with test systems.

09/25/2020 JNTUA 14
Organization of the Thesis

My research work is divided in to three modules.

Module-I
(a) Analyze the power quality issues like voltage sag, current swell and Total
Harmonic Distortions during the fault condition without and with DPFC-PID
controller.
(b) It is also analyzes the active power, reactive power, currents and voltages in
transmission line during the failure of a single series converter by providing a
PID controller.
Module-II

(a) Investigates DPFC is used to damp out the low frequency power oscillations
like active and reactive power oscillations and voltages at generator side.

09/25/2020 JNTUA 15
Module-III

(a) Investigate the power quality issues like voltage sag, current
swell and THD during the fault condition and after placing
GUPFC with PID controller.
(b) It is also Investigates low frequency power oscillations like
active power and reactive power and also analyze the
voltages during the fault condition and after placing GUPFC-
POD controller.

09/25/2020 JNTUA 16
Module -I
IMPROVEMENT OF POWER QUALITY IN
TRANSMISSION SYSTEM USING DPFC
&
PERFORMANCE OF DPFC DURING FAILURE
OF SERIES CONVERTERS

09/25/2020 JNTUA 17
Distributed Power Flow Controller(DPFC)

 DPFC employs the Distributed FACTS(D-FACTS) concept.

 DPFC is derived from the UPFC, it behaves like as UPFC.

Figure 5: flow chart from UPFC to DPFC

09/25/2020 JNTUA 18
Figure 6 : Schematic diagram of DPFC
09/25/2020 JNTUA 19
DPFC Operating Principle
The DPFC consists of a shunt and several series connected converters. Each
converter within the DPFC is independent and has its own dc capacitor to
provide the required dc voltage.

The shunt converter is similar as a STATCOM, while the series converter


employs the D-FACTS concept, which is to use multiple single-phase converters
instead of a large rated converter.

Two approaches are applied to the UPFC to increase the reliability and to
reduce the cost; they are as follows
(i) eliminating the common dc link of the UPFC and exchange of active
power,
(ii) distributing the series converters,
09/25/2020 JNTUA 20
Exchange of active power

Figure 7 : block diagram of active power exchange in transmission line

09/25/2020 JNTUA 21
DPFC with PID controller
The working of proposed system is sensing the receiving end

voltage and it compares with the reference voltage. Output of the


summer i.e. error signal is given to the PID controller block, and it
gives to DPFC controller.

Figure 8: block diagram of proposed system with PID controller

09/25/2020 JNTUA 22
In this proposed work is tested 3-test cases.

1. Single machine connected to infinite bus system

2. Two bus system

3. Standard test system of 30-bus system.

09/25/2020 JNTUA 23
Simulation Results


The DPFC is tested in a single machine connected to infinite
(SMIB) bus and 30-bus system.

It is proposed that three phase fault is injected in transmission
line of proposed system in order to measures the voltage sag,
current swell and THD values without DPFC and with DPFC.
Case 1 : Single machine connected to infinite bus
Case 2 : standard 30-bus system .

09/25/2020 JNTUA 24
Case 1: SMIB

Figure 9: single line diagram of SMIB

1. Voltage Sag

In the simulation model for time t = 0.07 sec the DPFC is connected to the
source. Up to t = 0.07 sec the three phase source is supplying the power to
the load. After at time of 0.07sec 3-ph fault is injected to system.

09/25/2020 JNTUA 25
Vvoltage (pu)
Vvoltage (pu)

(a) (b)
Figure 10: Three-Phase load voltage sag without and with DPFC

 It is observed that above results during the fault the voltage sag is about
0.38 pu during the time period 0.07 sec to 0.11 sec as shown in above
figure 10(a).
 By placing a DPFC, the voltage sag is reduced effectively as shown in
above figure 10(b).
09/25/2020 JNTUA 26
2. Current Swell
Current (pu)

Current (pu)
(a) Time (sec) (b)
Figure 11 : Three-Phase load current swell without DPFC with DPFC

 It is observed that above results during the fault the current levels are increased to 0.4 p.u
during the time period 0.07 sec to 0.11 sec as shown in above figure 11(a).
 By placing a DPFC, the current swell is decreased effectively as shown in above figure 11(b).

09/25/2020 JNTUA 27
3. Total Harmonic Distortion
 Load voltage harmonic analysis without and with DPFC through
FFT analysis is analyzed for test case 1.

Figure 12 : Total harmonic distortion of load voltage without and with DPFC

 From figure 12 it is observed that after placing DPFC the THD values
is reduced from 11.83% to 0.51%.
09/25/2020 JNTUA 28
Table 1 : Summary of test results for voltage sag, swell and THD.

DPFC with PI controller by DPFC with PID controller


Parameters Without DPFC Ahmad et al. (Proposed)

Voltage sag 55% 12% 10 %

Current swell 20 % 12 % 10 %

THD 11.83 % 0.65 % 0.51 %

09/25/2020 JNTUA 29
Case 2 : 30 bus system.

Figure 13 : 30-bus standard bus system

09/25/2020 JNTUA 30
Figure 14 : 30-bus standard bus system with DPFC

09/25/2020 JNTUA 31
1. Voltage Sag

In the simulation model for time t=0.07 sec the DPFC
is connected to the source. Up to t = 0.07 sec the three
phase source is supplying the power to the load. After
time of 0.07sec 3-ph fault is injected to system.

09/25/2020 JNTUA 32
Vvoltage (pu)
Vvoltage (pu)

(a) (b)
Figure 15: Three-Phase load voltage sag without and with
DPFC

 It is observed that above results during the fault voltage sag about 0.4 p.u during
the time period 0.07 sec to 0.11 sec as shown in above figure 15(a).
 By placing a DPFC, the voltage sag is reduced effectively as shown in above
figure 15(b).
09/25/2020 JNTUA 33
2. Current Swell
Current (pu)

Current (pu)
(a) Time (sec) (b)
Figure 16 : Three-Phase load current swell without DPFC with DPFC

 It is observed that above results during the fault the current swell is about 0.38 p.u during
the time period 0.07 sec to 0.11 sec as shown in above figure 16(a).
 By placing a DPFC, the current swell reduced effectively as shown in above figure 16(b).
09/25/2020 JNTUA 34
3.Total Harmonic Distortion
 It is observed that the load voltage harmonic analysis without and with
DPFC by placing a DPFC the THD will be reduced from 11.83% to
0.44%.

