Professional Documents
Culture Documents
Protection
GE Multilin
Outline
• Transmission line introduction
• What is distance protection?
• Non-pilot and pilot schemes
• Redundancy considerations
• Security for dual-breaker terminals
• Out-of-step relaying
• Single-pole tripping
• Series-compensated lines
2/
GE /
November 24, 2020
Transmission Lines
A Vital Part of the Power System:
• Provide path to transfer power between generation and load
• Operate at voltage levels from 69kV to 765kV
• Deregulated markets, economic, environmental requirements have
pushed utilities to operate transmission lines close to their limits.
3/
GE /
November 24, 2020
Transmission Lines
4/
GE /
November 24, 2020
Typical Protection Schemes
Short Lines
• Current differential
• Phase comparison
• Permissive Overreach Transfer Trip (POTT)
• Directional Comparison Blocking (DCB)
5/
GE /
November 24, 2020
Typical Protection Schemes
Medium Lines
• Phase comparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Inverse time overcurrent
• Current Differential
6/
GE /
November 24, 2020
Typical Protection Schemes
Long Lines
• Phase comparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Current Differential
7/
GE /
November 24, 2020
What is distance protection?
Intended
REACH point
F1
Z I*Z
V=I*ZF
I*Z -
V
Z I*Z
V=I*ZF
I*Z -
V
Intended
REACH point
RELAY
10 /
GE /
November 24, 2020
Source Impedance Ratio, Accuracy &
Speed Relay
Lin
System e
f LOC [ PU ]
Voltage at the relay: VR VN
f LOC[ PU ] SIR
Consider SIR = 30
Fault location Voltage Voltage change (%)
(%)
75% 2.4390 0.7868
90% 2.9126 0.3132
100% 3.2258 N/A
110% 3.5370 0.3112
12 /
GE /
November 24, 2020
Challenges in relay design
> Transients: 30
– High frequency
20
steady-state
– DC offset in currents output
10
– CVT transients in voltages
voltage, V
0
High Volta ge Line
C1 6 -10
3 5 CVT output
1
-20
C2
2
Seconda ry Volta ge
-30
0 1 2 3 4
power cycles
Output
13 /
GE /
November 24, 2020
Challenges in relay design
> Transients: 60
– High frequency
40
– DC offset in currents steady-state
output
20
– CVT transients in voltages
voltage, V
0
High Volta ge Line
C1 6 -20
CVT
3 5 output
1
-40
C2
2
Seconda ry Volta ge
-60
0 1 2 3 4
power cycles
Output
14 /
GE /
November 24, 2020
Challenges in relay design
100 100
vA vB vC
80
60
40
-20 SPOL
-40
-60
0 Sorry… Future (unknown)
-80
-100
-0.5 0 0.5 1 1.5
-50
5
iA
4
3
SOP
-100
2 -0.5 0 0.5 1 1.5
Current [A]
power cycles
1
-1
iB, iC > In-phase = internal fault
-2 > Out-of-phase = external fault
-3
-0.5 0 0.5 1 1.5
15 /
GE /
November 24, 2020
Transient Overreach
16 /
GE /
November 24, 2020
Zone 1 and CVT Transients
Capacitive Voltage Transformers (CVTs) create certain
problems for fast distance relays applied to systems with high
Source Impedance Ratios (SIRs):
> CVT-induced transient voltage components may assume
large magnitudes (up to 30-40%) and last for a
comparatively long time (up to about 2 cycles)
> 60Hz voltage for faults at the relay reach point may be as
low as 3% for a SIR of 30
> the signal may be buried under noise
17 /
GE /
November 24, 2020
Zone 1 and CVT Transients
CVT transients can cause distance relays to overreach.
