Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Why UPS is important?
What to consider when selecting a UPS?

UPS ultimate mission:


… to secure continuity of a critical process by supplying uninterrupted, clean power to
the critical load, maximizing availability.

 Identified criticality level of a process dominates also the infrastructure design:


 Sets the requirements for electrical power infrastructure around it
 Defines the levels of reliability and availability that needs to be achieved
 Defines the level of reasonable investment

UPS is the core of power infrastructure


Selecting correct UPS type for the application is the most critical part of site planning

© ABB Group
The concept of modular UPS
What makes it so unique

 Modular design allows the power protection capacity to be added when needed to meet the
existing demand, instead total up front deployment.
 Standardized modular design allows changes to such fundamentals as load criticality thus
needed protection level, installed power quantity and density.
 Modular designs typically include the ability to add redundancy which increases significantly
the system availability

 Until now, the advantages of modularity have been available with up to 50kVA
modules for the mid range power sector, only up to 1.2 MW systems.
 ABB is now ready to take it one step further……

ABB / Newave was the first to offer modular UPS to the market in 1998
- this drives to a technology advantage and experience!!

© ABB Group
Conceptpower DPA 500
High power modular UPS

All True Modular system benefits available in MW range


 The UPS for large data centers and other high power applications
 Scalable power in 100 kW steps

Decentralized Parallel Architecture (DPA™)


 Secures the highest level of availability through having true redundancy across modules.

© ABB Group
11/20/20 | Slide 10
Conceptpower DPA 500
Unique solution with superior benefits

 Scalability and future upgradability guaranteed with true


 Pay as you grow modular architecture

 Up to 96% efficiency ensures also OpEx can be


 Minimize the total cost of ownership minimized as result of reduced energy losses and costs
for electricity

 Reliable double conversion topology and redundancy


 Increase reliability across modules, makes the system fault proof

 Easy and fast to service: short MTTR thanks to on-line


 Maximize availability swappable modules

© ABB Group
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
True modularity with fault tolerant DPA™ architecture

 100 kW rated power module


 Each module can operate fully independently, thanks to
ABB’s Decentralized Paralleling Architecture (DPA™)

 5 modules in a single DPA 500 frame


 500 kW secured power in only 1.5 m²
 All modules are fully redundant with each other
 DPA 500 frame completes the system:
 Bypass input breaker, battery fuse and output
isolation switch for each module, dedicated.
 System maintenance bypass switch as option
 Single and dual input feed supported
 Top and bottom cable entry supported
 The frame supports both separate and common
battery arrangement

© ABB Group
11/20/20 | Slide 13
Conceptpower DPA 500
Scalability: 100 – 500 kW in one frame

Vertical, fast and easy scalability with 1 – 5 modules in a frame

© ABB Group
11/20/20 | Slide 14
Conceptpower DPA 500
Scalability: 100 – 3000 kW in a system

 6 frames can be further connected in parallel to achieve amazing 3 MW system total


power
 Multiple benefits follow from the advanced scalability:
 Adding capacity to system is easy
 Adding redundancy to increase availability and reliability becomes easy
 Standardizing UPS system to serve load segments of different sizes is reality

© ABB Group
11/20/20 | Slide 15
© ABB Group
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Top-of-the-line Performance
Specifications – brief overview

Technical Highlights
Classification IEC/EN 62040-3 VFI-SS-111
Working mode on-line double conversion
Module power rating 100 kW
Maximum power per frame 500 kW
Paralleling 5 modules per frame / 6 frames
System Power Range 100 kW – 3 MW
Maximum power (N+1) 2.9 MW
Output power factor 1.0
Efficiency in double conversion up to 96 %
Efficiency in eco-mode >99 %
Footprint 1.49 m²
Power density per m² up to 335 kW/m²
Maximum weight w/out batteries 975 kg
Module weight 55 + 54 kg (100 kW)
Input current distortion THDI < 3.5 %
Input power factor (PF) 0.99
Back-feed protection standard in each module

© ABB Group
11/20/20 | Slide 18
Top-of-the-line Performance
High double conversion efficiency

 High efficiency reaching - and exceeding 96%


 Having the curve flat means that high efficiency is reached already at low load levels
 95.8% at 25% load

© ABB Group
11/20/20 | Slide 19
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Mechanical construction highlights

 Very compact design occupying less space


 Footprint = 1.49 m²; power density (500 kW) = 335 kW/m²
 Small weight
 Empty frame = 430 kg; fully equipped (500kW) = 975 kg
 Top / bottom cable entry and front serviceable
 Single and dual feed supported
 Separate and common batteries supported
 Terminal bus-bars with a lot of space around them
 Smart module mechanical design allows easy servicing
 Split module makes sure the weight of each part is reasonable active module = 55 kg,
passive module = 54 kg
 MBS on frame level (optional)

