PowerLogic

ION7550/ION7650
Energy and power quality meters
Purpose

● Improve power quality measurements and enhance functionality.


(Certified ION7650 according to the IEC 61000-4-30 Class A)
● Anti-Aliasing
● Flicker
● Trending & Forecasting
● Disturbance direction detection
● Alarm Setpoint Learning
● Support new Ethernet Card for faster connections
● 100BASE-T/100BASE-FX
● SNMP traps
● Multilingual HMI

Schneider Electric - Division - Name – Date 2


Markets. Supply Side. Cont…

● Reasons to buy
● Multipoint, multi-protocol communications
● PQ compliance monitoring
● Transient detection
● Waveform recording sampling rate
● High accuracy revenue metering
● ITC (Instrument Transformer Compensation). Eliminates need to replace
Instrument transformers where accuracy is required
● Transformer losses compensation when the meter is in a different location
than the billing point.

Schneider Electric - Division - Name – Date 5


Positioning

● Customers with Medium and Large Energy Consumption


● Reduce energy costs
● Making energy a variable cost

● Customers with Process Sensitive to PQ or Power Reliability


● Improve reliability
● Improve PQ

● The ION75/7650 together with the ION-E software provides a powerful


tool that offers many other features to the above customers.

Schneider Electric - Division - Name – Date 6


IEC 61000-4-7 (2002) :Aliasing
What is Aliasing?
● Aliasing is an effect that causes different continuous signals to become
indistinguishable (or aliases of one another) when sampled. When this
happens, the original signal cannot be uniquely reconstructed from the
sampled signal.

● Aliasing is a major concern in power quality analysis because improper


sampling of the analog signal will cause high-frequency components to be
aliased with genuine low-frequency ones, and be incorrectly reconstructed.

Schneider Electric - Division - Name – Date 9


Aliasing Effect
Wagon Wheel Example

● Optical illusion that occurs in older


movies when wagon wheels appear to
be turning backwards.
● Caused by slower frame speed of
camera relative to the high speed of the
wagon wheels.

Schneider Electric - Division - Name – Date 10


What Causes Aliasing?
● Aliasing (or folding) occurs when a signal is sampled at a rate that is insufficient to capture
the changes in the signal.
● Sampling at a lower rates results not only in missing data, but also incorrect re-creation of
the waveform, leading to faulty analysis.

Sampled Source
Sampling Point
Re-created Signal

Sampled Source Re-created Signal

Schneider Electric - Division - Name – Date 11


Aliasing Effect Example
Sampled Source 100 Actual
90
80

Amplitude (%)
70
60
50
40
30
20
10
0
1 3 5 7 9 11
Harmonic Component

Re-created Signal Reported


100
90
80

Amplitude (%)
70
60
50
40
30
20
10
0
1 3 5 7 9 11
Harmonic Component

Sampled Source Re-created Signal


Schneider Electric - Division - Name – Date 12
How do you avoid Aliasing?
● The Nyquist Sampling Theorem states that in order to avoid aliasing, the
sample rate should be at least twice the highest frequency contained in the
sample

Sampled Source
Sampling Point
Re-created Signal

Sampled Source Re-created Signal

Schneider Electric - Division - Name – Date 13


Sampling Rate

● Sample rates are important in adequately representing the original


signal.
● Oversampling the original signal:
● Increases the meter’s bandwidth
● Reduces metering error
● Provides a closer approximation to the original signal

PQA 2004
Schneider Electric - Division - Name – Date 14
What is new with firmware 350?

● Trending and forecasting

● Disturbance direction detection

● Setpoint learning

● Gateway Functionality with Modbus TCP protocol

● Simple Network Management protocol (SNMP)

● 100 Base TX/FX

Schneider Electric - Division - Name – Date 16


Trending and forecasting

● Trends and Forecast up to 10 different user configurable


channels
● Hourly – Displays last 24 hrs plus current.
● Daily– Displays last 30-31 days plus current.
.

● Viewable through ION75/7650 Web-pages by using Ethernet


port and IE

Schneider Electric - Division - Name – Date 17


Schneider Electric - Division - Name – Date 18
Disturbance direction detection
Confidence Scores
● Requires a trigger (Sag, Swell or a
Transient) to run the algorithm

● Then the ION 75/7650 determines the


direction of a disturbance

● Provides a confidence score and the


direction of the disturbance. All recorded in
the Event Log.

● While the algorithm for a transient is


running, any further pulses are ignored.