Generally, transient overreach may be caused by:
> overestimation of the current (the magnitude of the current
as measured is larger than its actual value, and
consequently, the fault appears closer than it is actually
located),
> underestimation of the voltage (the magnitude of the
voltage as measured is lower than its actual value)
> combination of the above
18 /
GE /
November 24, 2020
Distance Element Fundamentals
Z1 End Zone
XL
XC
15
15
34
34 42
42 44
44
Actual
ActualFault
Fault
Locatio n
Location
10
10
dynami
dynamic cmhomho
zone extended
zone extended Line
forforhigh Line
30
30
highSIRs
SIRs Impedance
Impedance
5
5
Reactance [ohm]
Reactance [ohm]
18
18 Trajectory
Trajectory
22
22 (msec)
(msec)
0
0
26
26
-5
-5 -10
-10
-5
-5
Resistance [ohm]
0
0 Impedance
5
Impedance
5 locus
10
locus
10 may
maypass
pass
Resistance [ohm]
below
belowthe theorigin
originof ofthe
theZ-plane
Z-plane--
this
thiswould
wouldcall
callforforaatime
timedelay
delay
to
toobtain
obtainstability
stability
20 /
GE /
November 24, 2020
CVT Transient Overreach Solutions
> apply delay (fixed or adaptable)
> reduce the reach
> adaptive techniques and better filtering algorithms
21 /
GE /
November 24, 2020
CVT Transients – Adaptive Solution
> Optimize signal filtering:
– currents - max 3% error due to the dc component
– voltages - max 0.6% error due to CVT transients
> Adaptive double-reach approach
– filtering alone ensures maximum transient overreach at
the level of 1% (for SIRs up to 5) and 20% (for SIRs up
to 30)
– to reduce the transient overreach even further an
adaptive double-reach zone 1 has been implemented
22 /
GE /
November 24, 2020
CVT Transients – Adaptive Solution
The outer zone 1:
> is fixed at the actual reach
> applies certain security delay to cope with CVT transients
X
The inner zone 1:
> has its reach dynamically Delayed
Trip
controlled by the voltage
magnitude
> is instantaneous
Instantaneous
Trip
23 /
GE /
November 24, 2020
Desirable Distance Relay Attributes
Filters:
> Prefiltering of currents to remove dc decaying transients
– Limit maximum transient overshoot (below 2%)
> Prefiltering of voltages to remove low frequency transients
caused by CVTs
– Limit transient overreach to less than 5% for an SIR of 30
> Accurate and fast frequency tracking algorithm
> Adaptive reach control for faults at reach points
24 /
GE /
November 24, 2020
Distance Relay Operating Times
25 /
GE /
November 24, 2020
Distance Relay Operating Times
35ms
25ms 30ms
20ms
15ms
26 /
GE /
November 24, 2020
Distance Relay Operating Times
3P faults
27 /
GE /
November 24, 2020
Actual
Actualmaximum
maximumreach
reachcurves
curves
100
100
Relay 4
90
90
80
80 Relay 3
70
70
[%]
Rach[%]
60
60
MaximumRach
50
50
Maximum
40
40
Relay 2
30
30
20
20
Relay 1
10
10
00
00 55 10
10 15
15 20
20 25
25 30
30
SIR
SIR
28 /
GE /
November 24, 2020
Maximum Torque Angle
29 /
GE /
November 24, 2020
Mho Characteristics
Traditional
Directional angle
“slammed”
Directional angle
lowered and
“slammed”
30 /
GE /
November 24, 2020
Load Swings
+XL
Load Trajectory
+R
31 /
GE /
November 24, 2020
Load Swings
“Lenticular”
Characteristic
Load swing
32 /
GE /
November 24, 2020
Load Encroachment Characteristic
34 /
GE /
November 24, 2020
Quadrilateral Characteristics
35 /
GE /
November 24, 2020
Quadrilateral Characteristics
Ground Resistance
(Conductor falls on ground)
36 /
GE /
November 24, 2020
Distance Characteristics - Summary
Mho Lenticular Quadrilateral
JX
R
Standard for phase Used for phase elements with Better coverage for
elements long heavily loaded lines ground faults due to
heavily loaded resistance added to
return path
37 /
GE /
November 24, 2020
Distance Element Polarization
38 /
GE /
November 24, 2020
Memory Polarization
> Positive-sequence memorized voltage is used for polarizing:
– Mho comparator (dynamic, expanding Mho)
– Negative-sequence directional comparator (Ground Distance
Mho and Quad)
– Zero-sequence directional comparator (Ground Distance
MHO and QUAD)
