Professional Documents
Culture Documents
Fire Protection & Prevention: NME 525 - 1ME
Fire Protection & Prevention: NME 525 - 1ME
PREVENTION
CHAPTER 9
NME 525 – 1ME
GROUP 2
PADILLA, MARK DARYL C.
NERY, HARVEY D.
MALUMAY, LEYZER S.
HADAP, JOHN ISRAEL F.
IMPORTANCE OF FIRE PROTECTION AND
PREVENTION
• Fires affect thousands of companies each year resulting in injury, lost customer trust and
building damage. By establishing a fire prevention and preparedness program, you can help
avoid injuries to your employees and visitors, costly damages, and potential fines to your
business. Below are some best practices to help prepare your facility for a fire emergency.
Section 1.0 GENERAL REQUIREMENTS
1.1 SCOPE
The provision of the Fire Protection and Prevention to and govern the following:
a. All private or public buildings, facilities,
structures and their premises, constructed,
existing and proposed.
b. Storage, handling or use of combustible,
flammable, toxic, explosives and other
hazardous materials.
c. Applications of Fire safety construction,
automatic fire suppressions and fire
protective equipment or systems.
1.2 GENERAL SAFETY
REQUIREMENTS
Structure or Facility the owner of any building, structure,
facility shall install, provide, incorporate, adopt
and maintain under operable and usable
conditions the automatic fire protection devices,
equipment, fire safety construction, and warning
system.
1.3 PURPOSE
The purpose of this standard is to provide a reasonable degree of protection for life and
property from fire through the installation of the appropriate type of fire protection for the
different buildings, structures or facilities. Hence in relation to these standards, all of the
owner and all occupants of the buildings, structures or facilities shall organize themselves and
develop, implement fire safety programs to include fire preventions in the buildings, premises,
notification of the Fire Department Personnel to the existence of a fire.
SECTION 2.0 INDOOR GENERAL
STORAGE
2.1 APPLICATION AND SCOPE
The standard applies to storage, 6.40 m or less in height, of commodities which with them packaging
and storage aids would classify as ordinary combustibles. This standard also applies to storage of
commodities which with their packaging and storage aids would classify as non-combustibles
regardless of storage height. This standard does not cover unpacked bulk storage such as grain, coal or
similar commodities. Fire protection system related to certain commodities introduce hazard different
than contemplated with the above-mentioned General Storage standard. We have other standards for the
following storage occupancies:
STANDARDS FOR THE FOLLOWING STORAGE
OCCUPANCIES:
a. Rack storage of Materials over 12 ft. (3.66 m) in height in racks, and storage up to and including 25
feet (7.62 m) in height and storage over 25 feet (7.62 m) in height. Water density for fire protection for
these particular hazards varies from 0.24 gpm /sq.ft. 9.779 (Lmin/m sq.) to 0.68 gpm /sq.ft. (27.7
L/min/m sq.) Water density requirement for fire protection also depends on the four classes of
commodities, namely Class I, II, III, IV.
Commodity Classification
• Class I Commodity is defined as essentially non-combustible product on wood pallets, or in ordinary
corrugated cartons with or without single thickness dividers, or in ordinary paper wrappings, all on
wood pallets. Such product may have a negligible amount of plastic trims, such as knobs or handles.
Examples of Class I products are:
Metal products. Metal desk with plastic tops and trim, electrical coil, electrical devices in their metal
enclosures, dry cell batteries, stoves, metal cabinets, washers, dryers.
Foods. Foods in non-combustible containers, frozen, foods, meat, fresh fruits, and vegetables in non-
plastic trays.
• Class II Commodity is defined as Class I products in slatted wooden crates, solid wooden boxes, or
equivalent combustible packaging materials on wood pallets.
Thinly coated fine wire such as radio coil wire on reels or in cartons, incandescent lamps or fluorescent
bulbs; beer or wine up to 20 percent alcohol, in wood containers; and Class I product, if small cartons
or small packages placed in ordinary corrugated cartons.
• Class Ill Commodity is defined as wood, paper, natural fibre cloth, plastic products on wood pallets,
products may be contain a limited amount of plastics. Wood dressers with plastic drawer glides,
handles, and trim are examples of a commodity with a limited amount of plastic.