Figure 17 : Total harmonic distortion of load voltage without and with DPFC
09/25/2020 JNTUA 35
Table:2 power flow analysis for SMIB with PID Controller
S. no Bus from Bus to Power Flows with out Power Flows with DPFC
DPFC SMIB SMIB

P (MW) Q (MVAr) P (MW) Q (MVAr)

1 1 2 96 -120 124.0 -114.2

Table:3 power flow analysis for 30-bus system with PID Controller

S. no Bus from Bus to Power Flows without DPFC Power Flows with DPFC
(SMIB) (SMIB)

P (MW) Q (MVAr) P (MW) Q (MVAr)

1 1 2 96 -120 124.0 -114.2

09/25/2020 JNTUA 36
2 1 3 0.00098 -0.000158 0.001375 -0.000846

3 2 4 9.70 -89.21 14.12 -121.7

4 3 4 9.70 -89.21 14.12 -121.7

5 4 6 9.70 -89.21 14.12 -121.7

6 5 7 1021 -969.20 1550 -1501

7 6 7 398 -1024 512.6 -1494

8 6 8 0.00089 -0.000102 0.001827 -3.6*10-3

9 8 28 1060 -1024 1560 -1510

10 9 10 1.96 -35.2 2.218 -74.37

11 9 11 1.96 -35.2 2.218 -74.37

12 11 9 1.96 -35.2 2.218 -74.37

13 12 13 292.2 -201.3 389.9 -375.2

14 12 14 89.21 -289.34 124.6 -404.0

15 14 15 1.96 -45.7 2.218 -74.37

16 15 18 1.96 -45.7 2.218 -74.37

09/25/2020 JNTUA 37
17 16 17 1.96 -45.7 2.218 -74.37

18 17 10 1.96 -45.7 2.218 -74.37

19 18 19 1.96 -45.7 2.218 -74.37

20 19 20 1.96 -45.7 2.218 -74.37

21 20 10 1.96 -45.7 2.218 -74.37

22 21 22 201.2 -201.3 389.9 -375.2

23 22 10 89.21 -289.34 124.6 -404.0

24 22 24 159.3 -520.7 249.2 -808.1

25 24 25 201.5 -863.6 373.8 -1212

26 25 26 840.5 -920.3 1170 -1126

27 27 25 0.00104 -0.00024 0.001827 -0.000301

28 27 28 0.0040 -0.000254 0.0099 -0.000210

29 28 8 909.1 -1005 1198.5 -1316

30 29 30 0.00156 -0.00025 0.003655 -0.00092

31 30 27 0.00089 -0.00035 0.001827 -0.00241

09/25/2020 JNTUA 38
Table 4 : Summary of test results for voltage sag , current swell and THD

Parameters Without DPFC with DPFC with


PID controller PID controller
DPFC (Proposed) (Proposed)
(SMIB) (30-bus
system

Voltage sag 55% 10 % 9%

Current swell 20 % 10 % 9%

THD 11.83 % 0.51 % 0.44 %

09/25/2020 JNTUA 39
 In case failure of series converter for DPFC. Because, the series
converter directly connected to the transmission line through
transformer.

Figure 18 : Location of the supplementary control for the series converter


failure
09/25/2020 JNTUA 40
a. Two types of failures can happen in the DPFC series
converters: short circuit and open circuit. The short circuit for
the series converters is not a problem, because it will not
interrupt the transmission line.

b. However, when the series converters have an open circuit, the


transmission line will be also open circuit thereby influencing
the whole network. To prevent the open circuit of the series
converters, a bypass circuit is provided for each series
converter.

09/25/2020 JNTUA 41
 Series converter voltage is given by;

where k is the number of failed converter in phase a. By using


sequence analysis, this unbalanced series voltage can be
represented by;

Ex: No. of series converters n =3


Failure converter k= 1

Fault occurs in phase a is Vse,a = (n - k)/n =0.0667


09/25/2020 JNTUA 42
2-bus system:
 Here analyze the two-bus system with DPFC converter , by considering

two busses as a constant voltage source.

Figure 19: 2-bus system with DPFC

 Each series converter generated 0.0667 p.u voltage at the fundamental


frequency.
o One of the series converters is created with short circuit during the

duration 0.02 second to 0.08 seconds to analyse the effect of DPFC.


09/25/2020 JNTUA 43
(a) (b)

Figure 20 : Series converter voltages at bus1 and bus2 during fault and after fault


It is observed that during the fault shown in figure 20(a), voltage magnitude will be reduces

certain value upto 0.08 sec.


By placing a DPFC, voltage magnitude is compensated during this time, the voltage

magnitude is increases by 0.2 p.u for the duration of 0.02sec to 0.08 sec as shown in figure

20(b).

09/25/2020 JNTUA 44
(a) (b)
Figure 20(A): (a) Three phase currents with DPFC at bus1 and bus2 after fault
(b) Three phase voltage & current with DPFC at receiving end after fault

09/25/2020 JNTUA 45
P(pu)
Q(pu)

Q(pu)
P(pu)

(a) (b)
Figure 21 : Active & Reactive power during serious converter failure and after fault

o It is observed that above results during the fault, active and reactive power are

oscillates for more time duration as shown in figure 21(a).


o By placing a DPFC these oscillations is reduced with in short duration

as shown in figure JNTUA


09/25/2020 21(b). 46
Table 5 : Summary of test results for active power and reactive
power

Parameters Without DPFC DPFC with PI DPFC with


controller by PID controller
Yuan et al. (Proposed)
Active 20 % 12% 10 %
power
Reactive 20 % 12 % 8%
power

09/25/2020 JNTUA 47
Module- II
MODELLING OF DISTRIBUTED POWER FLOW
CONTROLLER (DPFC) FOR DAMPING OF POWER
OSCILLATION

09/25/2020 JNTUA 48
 In this module, low frequency power oscillations cause severe
problems on generator side, due to suddenly fault occurs in
transmission line and harmonic currents enters into generator
winding , it will oscillate the generator continuously.
 These type of oscillations can be reduced by providing a Power
Oscillation Damping (POD) controller.

09/25/2020 JNTUA 49
Design of POD controller

 In order to damp oscillations, POD controllers should be attached


to DPFC control. The structure of a POD controller is as shown
in figure 22 below and it is similar to PSS controllers.

Figure 22 : Block diagram of POD controller

09/25/2020 JNTUA 50
 It involves an amplification block, a wash-out block and two
lead-lag blocks.
 The washout block is proposed to eliminate the DC component
of a POD controller input signal and has a large time constant,
usually from 5 sec to 10 sec, since the oscillation is low
frequency (less than 2 Hz normally) to compensate the
difference between the oscillation input signal and DPFC
output variables.
 The lead-lag blocks provides phase shifting characteristic.