– Directional comparator (Phase Distance MHO and QUAD)
> Memory duration is a common distance settings (all zones,
phase and ground, MHO and QUAD)
39 /
GE /
November 24, 2020
Memory Polarization
jX Static MHO characteristic (memory not established or expired
ZL
Dynamic MHO characteristic for a reverse fault
ZS
40 /
GE /
November 24, 2020
Memory Polarization
jX Static MHO characteristic (memory not established or expired)
ZL
ZS
42 /
GE /
November 24, 2020
Ground Directional Elements
> Pilot-aided schemes using ground mho distance relays have
inherently limited fault resistance coverage
> Ground directional over current protection using either negative
or zero sequence can be a useful supplement to give more
coverage for high resistance faults
> Directional discrimination based on the ground quantities is fast:
– Accurate angular relations between the zero and negative
sequence quantities establish very quickly because:
During faults zero and negative-sequence currents and
voltages build up from very low values (practically
from zero)
The pre-fault values do not bias the developing fault
components in any direction
43 /
GE /
November 24, 2020
Distance Schemes
44 /
GE /
November 24, 2020
Step Distance Schemes
• Zone 1:
– Trips with no intentional time delay
– Underreaches to avoid unnecessary operation for faults beyond remote terminal
– Typical reach setting range 80-90% of ZL
• Zone 2:
– Set to protect remainder of line
– Overreaches into adjacent line/equipment
– Minimum reach setting 120% of ZL
– Typically time delayed by 15-30 cycles
• Zone 3:
– Remote backup for relay/station failures at remote terminal
– Reaches beyond Z2, load encroachment a consideration
45 /
GE /
November 24, 2020
Step Distance Schemes
Local
Z1
BUS
BUS
Z1
Remote
46 /
GE /
November 24, 2020
Step Distance Schemes
Local
Z1 End Zone
BUS
BUS
End Zone Z1
Remote
47 /
GE /
November 24, 2020
Step Distance Schemes
Local
Z1
Breaker
Tripped
BUS
BUS
Breaker
Closed Z1
Remote
48 /
GE /
November 24, 2020
Step Distance Schemes
Local
Z2 (time delayed)
Z1
BUS
BUS
Z1
Z2 (time delayed)
49 /
Remote GE /
November 24, 2020
Step Distance Schemes
Z3 (remote backup) …
Z2 (time delayed)
Z1
BUS
BUS
50 /
GE /
November 24, 2020
Step Distance Protection
51 /
GE /
November 24, 2020
Distance Relay Coordination
Over Lap
Local Relay – Z2
Remote Relay – Z4
52 /
GE /
November 24, 2020
Need For Pilot Aided Schemes
BUS
BUS
Local Relay Remote Relay
Communication Channel
53 /
GE /
November 24, 2020
Pilot Communications Channels
• Distance-based pilot schemes traditionally utilize simple on/off
communications between relays, but can also utilize peer-to-
peer communications and GOOSE messaging over digital
channels
• Typical communications media include:
– Pilot-wire (50Hz, 60Hz, AT)
– Power line carrier
– Microwave
– Radio
– Optic fiber (directly connected or multiplexed channels)
54 /
GE /
November 24, 2020
Distance-based Pilot Protection
55 /
GE /
November 24, 2020
Pilot-Aided Distance-Based Schemes
56 /
GE /
November 24, 2020
Direct Underreaching Transfer Trip
(DUTT)
• Requires only underreaching (RU) functions which overlap
in reach (Zone 1).
•Applied with FSK channel
– GUARD frequency transmitted during normal
conditions
– TRIP frequency when one RU function operates
• Scheme does not provide tripping for faults beyond RU
reach if remote breaker is open or channel is inoperative.
• Dual pilot channels improve security
57 /
GE /
November 24, 2020
DUTT Scheme
Zone 1
Bus Bus
Line
Zone 1
58 /
GE /
November 24, 2020
Permissive Underreaching Transfer
Trip (PUTT)
• Requires both under (RU) and overreaching (RO)
functions
• Identical to DUTT, with pilot tripping signal
supervised by RO (Zone 2)
59 /
GE /
November 24, 2020
PUTT Scheme
Zone 2
Zone 1
To protect end of
line
Bus Bus
Line
Zone 1
Zone 2
Rx PKP
Local Trip
Zone 2
&
OR
Zone 1
60 /
GE /
November 24, 2020
Permissive Overreaching Transfer
Trip (POTT)
• Requires overreaching (RO) functions (Zone 2).