© ABB Group
Conceptpower DPA 500
All included

 Up to 5 x 100 kW online swappable DPA


UPS modules
 Module dedicated output isolation
switch, static bypass and battery fuses
 I/O with top or bottom cable entry (as
standard)
 Single or dual input feed
 Common or separate battery connection
 Maintenance bypass switch (optional)
 Communications interface
 System display

© ABB Group
11/20/20 | Slide 22
Frame - Mechanical Construction
Compact and front serviceable
Front Back

Compact and space saving cabinet occupies only 1.5 m 2 footprint


Only front access needed for installation and service!
11/20/20 | Slide 23
Frame - Mechanical Construction
Dimensions and Clearances

Dimensions in mm
 Width = 1580
 Height = 1975
 Depth = 940
 1.5 m2 footprint!
 Frame weight < 500kg

Clearances in mm
 Front 900 mm
 Back 300 mm (air outlet)

High power density = 335 kW/m2


Frame - Mechanical Construction top entry
Cable entry

bottom entry

© ABB Group
11/20/20 | Slide 25
Frame - Mechanical Construction
Top entry
Top view

© ABB Group
11/20/20 | Slide 26
Frame - Mechanical Construction
Bottom entry
Bottom view

© ABB Group
11/20/20 | Slide 27
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500 – Electrically
Double Conversion True Modular UPS

100kW UPS Module


Bypass input
=
Rectifier input
=
= Critical
= Load

Each 100 kW module is a complete UPS:

IGBT rectifier and inverter


Control logic and display
Battery converter
Static bypass switch
Inbuilt back-feed protection

© ABB Group
11/20/20 | Slide 29
Module - Mechanical Construction
Very compact
Dimensions, H x W x D = 178(4HU) x 710 x 750 mm
Weight 55 kg Weight 54 kg

- Rectifier, booster, inverter, - Static bypass switch


- Battery charger - Input and output filters
- Logic control - Back-feed protection
- User interface (DPA mimic diagram + - Output contactor
display)

The 100 kW module is split into 2 separate subassemblies which makes the adding
and replacement easier as the weight is distributed evenly to both parts.

© ABB Group
11/20/20 | Slide 30
Module - Mechanical Construction
Front and Back View
Front Back

 Robust design
 Strong and practical handles
 Error proof: impossible to slide in the modules into wrong position
 Smart connectors allow the Online Swapping of modules
© ABB Group
11/20/20 | Slide 31
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Flexible runtime configuration

Number of battery blocks selectable from 40-50


 Flexibility in battery configuration  Batteries can be sized for exact match
 Straightforward re-use batteries of old, replaced UPS

 The line-and-match battery cabinet supports


 2x50x28Ah  5-6 min @ 100 kW load
 Most common battery runtimes  3x40x28Ah  8-9 min @ 100 kW load
with standard configuration  Longer autonomies supported thanks to the strong
battery charger (up to 60A charging capacity at full
100% nominal load)

 Separate battery arrangement allow full redundancy


 Separate and common battery thanks to module dedicated batteries
arrangement supported
 Common battery arrangement for lower battery costs

© ABB Group
Options
Battery cabinet

Each battery cabinet provides up to 8-9 minutes backup time @ 100kW

© ABB Group
11/20/20 | Slide 34
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
System Display
Graphical Touchscreen Display

 Clear system overview, measurements and system status


 Navigation into module level, module level measurements and status
 System level commands

Features
 7‘‘ touchscreen interface

 Interactive mimic diagram


 Colored and graphical display
 Integrated buzzer for alarms
 13 languages selection
 Extended events log (1000 events)

© ABB Group

Month DD, Year | Slide 36


System Display
Graphical Touchscreen Display

System status
Quick access to
mimic diagram Time
Date
Quick access to service, Parallel/single
operation and Access to module
information menus level

Status of system

Direct access zones


to specific menus

© ABB Group

Month DD, Year | Slide 37


System Display
Navigation Screen

Alarms and events log Service setup


UPS measurements User setup
UPS commands UPS information

© ABB Group

Month DD, Year | Slide 38


Conceptpower DPA 500
Options and accessories

 Line-and-match battery cabinets


 Frame integrated system maintenance bypass switch
 Selection of software and connectivity options including:
 SNMP cards
 Environmental monitoring sensor adapters
 Relay card
 Hardened packaging (wooden box)

NETWORK INTERFACE CARD, SOFTWARE


AND ENVIRONMENTAL SENSORS

© ABB Group

http://librex.co.uk/media/catalog/product/cache/1/image/5e06319eda06f020e4359
4a9c230972d/c/d/cd55.jpg_clipped_1_1.jpg
Connectivity
Options and possibilities
DATA PROTECTION - CLIENT DATA MONITORING AND MANAGEMENT