09/25/2020 JNTUA 51
Figure 23: Location of the POD controller in the DPFC

09/25/2020 JNTUA 52
Simulation Results
i. In this case analyzed two bus system, two busses are consider as a
generator buses.

Figure 26: single line diagram of two-bus system

ii. In simulation, the proposed that three phase fault is injected in transmission
line of proposed system in order to analyze the active power and reactive
power oscillations, bus voltages without and with DPFC-POD controller.

iii. In the simulation model for time t = 0.02 sec the DPFC is connected to the
source. Up to t = 0.02 sec the three phase source is supplying the power to
the load.

09/25/2020 JNTUA 53
(a) (b)
Figure 27: Active Power without and with DPFC-POD

 It is observed that above results during the fault, active powers is oscillates for

more time duration as shown in figure 27(a).

 By placing a DPFC these oscillations is reduced with in short duration as shown

in figure 27(b). These oscillations are settled from time t=0.02 sec onwards.
09/25/2020 JNTUA 54
Figure 28 : Reactive Power without and with DPFC-POD

 It is observed that above results during the fault, reactive powers is

oscillates for more time duration as shown in figure 28(a).

 By placing a DPFC these oscillations is reduced with in short

duration as shown in figure 28(b). These oscillations are settled


from time t=0.02 sec onwards.
09/25/2020 JNTUA 55
(a) (b)
Figure 29 : Bus voltages without and with DPFC-POD

 It is observed that the analyzed results during the fault, at the time of starting oscillations it

faces disturbance voltages at sending end and receiving end as shown in figure 29(a).

After placing DPFC with POD at the time of starting no disturbance in starting point of

oscillations at sending end and receiving end as shown in figure 29(b).

09/25/2020 JNTUA 56
Cont..
 Here observed that the magnitude of the voltages at sending
end and receiving end voltages are 507V and 516V without
DPFC, after placing a DPFC the voltage magnitudes are
increased to 660V and 680V respectively as shown in figure
29(a)&(b), therefore the system performance is improved in
transmission line.

09/25/2020 JNTUA 57
Module -III
MODELLING AND ANALYSIS OF GENERALIZED
UNIFIED POWER FLOW CONTROLLER & POWER
QUALITY IMPROVEMENT IN TRANSMISSION
SYSTEM

09/25/2020 JNTUA 58
Generalized Unified Power Flow Controller
GUPFC consists of two series and a single shunt converter, so that
GUPFC is treated as a three converter controller.
A common dc link is used to connect both the converters, the real
and reactive power is exchanged among the converters through
this link.
 GUPFC is used to monitor five power system parameters such as
real and reactive powers, bus voltages, current and impedance at
both ends and provides reactive power compensation.

09/25/2020 JNTUA 59
Figure 33 : Schematic diagram of GUPFC
09/25/2020 JNTUA 60
 The topics discussed in this module as

1. Mitigate the power quality problems by using GUPFC.


2. Reduced the low frequency oscillations by using POD controller.
 The above both objectives analyzed by providing a PID and POD
controllers.
 By providing a PID controller analyzed the power quality
problems like voltage sag, current swell and THD calculations.
In this proposed work is tested with two test cases.
1. Single machine connected to infinite bus system.

2. Standard test system of 30-bus system.


09/25/2020 JNTUA 61
Simulation Results

The GUPFC is tested in a single machine connected to infinite (SMIB) bus and 30-
bus system.

It is proposed that three phase fault is injected in transmission line of proposed
system in order to measures the voltage sag, current swell and THD values without
GUPFC and with GUPFC.
Case 1 : Single machine connected to infinite bus

Case 2 : standard 30-bus system

09/25/2020 JNTUA 62
Case 1 : SMIB

Figure 34: single line diagram of SMIB with GUPFC

1. Voltage Sag
 In the simulation model for time t = 0.07 sec the GUPFC is connected
to the source. Up to t = 0.07 sec the three phase source is supplying the
power to the load. After time of 0.07sec 3-ph fault is injected to system.

09/25/2020 JNTUA 63
Vvoltage (pu)
Vvoltage (pu)

(a) (b)
Figure 35: Three-Phase load voltage sag without and with GUPFC

 It is observed that above results during the fault the voltage levels are
decreased to 0.38 p.u during the time period 0.07 sec to 0.11 sec as
shown in above figure 35(a).
 By placing a GUPFC, the voltage sag is reduced effectively as shown

09/25/2020
in above figure 35(b).JNTUA 64
2. Current Swell
Current (pu)

Current (pu)
(a) Time (sec) (b)
Figure 36 : Three-Phase load current swell without and with GUPFC

 It is observed that above results during the fault the current levels are increased to 0.18 p.u
during the time period 0.07 sec to 0.11 sec as shown in above figure 36(a).
 By placing a GUPFC, the current swell is reduced effectively as shown in above figure 36(b).

09/25/2020 JNTUA 65
3. Total Harmonic Distortion
 Load voltage harmonic analysis without and with GUPFC
through FFT analysis is analyzed for test case 1.

Figure 37: Total harmonic distortion of load voltage without GUPFC

 From figure 37 it is observed that after placing GUPFC the


THD values is reduced from 11.83% to 0.30%.
09/25/2020 JNTUA 66
Table 7: Comparison of summary of test results for voltage sag , current swell
and THD with DPFC and GUPFC

Parameters Without device DPFC wit PID GUPFC with PID

Voltage sag 55% 10% 8%

Current swell 20 % 10 % 8%

THD 11.83 % 0.51 % 0.30 %

09/25/2020 JNTUA 67
Case 2 : 30 -bus system

Figure 38 : 30 bus standard bus system

09/25/2020 JNTUA 68
Figure 39 : 30 bus standard bus system with GUPFC

09/25/2020 JNTUA 69
1. Voltage Sag
 In the simulation model for time t = 0.07 sec the GUPFC is connected to
the source. Up to t = 0.07 sec the three phase source is supplying the
power to the load. After time of 0.07sec 3-ph fault is injected to system.

09/25/2020 JNTUA 70
Vvoltage (pu)

Vvoltage (pu)
(a) (b)
Figure 40: Three-Phase load voltage sag without and with GUPFC

 It is observed that above results during the fault the voltage levels are decreased to
0.42 p.u during the time period 0.07 sec to 0.11 sec as shown in above figure 40(a).
 By placing a GUPFC, the voltage sag is reduced effectively as shown in above
figure 40(b).