• Applied with FSK channel:
– GUARD frequency sent in stand-by
– TRIP frequency when one RO function operates
• No trip for external faults if pilot channel is
inoperative
• Time-delayed tripping can be provided
61 /
GE /
November 24, 2020
POTT Scheme
Zone 2
Zone 1
Bus Bus
Line
Zone 1
Zone 2
(Z1) Tx
Zone 1
Trip
(Z1) Rx OR Line
AND Breakers
Zone 2 t
o
62 /
GE /
November 24, 2020
POTT Scheme
POTT – Permissive Over-reaching Transfer Trip
BUS
63 /
Communication Channel GE /
November 24, 2020
POTT Scheme
Local Relay
Local Relay
FWD IGND Remote Relay
FWD IGND
Local Relay – Z2
Remote Relay – Z2
Communication
TRIP Channel
POTT RX POTT TX
Communications
POTT RX 1 POTT TX 1 A to G
Channel(s)
POTT RX 2 POTT TX 2 B to G
POTT RX 3 POTT TX 3 C to G
65 /
GE /
November 24, 2020
POTT Scheme
Current reversal example
TRIP
GND
GNDDIR
DIROC
OCFWD
REV POTT RX POTT TX ZONE
GND 2 OC
DIR ORREV
GND DIR OC FWD
66 /
GE /
November 24, 2020
POTT Scheme
Echo example
Remote FWD
IGND
Open
Remote – Z2
OPEN Communication
Channel
TRIP
POTT RX POTT TX
Communication
Channel 67 /
GE /
November 24, 2020
Hybrid POTT
68 /
GE /
November 24, 2020
Hybrid POTT
Zone 2
Zone 1
Remote Local
Weak
Bus Bus system
Line
Zone 1 Zone 4
Zone 2
69 /
GE /
November 24, 2020
Directional Comparison Blocking
(DCB)
• Requires overreaching (RO) tripping and blocking (B)
functions
• ON/OFF pilot channel typically used (i.e., PLC)
– Transmitter is keyed to ON state when blocking
function(s) operate
– Receipt of signal from remote end blocks tripping relays
• Tripping function set with Zone 2 reach or greater
• Blocking functions include Zone 3 reverse and low-set
ground overcurrent elements
70 /
GE /
November 24, 2020
DCB Scheme
Zone 2
Zone 1
Remote Local
Bus Bus
Line
Zone 1
Zone 2
71 /
GE /
November 24, 2020
Directional Comparison Blocking (DCB)
BUS
72 /
Communication Channel GE /
November 24, 2020
Directional Comparison Blocking (DCB)
Internal Faults
Local Relay – Z2
FWD IGND
TRIP
TRIP Timer
Start
Expired
Zone 2 PKP
NO Dir Block RX
OR
Local Relay GND DIR OC Fwd Remote Relay
73 /
GE /
November 24, 2020
Directional Comparison Blocking (DCB)
External Faults
Local Relay – Z2
FWD IGND
Remote Relay – Z4
75 /
GE /
November 24, 2020
DCUB Scheme
Forward
Bus Bus
Line
Forward
Trip
(Un-Block) Tx1 Line
Breakers
(Block) Tx2
Forward
76 /
Lockout GE /
November 24, 2020
Directional Comparison Unblocking
(DCUB)
BUS
77 /
Communication Channel GE /
November 24, 2020
Directional Comparison Unblocking
(DCUB)
Normal conditions
Load Current
GUARD1 RX GUARD1 TX
Local Relay Remote Relay
NO Loss of Guard GUARD2 TX GUARD2 RX NO Loss of Guard
NO Permission NO Permission
Communication
Channel 78 /
GE /
November 24, 2020
Directional Comparison Unblocking
(DCUB)
Normal conditions, channel failure
Load Current
Loss of Channel
FSK Carrier FSK Carrier
GUARD1
NO RX RX GUARD1 TX
Local Relay Remote Relay
Loss of Guard GUARD2 TX GUARD2
NO RX RX Loss of Guard
Block Timer Expired
Started Block Timer Expired
Started
Communication
Block DCUB Channel Block DCUB 79 /
until Guard OK until Guard OK GE /
November 24, 2020
Directional Comparison Unblocking
(DCUB)
Internal fault, healthy
Localchannel
Relay – Z2
Remote Relay – Z2
TRIP TRIP Z1
FSK Carrier FSK Carrier
GUARD1
TRIP1 RXRX GUARD1
TRIP1 TX
Local Relay Remote Relay
Zone 2 PKP ZONE 2 PKP
GUARD2
TRIP2 TX TX GUARD2
TRIP2 RXRX
Loss of Guard
Communication 80 /
Permission
Channel GE /
November 24, 2020
Directional Comparison Unblocking
(DCUB)
Internal fault, channel
Localfailure
Relay – Z2
Remote Relay – Z2
Loss of Channel