• Class IV Commodity is defined as Class I, II, Ill products containing an appreciable amount of
plastics in paper board cartons on wood pallets. Examples of Class IV products are: Small appliances,
typewriters, and cameras with plastic parts; plastic-backed tapes and synthetic fabrics or clothing. An
example of packing material is a metal product in a foamed plastic cocoon in corrugated cartons.
“Sprinkler System Design Curves for Solid Pile, Palletized and Bin Box Storage over 12 ft. (3.7 m),
and Shelf Storage 12 ft. (3.7 m) to 15 ft. (4.6 m) high, shall be in accordance with Figure 9-1.1” (6-
1.2)
b. Fire Protection Standard for Storage of Rubber Tires. This provision contained in this standard apply
to new facilities for tire storage and when converting existing facilities to tire storage occupancy.
c. Fire Protection Standard for the Storage of Roll Paper. The purpose of this standard is to provide a
reasonable degree of protection for the storage of roll paper when stored in buildings or structures
through installation requirements based upon sound engineer principles and test data.
Classification of Roll Paper
• Heavy Weight Class. Includes paper board and paper stock having a basis weight [weight per 1,000
sq.ft. (93 m.sq.)j of 20 lb. (9.1 kg.) or greater.
• Medium Weight Class. Includes the broad range of papers having basis weight [weight per 1,000
sq.ft. (93 m.sq.)] from 10 lb. (4.5 kg.) to 20 lb (9.1 kg.)
• Light Weight Class. Includes all papers having basis weight [weight per 1,000 sq.ft. (93 m.sq.)] less
than 10 lb (4.5 kg) and tissues.
DEFINITIONS
• Available Height for Storage —The maximum height at which commodities, packaging or storage can be stored
above the floor and still maintain adequate clearance from structural members and the required clearance below
sprinklers.
• Ordinary Combustibles —This term designates commodities, packages or storage aids which have hats of
combustion kilojoules per kilogram similar to wood, cloth or paper and which produce fires that may normally be
extinguished by the quenching and cooling effect of water.
• Exposure —The exterior presence of combustibles which, if ignited, could cause damage to the storage building or
its contents.
• Fire Wall —A wall designed to prevent then spread of fire having a fire resistance rating of not less than four hours
and having sufficient structural stability under fire conditions to allow collapse of construction on either side
without collapse of wall.
• Horizontal Channel —Any uninterrupted space in excess of 1524 m in length between horizontal layers of
stored commodities. Such channels may be formed by pallets, shelving, racks or other storage commodities.
Such channels may be formed by pallets, shelving, racks or other storage arrangements.
• Non-combustibles —This term designate commodities, packaging or storage aids which will not ignite, bum or
liberate flammable gases when heated to a temperature of 749 deg for five minutes.
• Storage Aids —This term designates commodity storage devices such as shelves, pallets, dunnage, decks,
platforms, trays, bins, separators and skids.
• Warehouse —Any building or area within a building used principally for the storage of commodities.
• Extra Combustible —Materials, which, either by themselves or in combination with their packaging, are highly
susceptible to ignition and will contribute to the intensity and rapid spread of fire.
• Moderate Combustible —Materials or their packaging, either of which will contribute fuel to fire.
• Non-Combustibles —Materials and their packaging which will neither ignite nor support
combustion.
The word SHALL is intended to indicate requirements. The words IT IS RECOMMENDED indicate
advisory provisions. APPROVED refers to approval by the authority having jurisdiction.
• Authority Having Jurisdiction. The “authority having jurisdiction” is the organization, office or
individual responsible for approving equipment, an installation or procedure.
Class A Fire —Fire involving ordinary combustible materials such as wood, cloth, paper, rubber and plastics
• Sprinkler System —A sprinkler system, for fire protection purpose, is an integrated system of one or
more water supplies for fire use, underground and overhead piping designed in accordance with fire
protection engineering standards.