09/25/2020 JNTUA 71
2. Current Swell
Current (pu)

Current (pu)
(a) Time (sec) (b)
Figure 41: Three-Phase load current swell without and with GUPFC

 It is observed that above results during the fault current swell about 0.18 p.u during the
time period 0.07 sec to 0.11 sec as shown in above figure 41(a).
 By placing a GUPFC, the current swell is decreased as shown in above figure 41(b).
09/25/2020 JNTUA 72
3.Total Harmonic Distortion
 It is observed that the load voltage harmonic analysis without and with
GUPFC by placing a DPFC the THD will be reduced from 11.83% to
0.22%.

Figure 42 : Total harmonic distortion of load voltage without and with GUPFC
09/25/2020 JNTUA 73
Table:8 power flow analysis for SMIB with PID Controller
S. no Bus from Bus to Active power with out Power Flows with GUPFC
GUPFC( SMIB) (SMIB)

P (MW) Q (MVAr) P (MW) Q (MVAr)

1 1 2 96 -120 132.0 -123.0

Table:9 power flow analysis for GUPFC with PID Controller

S. no Bus from Bus to Power Flows without Power Flows with GUPFC
GUPFC (30-bus) (30-bus)

P (MW) Q (MVAr) P (MW) Q (MVAr)

1 1 2 29.50 39.99 -35.65 -57.84

09/25/2020 JNTUA 74
2 1 3 0.00098 -0.000158 0.001983 -0.00098

3 2 4 9.70 -89.21 16.5 -160.5

4 3 4 9.70 -89.21 16.5 -160.5

5 4 6 9.70 -89.21 16.5 -160.5

6 5 7 1021 -969.20 1560 -1499

7 6 7 398 -1024 571 -1366

8 6 8 0.00089 -0.000102 0.002083 -0.000397

9 8 28 1060 -1024 1567 -1513

10 9 10 1.96 -35.2 3.71 -71.44

11 9 11 1.96 -35.2 3.71 -71.44

12 11 9 1.96 -35.2 3.71 -71.44

13 12 13 292.2 -201.3 399.7 -373.4

14 12 14 89.21 -289.34 139.2 -389

15 14 15 1.96 -45.7 3.71 -89.02

16 15 18 1.96 -45.7 3.71 -71.44

09/25/2020 JNTUA 75
17 16 17 1.96 -45.7 3.71 -71.44

18 17 10 1.96 -45.7 3.71 -71.44

19 18 19 1.96 -45.7 3.71 -71.44

20 19 20 1.96 -45.7 3.71 -71.44

21 20 10 1.96 -45.7 3.71 -71.44

22 21 22 201.2 -201.3 399.7 -373.4

23 22 10 89.21 -289.34 139.2 -389

24 22 24 159.3 -520.7 310.4 -637.9

25 24 25 201.5 -863.6 397.8 -493.9

26 25 26 840.5 -920.3 1175 -1120

27 27 25 0.00104 -0.00024 0.001963 -0.000329

28 27 28 0.0040 -0.000254 0.00126 -0.00105

29 28 8 909.1 -1005 1210.8 -1206.66

30 29 30 0.00156 -0.00025 0.004052 -0.000859

31 30 27 0.00089 -0.00035 0.00198 -0.003297

09/25/2020 JNTUA 76
a. GUPFC-POD controller eliminated the low frequency
oscillations by controlling the real and reactive power flow in
the transmission line. Hence it offers better performance
characteristics.

b. In simulation, the proposed that three phase fault is injected


in transmission line of proposed system in order to analyze
the active power and reactive power oscillations , bus
voltages without and with GUPFC-POD controller.

09/25/2020 JNTUA 77
c. In this case, here analyzing two bus system, two buses are consider as a
generator buses.

Figure 43: single line diagram of two-bus system

d. In the simulation model for time t = 0.02 sec the GUPFC-POD is


connected to the source. Up to t = 0.02 sec the three phase source is
supplying the power to the load. After t=0.02sec 3-ph fault is
injected to system.

09/25/2020 JNTUA 78
(a)

(b)
Figure 44: Active power without and with GUPFC-POD
09/25/2020 JNTUA 79
 It is observed that above results during the fault, active powers

is oscillates for more time duration as shown in above figure


44(a).

 By placing a GUPFC-POD these oscillations is settled faster

and provided superior damping as shown in above figure


44(b).

09/25/2020 JNTUA 80
Figure 45: Reactive power without and with GUPFC-POD
09/25/2020 JNTUA 81
 It is observed that above results during the fault, active powers

is oscillates for more time duration as shown in above figure


45(a).

 By placing a GUPFC-POD these oscillations is settled faster

and provided superior damping as shown in above figure


45(b).

09/25/2020 JNTUA 82
Conclusions
My research work concluded as :

DPFC is used to control the Power Quality Problems in

Transmission system. When 3-phase fault is injected in


transmission line to measure the voltage sag, current swell and
THD are analyzed by placing of DPFC with PID controller
and without DPFC in transmission line. It is observed that
voltage sag is reduced from 55% to 10% for the proposed 2-bus
system without and with DPFC device connected. Similarly
current swell and THD reduced to 10 % and 0.51 %
respectively.
09/25/2020 JNTUA 83
 It is observed that voltage is increased by 0.2 pu by placing the
DPFC during the failure of series converter. The transmission
system voltage is maintained under standard values even
though during the failure of series converter.
 Power Oscillations Damping Controller is used to damp-out
the low frequency oscillations in active power, reactive power
and voltage for test system with DPFC-POD.

09/25/2020 JNTUA 84
 GUPFC is used to control the Power Quality Problems in Transmission
system. It is proposed that three phase fault is injected in transmission line
of proposed system in order to measures voltage sag, current swell and
THD values without GUPFC and with GUPFC. It is observed that voltage
sag is reduced from 55% to 8 % for the proposed system without and with
GUPFC device connected. Similarly current swell and THD reduced to 8 %
0.30 % respectively.
 It is observed that during fault active power and reactive power oscillations
settled it takes more time. By placing a GUPFC-POD these oscillations are
reduced fastly.

09/25/2020 JNTUA 85
Future Scope
In future, this work can be extended easily by implementing

advanced methods like Hybrid Power Flow Controller (HPFC)


and Optimal Unified Power Flow Controller (OUPFC) in
transmission system.
Based on the study carried out, a basic platform is available to

investigate various issues in the future, few of techniques are


used to improve the performance of the system, which are given
below.
09/25/2020 JNTUA 86
Cont..
 Various optimization techniques like ANN, Sliding Mode Controller
(SMC) and grey-wolf optimization can be adopted for the optimal
location and optimal setting of FACTS devices for power quality
improvement and their effectiveness can be compared.
 Multi-bus system with multiple FACTS controllers may be studied
to observe the power quality improvement.
 This work has covered power quality in 30-bus system using DPFC
and GUPFC. The work may be extended to higher bus system.