TRIP TRIP Z1
FSK Carrier FSK Carrier
GUARD1
NO RX RX GUARD1
TRIP1 TX
Local Relay Remote Relay
Zone 2 PKP ZONE 2 PKP
GUARD2
TRIP2 TX TX GUARD2
NO RX RX
Loss of Guard Loss of Guard
Block Timer Started Communication 81 /
Duration Timer Expired
Started Channel GE /
November 24, 2020
Redundancy Considerations
• Redundant protection systems increase dependability of the
system:
Multiple sets of protection using same protection principle and
multiple pilot channels overcome individual element failure, or
Multiple sets of protection using different protection principles
and multiple channels protects against failure of one of the
protection methods.
• Security can be improved using “voting” schemes (i.e., 2-out-of-3),
potentially at expense of dependability.
• Redundancy of instrument transformers, battery systems, trip coil
circuits, etc. also need to be considered.
82 /
GE /
November 24, 2020
Redundant Communications
End Zone
BUS
BUS
AND Channels: OR Channels:
POTT Less Reliable POTT More Reliable
Communication Channel 1
DCB Less Secure DCB More Secure
Communication Channel 2
More Channel Security More Channel Dependability
Loss of Channel 2 83 /
GE /
November 24, 2020
Redundant Pilot Schemes
84 /
GE /
November 24, 2020
Pilot Relay Desirable Attributes
• Integrated functions:
weak infeed
echo
line pick-up (SOTF)
• Basic protection elements used to key the
communication:
distance elements
fast and sensitive ground (zero and negative
sequence) directional IOCs with current, voltage,
and/or dual polarization
85 /
GE /
November 24, 2020
Pilot Relay Desirable Attributes
Pre-programmed distance-based pilot schemes:
Direct Under-reaching Transfer Trip (DUTT)
Permissive Under-reaching Transfer Trip (PUTT)
Permissive Overreaching Transfer Trip (POTT)
Hybrid Permissive Overreaching Transfer Trip (HYB POTT)
Blocking scheme (DCB)
Unblocking scheme (DCUB)
86 /
GE /
November 24, 2020
Security for dual-breaker terminals
• Breaker-and-a-half and ring bus terminals are common
designs for transmission lines.
• Standard practice has been to:
– sum currents from each circuit breaker externally by
paralleling the CTs
– use external sum as the line current for protective
relays
• For some close-in external fault events, poor CT
performance may lead to improper operation of line relays.
87 /
GE /
November 24, 2020
Security for dual-breaker terminals
88 /
GE /
November 24, 2020
Security for dual-breaker terminals
89 /
GE /
November 24, 2020
Security for dual-breaker terminals
• Direct measurement of currents
from both circuit breakers allows the
use of supervisory logic to prevent
distance and directional overcurrent
elements from operating incorrectly
due to CT errors during reverse faults.
• Additional benefits of direct
measurement of currents:
independent BF protection for
each circuit breaker
independent autoreclosing for
each breaker
90 /
GE /
November 24, 2020
Security for dual-breaker terminals
Supervisory logic should:
– not affect speed or sensitivity of protection elements
– correctly allow tripping during evolving external-to-internal
fault conditions
– determine direction of current flow through each breaker
independently:
• Both currents in FWD direction internal fault
• One current FWD, one current REV external fault
– allow tripping during all forward/internal faults
– block tripping during all reverse/external faults
– initially block tripping during evolving external-to-internal
faults until second fault appears in forward direction. Block
is then lifted to permit tripping.