• Warehouse —Any building or area within a building used principally for the storage of commodities
CLASSIFICATION OF STORAGE
• a. Type I Storage. Type I storage is that in which combustible commodities or noncommodities
involving combustible package or storage aids are stored over 4,550 mm but not more than 6,400 mm
high in solid piles or over 3,650 mm but not more than 6,400 mm high in piles that contain horizontal
channels.
b. Areas. Fire areas of warehouses should be limited to maintain the total value of the commodity within reasonable limits
yet not be too restrictive for low value commodities. Conversely, high value and vital commodities. Should be restricted to
smaller areas than for average value commodities such as found in the usual general warehouse. The combustibility of the
commodity and its packaging or storage aids should be taken into account. Other considerations are the difficulty
encountered in fire fighting and salvage operations in large undivided areas.
• Type I and Type II Storage. When protected in accordance with this standard, 4,645 m2 is considered the
maximum area for average value commodities enclosed by exterior walls or combination of exterior walls
and fire walls. A multi-storey building having three-hour fire-resistive construction shall be considered as
having each floor a separate fire area.
• Type Ill Storage. Warehouses constructed and protected in accordance with this standard may be of any
reasonable area.
c. Ventilation. Consideration should be given to the provision of roof vents and curtain boards, particularly
in large one-storey warehouses where distance to exterior wall openings makes it difficult to place hose
streams in service.
d. Protection of Stairways and Shafts. Stairways and other vertical shafts shall be enclosed with fire-
resistive construction or sealed at each floor level with construction having the same fire resistance rating as
the floor. Where stairways are required for the exit of occupants, such stairways and doors in interior
partitions enclosing stairways shall be adequately protected.
e. Stairways and Shaft of High Rise Buildings Shall Be Smoke Proof Enclosures. Smoke proof enclosures
shall be a stair enclosure so designed that the movement into the smoke proof enclosure of the product of
combustion produced by a fire occurring in any part of the building shall be limited and/or eliminated. The
smoke proof enclosure may be accomplished by using natural ventilation, mechanical ventilation a vestibule
or by pressurizing A smoke enclosure shall consist of a continuous stair enclosed from the highest point to the
lowest point by barriers having a 2-hour fire resistance rating.
f. Natural Ventilation. Smoke proof enclosures by natural ventilation shall comply with all the following:
• Where a vestibule is provided, the doorway into the vestibule shall be protected with an approved fire door
assembly having a 1-1/2-hour fire protection rating and the fire door assembly from the vestibule to the stair
shall have not less than a 20- minute fire protection rating.
• Every vestibule shall have a minimum net area of 16 sq. ft. (1.5 sq. m) of opening in an exterior court, yard
or public space at least 20 ft. (6.1 m) in width.
• Every vestibule shall have a minimum dimension not less than the required width of the corridor leading to
it and a minimum dimension of 72 in. (183 cm) in the direction of travel.
g. Mechanical Ventilation. Smoke proof enclosures by mechanical ventilation shall comply
with all of the following:
The door assembly from the building into the vestibule shall be 1-1/2-hour fire protection
rating and the door assembly from the vestibule to the stairway shall have not less than 20-
minute fire protection rating.
Vestibules shall have a minimum dimension of 44 in. (112 cm) in width and 72 in. (183 cm)
in direction of exit travel.
The vestibules shall be provided with not less than one air change per minute, and the
exhaust shall be 150 percent of the supply. Supply air shall enter and exhaust air shall
discharge from the vestibule through separate tightly constructed ducts used only for that
purpose. Su
The vestibule ceiling shall be at least 20 in. (50.8cm) higher than the door opening into the vestibule
to serve as a smoke and heat trap and to provide an upward moving air column. The height may be
decreased when justified by engineering design and field testing.
The stair shall be provided with a damper relief opening at the top and supplied mechanically with
sufficient air to discharge a minimum of 2500 cu. Ft/mm. (70.8 cu rn/mm) through the relief opening
column in the stair relative to atmosphere with all doors closed and a minimum of 0.10 inch water
column (25 Pa) difference between the stair and the vestibule.
h. Stair Pressurization. Smoke proof enclosures by stair pressurization shall comply with all of the
following:
The building shall be throughout by an supervised automatic system.
There shall be an engineered system to pressurize the air enclosure capable of developing 0.05 in.