09/25/2020 JNTUA 87
References
[1] N. G. Hingorani and L. Gyugyi “Understanding FACTS: Concepts and Technology of Flexible AC
Transmission Systems”, New York: IEEE Press, 2000.
[2] Y.H. Song and A.T. John “Flexible AC Transmission Systems (FACTS)”, Book, IEE Power and
Energy Series, 2000, pp: 143-157.
[3] R.M. Mathur and R.K. Varma “Thyristor-Based FACTS Controllers for Electrical Transmission
Systems”, Book, Wiley Publications, 2000, pp: 123-154.
[4] Dusan Povh “Use of HVDC and FACTS”, The IEEE, Vol.88, No.2, February 2000.
[5]M. Fotuhi Firuzabad, Roy Billinton and Sherif Omar Faried “Sub transmission system reliability
enhancement using a thyristor controlled series capacitor”, IEEE Trans. Power Delivery, Vol. 15, Jan.
2000, pp: 443-449.
[6]E. Acha “FACTS Modelling and Simulation in Power Networks”, Book, Wiley Publications, 2001, pp:
13-54.
[7]Fan Li, Baohua Li and Xujun Zheng “Coordination of Power Flow Control in Large Power system”,
IEEE Power and Energy Society, Vol. 16, No. 4, 2001, pp: 776-781.
[8]Issarachai Ngamroo “A Stabilization of Frequency Oscillations in an Interconnected Power System
Using Static Synchronous Series Compensator”, Int. Journal of Science and Technology, Vol. 6, No. 1,
2001, pp: 52-59.
[9] G. M. Huang and Y. Li “Impact of Thyristor Controlled Series Capacitor (TCSC) on bulk power system
reliability”, In: Power Engineering Society Summer Meeting, IEEE, 2002.

09/25/2020 JNTUA 88
[10] D. Shen and P. W. Lehn “Modeling, analysis and control of a current source inverter based STATCOM”, IEEE
Trans. on Power Delivery, Vol. 17, No.1, 2002, pp: 248-253.
[11] A. D. Del Rosso, C. A. Canizares, and V. M. Dona “A Study of TCSC Controller Design for Power System
Stability Improvement”, IEEE Trans. on Power system, September 2002, pp: 1110-1123
[12] R. M. Mathur and R. K. Varma “Thyristor-Based FACTS Controllers for Electrical Transmission Systems”,
IEEE Power Engineering Review, Vol. 22, No. 11, Nov. 2002, pp: 11-15.
[13] John J. Paserba “How FACTS Controllers Benefit AC Transmission Systems”, Mitsubishi Electric Power
Products, Inc.,Warrendale, Pennsylvania, USA-2002.
[14] X.P. Zhang “Modelling of the Interline power flow controller and the generalised unified power flow controller
in Newton power flow”, IEE Pro. Gener. Trans Distribution, Vol.150, Issue No. 3, May 2003, pp: 268-274.
[15] Chintan R Patel, Sanjay N Patel and Dr. Axay J Mehta ”Static Synchronous Series Compensator (SSSC): An
approach for reactive power compensation for the transmission system”, In National Conference on Recent Trends
in Engineering & Technology-2003.
[16] N. Mohan, T. M. Undeland, and W. P. Robbins “Power electronics: converters, applications, and design”, John
Wiley & Sons, 2003.
[17] Lin Sun, Shengwei Mei, Qiang Lu and Jin Ma “ Application of GUPFC in China’s Sichuan Power Grid
Modelling, Control Strategy and Case Study” IEEE Power Engineering Society General Meeting-2003, pp:175-
181.
[18] H. B. Puttgen, P. R. Mac Gregor and F. C. Lambert “Distributed generation: Semantic hype or the dawn of a new
era”, Power and Energy Magazine, IEEE, 2003.
[19] Xiao Ping Zhang “Advanced Modelling of the Multi-control Functional Static Synchronous Series Compensator
(SSSC) in Newton Power Flow”, IEEE Trans. on Power system, Vol. 18, No. 4, 2003, pp: 1410-1416.

09/25/2020 JNTUA 89
[20] L. Gyugyi “Unified power flow control concept for flexible AC transmission systems generation”, IEE Proc. of
Generation, Transmission and Distribution, Vol. 139, No. 4, 2003, PP: 323-331.
[21] P. Kumkratug and M. H. Haque “Improvement of Stability Region and Damping of a Power System by using
SSSC”, Proceedings of IEEE Power Engineering Society General Meeting, 13-17 July 2003, Vol.3, No. 2, pp:
1417-1421.
[22] T.Tambey and M.L Kothari “Unified Power Flow Controller (UPFC) based DampingControllers for Damping
Low Frequency Oscillation in a Power System”, SEE Proc. Generation, Transmission and Distribution, Vol. 150,
No. 2, March 2003, pp:129-140.
[23] P.K. Dash, S. Mishra “Damping of multimodel Power System Oscillation by FACTS devices using nonlinear
Takagi – sugeno fuzzy controller”, Int. Journal of Electrical Power and Energy Systems, Vol. 25, No. 6, 2003, pp:
481-490.
[24] Y. Qingguang, L. Pei, L.Wenhua, and X. Xiaorong “Overview of STATCOM technologies”, In Electric Utility
Deregulation,Restructuring and Power Technologies, IEEE Conference on, 2004.
[25] A. K. Verma, A. Srividya, and B. l. C. Deka “Impact of a FACTS controller on reliability of composite power
generation and transmission system”, Electric Power system Research, 2004.
[26] P. Bresesti, M. Sforna, V. Allegranza, D. Canever, and R. Vailati “Application of phase shifting transformers for
a secure and efficient operation of the interconnection corridors”, In: Power Engineering Society General
Meeting,IEEE, 2004.
[27] S. Kannan, S. Jayaram, and M. M. A. Salama “Real and reactive power co-ordination for a unified power flow
controller”, Power system, IEEE Transactions on, 2004.
[28] X. Zhang, C. Xue and K. R. Godfrey “Modeling of the static Synchronous Series Compensator (SSSC) in three-
phase Newton power flow”, IEEE Proc. on GenerationTransmission and Distribution, Vol. 15, No. 4, 2004, PP:
486-494.
[29] Fang Z. Peng and Jim Wang “A Universal STATCOM with Delta-Connected Cascaded Multilevel Inverter”,
34th Annual IEEE Power Electronics Special Conference, Vol. 5, PESC No. 4, 2004, pp: 3529-3533.