91 /
GE /
November 24, 2020
Single-pole Tripping
93 /
GE /
November 24, 2020
Out-of-Step Relaying
Out-of-step blocking relays
– Operate in conjunction with mho tripping relays to prevent a
terminal from tripping during severe system swings & out-of-
step conditions.
– Prevent system from separating in an indiscriminate manner.
Out-of-step tripping relays
– Operate independently of other devices to detect out-of-step
condition during the first pole slip.
– Initiate tripping of breakers that separate system in order to
balance load with available generation on any isolated part of
the system.
94 /
GE /
November 24, 2020
Out-of-Step Tripping The locus must stay
When the inner for some time between
characteristic is the outer and middle
entered the element is characteristics
ready to trip
96 /
GE /
November 24, 2020
Series-compensated lines
Benefits of series capacitors:
• Reduction of overall XL of long lines
• Improvement of stability margins
• Ability to adjust line load levels
• Loss reduction
• Reduction of voltage drop during severe disturbances
• Normally economical for line lengths > 200 miles
Xs SC XL
E Infinte
Bus
97 /
GE /
November 24, 2020
Series-compensated lines
SCs create unfavorable conditions for protective relays and fault
locators:
• Overreaching of distance elements
• Failure of distance element to pick up on low-current faults
• Phase selection problems in single-pole tripping applications
• Large fault location errors
Xs SC XL
E Infinte
Bus
98 /
GE /
November 24, 2020
Series-compensated lines
Series Capacitor with MOV
99 /
GE /
November 24, 2020
Series-compensated lines
100 /
GE /
November 24, 2020
Series-compensated lines
Dynamic Reach Control
101 /
GE /
November 24, 2020
Series-compensated lines
Dynamic Reach Control for External Faults
102 /
GE /
November 24, 2020
Series-compensated lines
Dynamic Reach Control for External Faults
103 /
GE /
November 24, 2020
Series-compensated lines
Dynamic Reach Control for Internal Faults
104 /
GE /
November 24, 2020
Distance Protection Looking Through
a Transformer
• Phase distance elements can be set to see beyond any 3-
phase power transformer
• CTs & VTs may be located independently on different
sides of the transformer
• Given distance zone is defined by VT location (not CTs)
• Reach setting is in sec, and must take into account
location & ratios of VTs, CTs and voltage ratio of the
involved power transformer
105 /
GE /
November 24, 2020
Transformer Group Compensation
Depending on location of VTs and CTs, distance relays need to compensate for
the phase shift and magnitude change caused by the power transformer
106 /
GE /
November 24, 2020
Setting Rules
• Transformer positive sequence impedance must be
included in reach setting only if transformer lies between
VTs and intended reach point
• Currents require compensation only if transformer located
between CTs and intended reach point
• Voltages require compensation only if transformer located
between VTs and intended reach point
• Compensation set based on transformer connection &
vector group as seen from CTs/VTs toward reach point
107 /
GE /
November 24, 2020
Distance Relay Desirable Attributes
> Multiple reversible distance zones
> Individual per-zone, per-element characteristic:
– Dynamic voltage memory polarization
– Various characteristics, including mho, quad, lenticular
> Individual per-zone, per-element current supervision (FD)
> Multi-input phase comparator:
– additional ground directional supervision
– dynamic reactance supervision
> Transient overreach filtering/control
> Phase shift & magnitude compensation for distance applications
with power transformers
108 /
GE /
November 24, 2020
Distance Relay Desirable Attributes
> For improved flexibility, it is desirable to have the following
parameters settable on a per zone basis:
– Zero-sequence compensation
– Mutual zero-sequence compensation
– Maximum torque angle
– Blinders
– Directional angle
– Comparator limit angles (for lenticular characteristic)
– Overcurrent supervision
109 /
GE /
November 24, 2020
Distance Relay Desirable Attributes
> Additional functions
– Overcurrent elements (phase, neutral, ground, directional,
negative sequence, etc.)
– Breaker failure
– Automatic reclosing (single & three-pole)
– Sync check
– Under/over voltage elements
> Special functions
– Power swing detection
– Load encroachment
– Pilot schemes
110 /
GE /
November 24, 2020
111 /
GE /
November 24, 2020