Schneider Electric - Division - Name – Date 19


Alarm Setpoint Learning
● Setpoint Module (65).- Monitors a source with respect to an
absolute threshold and it can evaluate either an over or an under
condition

● Sag/Swell Module (1).- The Sag/Swell Module learns two values:


a sag limit and a swell limit

● Disturbance Analyzer (6).- Learns an over-alarm If the pickup


value is greater than 100% of the nominal value at the moment
when learning period is initiated; also, an under-alarm will be
learned if the pickup values is less than 100% of the nominal
value.

● And Transient Module (6).- Evaluates when transients occur in


the system.

● All four modules Include the following characteristics:


● Learn now input
● Learn install mode
● Learn duration

Schneider Electric - Division - Name – Date 20


Gateway Functionality with Modbus TCP
protocol

● Provides gateway functionality when the Ethernet port and/or modem options
are present
● Modbus Master allows front panel display of real-time parameters from any
downstream Modbus devices.
EtherGate ModemGate

Ethernet Telephone line


Serial Serial

● EtherGate: access via Ethernet port and ● ModemGate: access from


ModbusTCP to daisy-chained Modbus telephone network to devices
devices connected to the meter’s serial connected to the meter’s serial ports
ports

Schneider Electric - Division - Name – Date 22


Simple Network Management protocol
(SNMP)

● Some applications as Data Centers and Critical Power require SNMP protocol
to map (convert) registers or data from the meter in to usable information for the
different systems.

● This implementation of the ION7650 and 7550 supports read only mode, except
for the following SNMP related text strings:
● System Contact
● System Name
● System Location

● You can also customize the text on the meter’s MIB (Management Information
Base) file: ion7x50schneiderMIB.asn.

Schneider Electric - Division - Name – Date 23


100 Base TX/FX Connectivity

● New communications cards support 100 Base TX and 100 Base FX


connections
● This will support more network infrastructures

Schneider Electric - Division - Name – Date 26


New communications card. (Field
installations)

● Firmware v350 or higher is required

● The 7550/7650 communications card is not supported on legacy


meters ION7500 and ION7600.

● The difference is only that the D7 and F1 provide faster Ethernet


connections (100Base-TX and 100Base-FX rather than 10Base-T and
10Base-FL).

Schneider Electric - Division - Name – Date 34


New communications card. (Field
installations)
Speci
Comm
Type al
Card
Order

P765
C

ION7550 /
7650 Comm Order Code Description
Card*
Comm Card P765C ION7550 / ION7650 Communications card for field retrofit installations

Type A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port).


Front optical port support for meters with integrated display.

C1 Standard communications plus 10/100BASE-T Ethernet (RJ-45), 56k universal internal modem (RJ-
11; the modem port is shared with the front optical port). Ethernet and modem gateway functions each
use a serial communications port.

D7 Standard communications plus 10/100BASE-T Ethernet, 100BASE-FX Ethernet Fiber, 56k universal
internal modem (RJ-11; the modem port is shared with the front optical port).
Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10/100BASE-T Ethernet. Ethernet gateway function uses a serial
communications port.

F1 Standard communications plus 10/100BASE-T Ethernet, 100BASE-FX Ethernet Fiber (SC fiber optic
connection). Ethernet gateway function uses a serial communications port.

M1 Standard communications plus 56k universal internal modem (RJ-11; the modem port is shared with
the front optical port). Modem gateway function uses a serial communications port.

Special Order A None

C Tropicalization treatment applied

Schneider Electric - Division - Name – Date 35


New communications options and part
numbers

● Example of New Part Number with one of the new communications options:
M7650B1C0B6F1A0E
Communications ■ A0.- Standard Comms: 1 RS232/RS485 port (COM1), 1 RS485
(COM2), Integrated display models also include a Type 2 ANSI
optical port (COM4)

■ E0.- Standard Comms. plus Ethernet 10/100 BaseT Ethernet (RJ-45).


Ethernet gateway function uses a serial communications port.
■ D7..- Standard communications plus 10/100Base-T Ethernet (RJ-45)
and 100BASE-FX Ethernet Fiber, 56k universal internal modem (RJ-
11). Ethernet and modem gateway functions each use a serial
communications port.

■ F1.- Standard communications plus 10/100Base-T Ethernet (RJ-45)


and 100BASE-FX (SC fiber optic connection). Ethernet gateway
function uses a serial communications port.

Schneider Electric - Division - Name – Date 36


Integration with ION-Enterprise

● Version 5.6 SP1 supports all new features of the ION75/7650 firmware
version 350

Schneider Electric - Division - Name – Date 38