09/25/2020 JNTUA 90
[30] Lijun Cai and Istvan Erlich “Coordination Between Transient and Damping Controller for Series Facts
Devices Using ANFIS Technology”, Vol. 20, No. 2, 2004, pp: 1-7.
[31] D. Divan and H. Johal “Distributed facts-A new concept for realizing grid power flow Control” Proc.
IEEE 36th Power Electron. Spec. Conf. (PESC), 2005, pp: 8–14.
[32] Bikash Pal and B. Chaudhuri “Robust Control in Power system” Power Electronics, Power system,
Engineering and Energy Technology (Press), Springer Science, 28-July-2005.
[33] K. R. Padiyar and Nagesh Prabhu “A Comparative study of SSR Characteristics of TCSC and SSSC”, 15th
PSCC Liege, Indian Institute of Science, Bangalore, India, Aug. 2005, pp: 1-7.
[34] Visakhan and Rahul “Analysis of power oscillation damping capability of STATCOM- POD and optimal
placement of PMUs in IEEE-14 bus system” 2005 IEEE International Conference on Power, Instrumentation,
Control and Computing (PICC).
[35] Lijun Cai and Istvan Erlich “Simultaneous coordinated tuning of PSS and FACTS damping controllers in
large power system”, IEEE Trans. on Power and Energy Society, Vol. 20, No. 1, 2005, pp: 294-300.
[36] D. Divan, E. B.William, S. S. Robert, K. Bill, W. G. Randal, T. B. Dale, R. I. Michael, and S. G. Ian “A
distributed static series compensator system (DSSC) for realizing active power flow control on existing power
lines”, Power Delivery,IEEE Transactions on, 2007.
[37] W.Song, Alex Q. Huang and Subhashish Bhattacharya “Distributed Power Flow Controller Design
Based-on ETO-Light Converter”, IEEE-2008, pp: 1893-1897.
[38] N. Magaji and Mohd Wazir bin Mustafa “Applications of SVC Device for Damping Oscillation Based on
Eigenvalue Techniques”, Int. Journal of Power, Energy and Artificial Intelligence Vol. 1, No. 1, 2008, pp: 42-
49.
[39] Awadallah M. A and H. M. Soliman “An Adaptive power system stabilizer based on fuzzy and swarm
intelligence”, Int. Journal of Modelling, Identification and control,Inderscience Publications, Vol. 5, No. 1,
2008, pp: 55-65.
09/25/2020 JNTUA 91
[40] J. Hao, Li-Bao Shi, Yi-Xin Ni and C. Chen “Improvement of Transient Stability by Unified Power Flow
Controllers based on Hamiltonian System Theory”, European Trans. on Electrical Power, Vol. 18, No. 6, 2008, pp:
617-635.
[41] N.Senthil Kumar, R.Srinivasan and M.Abdullah Khan “Damping Improvement by Facts Devices: A Comparison
between STATCOM, SSSC and UPFC”, Int. Journal of Electrical and Power Engineering, Vol. 2, No. 3, 2008, pp:
171-178.
[42] Amany El-Zonkoly “Optimal Sizing of SSSC Controllers to Minimize Transmission Loss and a Novel Model of
SSSC to Study Transient Response”, Electric Power system Research, Vol. 78, No. 11, Nov. 2008, pp: 1856–1864.
[43] Zhihui Yuan, Sjoerd W.H. de Haan and Braham Ferreira “Utilizing Distributed Power Flow Controller (DPFC)
for Power Oscillation Damping”, IEEE power & Energy society general meeting, DOI:10.1109, july-2009,pp:1-5.
[44] Wenchao Song, Xiaohu Zhou, Zhigang Liang , Subhashish Bhattacharya and Alex Q. Huang “Modeling and
Control Design of Distributed Power Flow Controller based-on Perphase control”, IEEE Energy Conversion
Congress and Exposition-2009,pp:3262-3267.
[45] Zhihui Yuan, Sjoerd W.H. de Haan and Braham Ferreira “DPFC Control during Shunt Converter Failure”,IEEE
Energy Conversion Congress and Exposition-2009, pp: 2727-2732.
[46] C.C.Davidson and G.de Preville “The future of high power electronics in Transmission and Distribution power
system”, In:Power Electronics and Applications, European Conference on, 2009.
[47] H. Taheri, S. Shahabi, Sh. Taheri and A. Gholami “Application of Synchronous Static Series Compensator (SSSC)
on Enhancement of Voltage Stability and Power Oscillation Damping”, IEEE- Conference Publications, EUROCON
'09, 2009,pp: 533-539.
[48] D.Van Hertem, R. Eriksson, L. Söder and M. Ghandhari “Co-ordination of multiple power flow controlling
devices in transmission systems”, 9th  IET International conference on AC and DC power Transmission
(ACDC2017),2010,pp:1-6.
[49] B. Fardanesh and B. Shperling “Multi-Converter FACTS Devices: The Generalized Unified Power Flow
Controller (GUPFC)” , IEEE -2010,pp:1020-1024.

09/25/2020 JNTUA 92
[50] Zhihui Yuan, Sjoerd W. H. de Haan, Jan Braham Ferreira and Dalibor Cvoric “A FACTS Device: Distributed
Power-Flow Controller (DPFC)”, IEEE Transactions on Power Electronics, DOI: 10.1109/TPEL.2010.2050494 ,vol.
25,issue.10, october- 2010,pp: 2564 – 2572.
[51] Z. Yuan, S.W.H. de Haan, and J.A. Ferreira “Control Scheme to Improve DPFC Performance during Series
Converter Failures”, IEEE, DOI: 978-1-4244-6551-4, october- 2010,pp:1-6.
[52] A.Lashkar Ara, A.Kazemi, and S.A.Nabavi Niaki, "Multiobjective Optimal Location of FACTS Shunt-Series
Controllers for Power System Operation Planning", IEEE Transactions on Power Delivery, Vol.27, No.2,2010, pp:
481-490.
[53] Vibhor Gupya “Study and Effects of UPFC and its Control system for Power Flow Control and Voltage Injection in
a Power System”, Int. Journal of Engineering Science and Technology, Vol. 2, No.7, 2010, pp: 2558-2566.
[54] S. Muthukrishnan and A. Nirmal Kumar “ Enhancement of Power Quality in 14-Bus System using UPFC”,
Research Journal of Applied Sciences, Engineering and Technology, Vol. 2, No. 4 , 2010, pp: 356-361.
[55] Sidhartha Panda “Modeling, simulation and optimal tuning of SSSC-based controller in a multi-machine power
system”, World Journal of Modeling and Simulation, Vol. 6, No. 2, 2010, pp: 110-121.
[56] S. V. Chandarakar , J. B. Helonde, R. M. Mohril, and V. K. Chandrakar “Fuzzy Based SVC with coordinated POD
for Damping of Oscillations of Power System”, WSEAS Tran. on Power system, Vol. 5, No. 3, 2010, pp: 253-262.
[57] E.L. Miotto and M.R. Covacic “Analysis of Impacts of PSS Controller and TCSC FACTS Devices at Dynamic
Stability of a Multimachine System Power”, IEEE/PES Transmission and Distribution Conference and Exposition,
Latin America, Nov. 2010, pp: 359 – 365.
[58] Rakhmad Syafutra Lubis “Modeling and Simulation of Generalized Unified Power Flow Controller (GUPFC)”,
International Conference on Instrumentation, Communication Information Technology and Biomedical Engineering,
Bandung, Indonesia,nov- 2011.
[59] Rakhmad Syafutra Lubis “Digital Simulation of the Generalized Unified Power Flow Controller System with 60-
Pulse GTO-Based Voltage Source Converter”,International Journal of Energy Engineering, DOI:
10.5923/20120203.06, march- 2012, pp: 91-99.