Shutdown service Web browser, Remote View, BMS

E-mails

LAN

SMS Several
protocols

NETWORK INTERFACE CARD ENVIRONMENTAL SENSORS


UPS
AND SOFTWARE

© ABB Group

11/20/20 | Slide 40
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Straightforward service concept

Modular concept benefits for maintenance and service


 Limited spare parts inventory in quantities, different articles and total value
 Standardized service practices
 Minimized risk for human errors

UPS service with ABB’s online swappable modules:


 Concurrent preventative maintenance by swapping modules
 Concurrent repair by swapping a module

DPA 500 frame mechanical design allows for efficient and safe servicing
 Front access only needed for maintenance and service
 Smart connectors allow for safe handling of modules

Operator training can be standardized and simplified since the UPS system is
a standard solution.

© ABB Group
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Designed to secure continuity of critical operations

Conceptpower DPA 500 is designed for:


 Large datacenters
 Mid-sized datacenters
 Server rooms and other IT applications
 Healthcare
 Industry automation processes
 Other critical applications

© ABB Group
Conceptpower DPA 500
Allows for standardization of power protection concept

Modular scalability
Modular scalability enables
enables the
the users
users with
with various
various types
types and
and
sizes of
sizes of data
data centers
centers to:
to:
 Optimize
 Optimize the
the solution
solution according
according to
to the
the needs
needs of
of each
each data
data
center or
center or each
each load
load segment
segment

 Increase
 Increase the
the system
system availability
availability and
and gain
gain savings
savings due
due to
to
simple and
simple and standardized
standardized power
power protection
protection concept
concept

 Streamline
 Streamline and
and simplify
simplify service
service concept,
concept, which
which minimizes
minimizes
chances for
chances for error,
error, is
is cost
cost efficient
efficient and
and maximizes
maximizes availability
availability
Small or big

… growing … modular

© ABB Group
Conceptpower DPA 500
Allows for standardization of power protection concept

The same UPS module is the basic building


block for large variety of applications.
Datacenter Application
Scalability example – distributed end-of-row concept

Typical one-rack-row power demand can vary from 20kW to even hundreds of kW. Only a modular
UPS is capable to adapt changes of power demand in a growing infrastructure

© ABB Group
Datacenter Application
Scalability example – distributed end-of-row Tier IV

TIER IV built using de-centralized


power protection concept:

Power demand can vary greatly, from


500kW up to 3 MW and above.
Only a modular UPS is capable to
adapt changes in power demand in a
changing infrastructure

© ABB Group
Conceptpower DPA 500
Scalability example – centralized Tier IV
Stage 1 – 4x300kW (A and B feeds)

Stage 2 – 6x500kW (A and B feeds)

Power demand can vary greatly, from 500kW up to 3 MW and above.


Only a modular UPS is capable to adapt changes in power demand in a changing infrastructure

© ABB Group
11/20/20 | Slide 49
Conceptpower DPA 500
Content

 The Concept of a Modular UPS


 Product Overview
 Performance Characteristics
 Mechanical Design
 The 100 kW Module
 Battery Configuration
 User Interface, Software and Connectivity
 Maintenance and Service
 Applications
 Conclusions

© ABB Group
Conceptpower DPA 500
Advantages of the modular UPS concept

 Combines the right-sizing approach with scalability,


Pay-as-you-grow solution lowers your capital costs and increases
Optimize and save on capital 
utilization rates
investment  Innovative technology allows for maximal power density that frees
space for other critical equipment.

 Electrical and physical modularity allows for rapid installation with


Accelerate speed of minimal engineering.
 Same product and technology base can be selected to match the
deployment needs of each data center and each load segment

 Modular architecture allows for implementation of simple and


Decrease complexity and standardized power protection and service concept across
installations.
costs of service and  On-line swappable modularity ensures need for scheduled and
maintenance unscheduled downtime is minimized

 With efficiency of 96% in double conversion and 99% in ECO


mode, the operating costs can be >40% less compared to UPS of
Decrease the operating costs previous generation
 Increased availability and load uptime result in increased utilization

© ABB Group
Conceptpower DPA 500
Highest availability – lowest cost of ownership

Vertical
scalability: one to
five modules in
one single
cabinet

Horizontal scalability: cabinets in parallel


configuration up to 3 MW

Highest availability – Zero down time Lowest total cost of ownership (TCO)
• True redundancy with fault tolerant DPA • Modular architecture: optimized initial
architecture investment – Pay as you grow
• Fast and easy maintenance without downtime • Compact size and small footprint
with Online Swappable Modules (OSM) • Reduced energy losses with high double
• True scalability; flexible power upgrades and conversion efficiency, 96% (Eco-Mode >99%)
downgrades (100kW steps) • Concurrent, easy and fast maintenance

© ABB Group
© ABB Group
11/20/20 | Slide 53