(12.5 Pa) in addition to the maximum anticipated stack pressure relative to other parts of the building
measured with all the enclosure doors closed.
i.Activation of Mechanical Ventilation System. For both mechanical and pressurized stair enclosure
systems, the activation of the systems shall be initiated by smoke detectors and by manual controls
accessible to the fire department. The required system shall also be initiated by the following, if
provided.
Water flow signal from a complete automatic sprinkler system.
General evacuation alarm system.
j. Standby Power. An approved self-contained generator set to operator whenever there is a loss of
power in a normal house current shall provide standby Power for mechanical ventilation.
k. Testing. Before the mechanical equipment is accepted by the authority having jurisdiction, it shall be
tested to confirm that the mechanical equipment is operating in compliance with these requirements.
l. Emergency Lighting. The stair shaft and vestibule shall be provided with emergency lighting.
m. Exposure Protection. Adequate protection against exposure shall be provided where the warehouse
or its contents are subject to damage from external fire. Depending upon the severity of the exposure,
such protection should consist of parapet masonry walls without openings, wire glass in metal framed
windows and/or open sprinklers.
o. Piles Containing Horizontal Channels
p. Type I and Type II Storage. Horizontal channels formed by rack arrangement should be suitably
fire stopped by means of barrier at intervals of 7,620 mm unless additional automatic sprinklers are
provided at intermediate levels to protect the storage.
SECTION 3.0 FIRE PROTECTION
SYSTEMS
3.1 STANDARD FOR THE DESIGN AND
INSTALLATION OF SPRINKLER SYSTEM
a. General Information
1. Sprinkler System. A sprinkler system, for fire protection purposes, is an integrated system of underground and
overhead piping engineering standards. The installation includes a water supply such as a gravity tank, fire
pump, reservoir or pressure tank and/or connection by underground piping to a city main. The portion of the
sprinkler system above ground is a network of specially sized or hydraulically designed piping installation in a
building, structure or area to which sprinklers are connected
• 2. Scope and Purpose. This standard is the minimum for the installation of the
sprinkler system for buildings, the character and adequacy of water supplies to
sprinkler systems. The purpose of this standard is to provide protection for life and
property from fire through installation requirements for sprinkler systems based
upon engineering principles, test data, and field experience.
3. Classification of Sprinkler Systems. Sprinkler Systems are classified into different types listed below:
(a) Wet Pipe Systems. A system employing automatic sprinklers attached to a piping system containing water and
connected to a water supply so that water discharges immediately from sprinklers opened by a fire. This is the
type of sprinkler system commonly used and adaptable to the climate in our country.
• (b) Deluge System. A system employing open sprinklers attached to a piping system connected to a water supply
through which is opened by the operation of a fire detection system installed in the same areas as the sprinklers;
when this valve opens, water flows into the piping system and discharges from all sprinklers attached thereto.
This is the system used in extra hazard areas like an aircraft hangar, storage tanks of combustible liquids, gases
and oils, high voltage substations transformers. Foam chemicals may be incorporated to the system to be more
effective in fighting class B fires.
4. Classification of Occupancies
(a) Light Hazard Occupancies. Occupancies where the quantity and/or combustibility of contents are low and fire
with relatively low rate of heat release are expected
(b) Ordinary Hazard Occupancies. There are three groups of ordinary hazard occupancies and these are as
follows:
1) Ordinary Hazard (Group 1). Occupancies where combustibility is low, quantity of combustible is moderate,
stockpiles of combustibles do not exceed 2,400 mm and fire with moderate rate of heat release are expected.
Included in this group are the following having conditions similar to: Automobile parking garages, Bakeries,
Beverages manufacturing, Canneries, Dairy products manufacturing and processing, Electronic plants, Glass and
glass products manufacturing, Laundries and Restaurant service areas.
2) Ordinary Hazard (Group 2). Occupancies where quantity and combustibility of content is moderate. Stockpiles
do not exceed 3,700 mm and fire with moderate heat release is expected. Under this group are the following: Cereal
mills, Chemical plant —ordinary, Machine shops, Metal working, Cold storage warehouses, Distilleries Leather
goods manufacturing, Libraries, large stock room areas, Mercantile, Printing and publishing, Textile
manufacturing, Tobacco pro-ducts manufacturing and Wood products assembly.