09/25/2020 JNTUA 93
[60] Abu.Siada and Chatura Karunar ”Improvement of Transmission Line Power Transfer Capability, Case Study” Electrical
and Electronics Engineering: An International Journal (EEEIJ) Vol.1, No.1, May 2012..
[61] Ahmad Jamshidi, S.Masoud Barakati and M.Moradi Ghahderijani “Power Quality Improvement and Mitigation Case
Study using Distributed Power Flow Controller”, IEEE   International Symposium on Indurstial Electronics,
DOI:101.1109,may-2012, pp:464-468.
[62] M. Martins and Fernando A. Silva “Control of Distributed Power Flow Controllers using active power from homo-polar
line currents”, IEEE-2012,pp:806- 813.
[63] Amin Safari, Behrouz Soulat and Ali Ajami “Modeling and unified tuning of distributed power flow controller for
damping of power system oscillations“, Ain Shams Engineering Journal, april-2013,pp:775–782.
[64] Natalia Rosa M.Santos, V.Fernao Pires and R.M.Castro “Modelling of the Generalized Unified Power Flow Controller to
Integrate in power flow studies”, 4th International Conference on Power Engineering, Energy and Electrical Drives, Istanbul,
Turkey, May-2013,pp:635-640.
[65] A.N. Hussain, F. Malek, M.A. Rashid and M.F. Haji Abd Malek “Performance Improvement of Power System Stability by
Using Multiple Damping Controller Based on PSS and the UPFC”, Int. Journal of Engineering and Technology, Vol. 5, No. 4,
2013, pp: 3257-3268.
[66] N. Karuppiah,V. Malathi and G. Selvalakshmi“Transient Stability Enhancement fuzzy Controlled SVC and STATCOM”,
Int. Journal of Innovative Research in Science, Engineering and Technology, Vol. 3, No. 2, 2014, pp: 397-404.
[67] M.Abdul Khader Aziz Biabani, Syed Mahamood Ali and Akram Jawed “Enhancement of Power quality in distributed
system using D-Statcom”, International Conference on Signal Processing, Communication,Power and Embedded System
(SCOPES),2016,pp: 648 – 652.
[68] Mircea Eremia,Chen-Ching Liu and Abdel-Aty Edris “Static var compensator(SVC)”, Advanced solutions in power
system:HVDC,FACTS and Artificial Intelligence, Wiley-IEEE press eBook chapters -2016.
[69] Bhushan D.Deotale and Sudhir R.Paraskar “Transient stability improvement using Thyristor Switched Series Capacitor
(TSSC) FACTS devices” IEEE conference on Electrical,Electronics and Computer science (SCEECS-2016),pp:1-6.
[70] J.Amritham and V.Uma “Optimal Location of Unified Power Flow Controller Enhancing System Security” 2016 Second
International Conference On Science Technology Engineering and Management (ICONSTEM), pp: 326-331.
[71] Uday Kishan and Chengzong Pang “Smooth Shunt Control of a Fuzzy based Distributed Power Flow Controller to
Improve Power Quality” DOI: 978-1-5090-6132-7/16, 2016 IEEE.
[72] K.R. Padiyar “FACTS Controllers in Power Transmission and Distribution” new age international publishers.

09/25/2020 JNTUA 94
Published papers in support of work
 
International/National Journals
1. RajaReddy. Duvvuru, B.VenkataPrasanth, V.Ganesh “A Novel Approach for Improvement
of Power Quality in Transmission System by Using Distributed Power- Flow Controller”
International Journal of Engineering Research in Electrical and Electronic Engineering
(IJEREEE) Vol 3, Issue 3, March 2016.
2. RajaReddy. Duvvuru, B.VenkataPrasanth,V.Ganesh “A Novel Approach for Reducing the
Power Oscillations in Transmission System by using Distributed Power Flow
Controller(DPFC)”IJCTA,9(14) 2016, International Science Press,pp:6721-6730.
(Scopus)
3. 5. RajaReddy.Duvvuru, B.VenkataPrasanth, V.Ganesh “Performance of Generalized
Unified Power Flow Controller (GUPFC) in Transmission System” accepted for
International Journal of Renewable Energy Technology, INDERSCINCE publications
waiting for publishing. (Scopus)

09/25/2020 JNTUA 95
International Conference
 RajaReddy.Duvvuru, B.VenkataPrasanth, V.Ganesh “Improvement of the
Distributed Power Flow Controller (DPFC) performance in Transmission Lines
during failure of Series Converter” Special issue in ELSEVIER Energy
Procedia to be Published, Science Direct on September -2016. (Scopus)

09/25/2020 JNTUA 96
Related Journals
1. RajaReddy.Duvvuru, B.VenkataPrasanth, V.Ganesh “Modeling and Analysis of
Distributed Power Flow Controller Damping of Power System Oscillations in
Transmission System” Journal on Circuits and Systems Engineering, i-manager’s
publications, vol.5,no.1,December-16 to February-17,pp: 30-35. (Scopus)
2. RajaReddy.Duvvuru, B.VenkataPrasanth, V.Ganesh “Modelling of the
Generalized Unified Power Flow Controller (GUPFC) with 48-Pulse Gate Turn-
off Based Voltage Source Converter” accepted in Lecturer notes in Electrical
Engineering, SPRINGER SERIES to be Published on october -2017. (Scopus)
3. RajaReddy. Duvvuru, B. VenkataPrasanth, V. Ganesh, “Active and Reactive
Power Control of Distributed Power-Flow Controller (DPFC) with Fuzzy
Logic Controllers” Submitted to Taylor & Francis, Under review process-
Submitted on July-2018.(SCI)