3) Ordinary Hazard (Group 3). Occupancies where quantity and/or combustibility of contents is high, and fire of
high rate of release are expected. Included in this group are the following having conditions similar to: Feed mills,
Pulp and paper mills, Paper process plants, Piers and wharves, Repair garages, Tire manufacturing, Ware houses
(having moderate to higher combustibility of contents such as paper, household furniture, paint general storage,
whiskey, etc.), and Wood machining.
(c) Extra Hazard Occupancies. Occupancies where quantity and combustibility of contents is very high, and
flammable and combustible liquid, dust, lint or other materials are present introducing the probability of rapidly
developing fire with high rate of heat release. Extra hazard occupancies are classified into two groups, Group 1 and
2.
1) Extra Hazard (Group 1). Include occupancies as described above with little or no flammable or combustible
liquids: combustible hydraulic fluid used areas, Die casting, Metal extruding, Plywood and particle board
manufacturing, Printing (using inks, with below 37.8°C flash points, Rubber reclaiming, compounding, drying,
milling, vulcanizing, Saw mills, Textile picking, opening, blending, garneting, carding, combining of cotton
synthetics, wool, shoddy, or burlap, and Upholstering with plastic foams.
2) Extra Hazard (Group 2). Include occupancies with moderate to substantial amount of flammable or combustible
liquids or where shielding of combustibles is extensive: Asphalt saturating, Flammable liquids spraying, Flow
coating, Mobile home or modular building, assemblies (where finished enclosure is present and has combustible
interiors, Open oil quenching, Solvent cleaning, Varnish and paint dipping.
5. Working Plans. Working plans shall be submitted to the authority having jurisdiction and the office of the Mechanical Department Building
Official before any equipment is installed or remodelled. Deviations from approved plans will require permission of the authority having
jurisdiction. Working plans shall be drawn to indicated scale, on sheets of uniform size, with plan of each floor, made so that they can be easily
duplicated and shall show the following data:
a. Name of owner and occupant
c. Point of compass
g. Location of partitions
w. Nominal pipe size and cutting length of pipe (or center to center dimensions) where typical branch lines prevail,
it will be necessary to size only one line.
y. Type of fittings and joints and location of all welds and bends.
z. Type and location of hangers and sleeves aa. All control valves ( OS&Y, outside screw and yoke) indicating
valve, check valves, drain pipes and test pipes.
• bb. Size and location of hand hose, hose outlets and related equipment.
• cc. Underground pipe size, length, location, weight, material, point of connections to city main, the type of
valves, meters and valve pits, and the depth that top of the pipe is laid below grade.
• ee. When the equipment is to be installed as an addition to an existing system, enough of the existing system
shall be indicated on the plans to make all conditions clear.
• gg. Location and detail plan of fire pumping units and type of pump drive, concrete foundation, pump suction
and discharge piping, type of controllers, in the case of electric motor driven pumps, the electrical power supply
to electric motor must be connected to an automatic started emergency generator of approved capacity to handle
fire pump motor loads in case of power failure of the local power supply facilities.
• hh. Hydraulic calculation for the system must be submitted which must indicate thefollowing: Density liter per
min/sq.m. Area of application, sq.m.; Coverage per sprinkler; Number of sprinkler calculated;Total water
required, liter per mm; Total water required for hose stream, liter/mm; Name of contractor; Name of designer.
• ii. Dry standpipe layout must be shown in the plans as required by the Building Code and Philippine Fire Code
P.D. No. 1185.
• jj. In case of high-rise buildings full building height must be shown, fire walls, fire doors, large unprotected
window openings, and blind spaces, distance to, construction and occupancy of exposing buildings which may
affect the effectivity of the proposed fire protection.
4.1 Purpose Requirements contained herein are for the proper handling and safeguarding of storage of types of commodities of
moderate combustible hazard. Standards for the storage of noncombustible commodities and those of extra combustible
hazard are excluded, as well as storage covered by specific standards.
• a. Because of the diversity of the materials handled, no fixed requirements can be provided
to cover all conditions. However, principles set forth herein will provide a basis for proper
protection of commodities in storage in the open.
• 4.2 Definitions