09/25/2020 JNTUA 97
CORRECTIONS ARE MADE AS PER THE RECOMMENDATIONS OF
THE EXTERNAL EXAMINER –1
S.No Review Comments and Queries Old Answers/Clarifications New
report report
page page
no. no.
1. The literature survey needs to be 9-15 The referred papers have been studied & 9-18
exhaustive. The chapter 2 extended the information in Literature
presents briefly. Survey.
2. The equation 3.1 in page 17 is to 17 The equation 3.1 is corrected in page 20
be corrected. no.20, and modified thesis as

3. Page 19, figure 3.3: add source 19 This information is adopted from text 22
information or reference informat book “FACTS Controllers in Power 
ion from where it has been Transmission and Distribution” by K.R.
adopted. Padiyar, New age International Publishers as
kept in reference [72].

09/25/2020 JNTUA 98
4. Page 22, section 3.4.2, 4th line: 22 Typographical mistake has been corrected 25
“theta­_se” symbol missing. and the symbol is inserted in page 25,
section 3.4.2, and 4th line.
5. Page 28, equation 3.25: explain 28 Explanation added on “why mutual 31
why mutual impedance is ignored impedance is ignored for the transmission
for the transmission line? line?” in page no.31 last Paragraph.
6. Figures 3.9, 3.18, 4.6 are not 28, As per the suggestion of the examiner the 31, 39
clear. Please re-draw. 36 figures of 3.9, 3.18 and 4.6 have been and 51
and redrawn clearly.
46
7. Modeling of GUPFC is not 36-37 More explanation has clearly given with 39-42
clearly explained. Needs more necessary information related to modeling of
explanations. GUPFC in page no’s 39 to 42.
8. Page 51: there is no information 51 This information is added in page no. 56 of 56
has been provided in the thesis first Para about how the voltage sag is
about how the voltage sag has created and location of the fault is drawn in
been created? In addition, at what fig 4.11.
location the disturbance has been
created on the system shown in
Fig.4.11.

09/25/2020 JNTUA 99
9. With reference to Figures 4.12 52 The results are updated in Figure 4.13 (a) & 57
and 4.13, why the current before (b) as per the question in page no. 57.
current swell is not maintained
with and without DPFC-PID?
10. Page 52, the last paragraph 52 The detailed explanation is included 57
concluding that by placing DPFC, regarding mitigation of current swell in page
the current swell has been no.57.
effectively mitigated. But there is
no information on what basis this
conclusion has been made?
11. Page 54, for 30-system, how the 54 The detailed explanation regarding placing 59
buses 8 and 28 are chosen as best of DPFC for buses 8 and 28 are the best
location? What is the criterion locations for 30 bus systems is explained in
chosen for best location? case : 2 of page no. 59.
12. For the case of DPFC-PID, how 49 The PID parameters have been chosen based 54
the PID controller parameters on the Zeigler- Nichols method. The detailed
have been chosen? explanation is given in page no. 54.
13. Figure 4.19: without and with 57 The results are updated in Figure 4.19 as per 62
DPFC-PID, why the current the question in page no. 62.
values are not matching during
normal operation (before current
swell)?.

09/25/2020 JNTUA 100


14. Table 4.2, sl.no.2, why the power 59 For 30-bus system network, the impedance 64
flow from bus-1 to bus-3 is very of the line between bus1 & bus3 is high.
less. Hence power flow between bus1 and bus3
are less.
15. Table 4.2, there is no flow 59 The detailed flow information is added in 64
information between the buses 2 table 4.2 in page no.64 regarding power flow
and 4. between bus 2 and 4.
16. In table 4.2 and In table 6.2, why 59 & The information regarding power flow from 64 &
there is a lot of difference between 88 bus 25 to 26 and 26 to 25 is to be same. 93
flow the buses 25 to 26 is Here bus 26 to 25 was typed mistake instead
different from buses 26 to 25. of bus 27 to 25. This has been rectified in
Looks to be the power flow table 4.2 and 6.2.
results are not correct.
17. Figure 4.24, why the two buses 1 61 The results were correct, but different colors 66
and 2 are not having the same were selected to show results and missed the
phase sequence voltages? One is uniformity. It is corrected and redrawn in
RGB and another one is RBG. figure no.4.24 in page no. 66.
Looks to be wrong results.
18. Figure 4.26 caption mentions bus- 62 If the network is 2-bus system, figure 4.26 67
3. However, the system does not results considered as voltage and current at
have a 3rd bus. receiving end side, it is typographical
mistake and it is rectified and is shown in
page no. 67.

09/25/2020 JNTUA 101


19. Figure 5.10: why the phase 73 The results were correct, but different 78
sequence the sending end and the colours were selected to show results and
receiving end voltages are not the missed the uniformity. It is corrected and
same? With the addition of DPFC- redrawn in figure no.5.10 in page no. 78.
POD, why the phase sequence is
changing?.
20 Observations based on the Figure 73 The detailed explanation has been added 78 &
5.10 does not carry any novelty. about figure no. 5.10 in last Para page no. 78 79
& 79.
21. Figure 6.7: without and with 81 The results are updated in Figure 6.7 as per 86
GUPFC-PID, why the current the question in page no. 86.
values are not matching during
normal operation (before current
swell)?.
22. Figure 6.13: without and with 86 The results are updated in Figure 6.13 as per 91
GUPFC-PID, why the current the question in page no. 91.
values are not matching during
normal operation (before current
swell)?.

23. Figure 6.17,the y-axis values are 90 The Y axis is renamed as in MW in fig 6.17 95
in MW, not W.

09/25/2020 JNTUA 102


24. Figure 6.18,the y-axis values are 91 The Y axis is renamed as in MVAr in fig 96
in MVAr, not VAr. 6.18

25. Page 94, the scope for future 94 The scope of future work is rewritten and 99 &
work is very brief. presented in page.no.99 & 100. 100

26. The format for reference [71] 102 The reference no.71 is corrected and 108
needs to be uniform. maintained uniformly.

27 In appendix A and B, why the 103 Typographical mistake has been corrected in 109 &
transmission line parameters are & appendix A and B transmission line 110
mentioned in p.u/km?. 104 parameters are mentioned in Ohm/Km,
Henry/Km and Farad/Km (R,L and C) in
page no. 109 & 110.

09/25/2020 JNTUA 103


THANK YOU

09/25/2020 JNTUA 104

You might also like