Professional Documents
Culture Documents
- CTR = lp/Is
- Rated test winding current
- Nominal turn ratio (the error must not exceed ± 0.25%)
- Knee point voltage (kpv) at the maximum secondary turns;
Vk ≥ 2Vft
• Vft = maximum voltage developed across the relay circuit due to other groups of
fully-function CTs during a severe through-fault.
• Isc = maximum fault current through the secondary of the CTs, on a severe
through-fault.
• In this case, stability limit of the protection scheme define the minimum
voltage setting of the relay. This setting also will consider the safety margin
as the knee point voltage, Vk of the CTs is considered quite high Vk ≥ 2Vft
hence the saturation is possible under severe fault condition.
• Therefore, the level of Vft developed by the CTs may not be as high as
thought and when the relay is set at this voltage it will provide sufficient
stability.
• Note
• For this scheme, advisable to select low secondary current CT of 1A. reason:
-> to permit a lower relay setting for the voltage and the current trip coils.
• Stability level of protection -> auto improve when voltage across the relay
reduces.
• Sensitivity -> Ability of the scheme to detect the weakest internal fault.
• Stability -> Ability of the system to remain inoperative during healthy condition and also during the most severe
external fault. The system should be immune to
– Momentary voltage or
– Current transients and
– Normal harmonic contents in the circulating current.
Function of stab resistance Rst:To ensure that no spill current higher than the relay setting, I st will flow through the
relay circuit under a through-fault condition.
– Differential circuit will act like a high impedance path for this spill current, compared to the very low magnetizing impedance of
the saturated CT
Ire = Ic1 + Ic2 = (Isf2 – Im2) + (Isf1 –Im1) = Isf2 + Isf1 – 2Im
If IPf = minimum fault current through the primary (chosen on the basis of the rated full-
load current of the machine or the system being protected)required to trip the relay.
Also know as the minimum primary operating current (POC) of the scheme.
Ipf, In terms of the secondary = n x Isf
n = turn ratio of the CTs
Im = corresponding to the V,, to account for the most severe through fault
Ist = relay current setting, i.e. minimum spill current required to operate the relay
Then
Isf = Im + Ist
*During fault -> the p.f. is low, all these quantities may be considered in phase with each
other.
• In a GF protection scheme all the 3 CTs of all the feeders
being protected together will fall in parallel,
– a combined GF and phase fault protection scheme, only one third
of these CTs will fall in parallel.
• The CT in the faulty circuit must be able to draw enough
current to feed the magnetizing losses of all the CTs falling in
parallel and the relay pickup current, Ist .
• The sensitivity of the differential scheme can be expressed
as:
Isf = N x Im + Ist (N being the number of CTs falling in parallel)
and in terms of the primary Ipf = n(N x Im + Ist)
• Isf must be kept as low as possible to detect
even a small fault.
• High sensitivity can be achieved as:
– To have the CTs with a low Im
– To keep the number of CTs in parallel as small as
possible
– To protect individual feeders, rather than many
feeders together
• Relay -> only one current setting for all types of faults,
– recommended to keep around 20 - 40% of the rated current
of the system being protected.
– Reason: This setting -> sufficient to meet the CT’s
magnetizing current requirements and also trip the relay.
• GF scheme -> recommended to consider lower setting
to ensure effective detection.
– actual ground fault current may be larger than is being
detected by the relay due to a higher impedance of the
ground loop than assumed previously.
• Choose POC within 30% of the estimated GF
current (recommended by IEC 60255-6)
• The CTs are designed for the worst conditions of fault,
even when the scheme is designed to detect only a
ground fault.
• Phase to phase and ground fault -> severe unbalance.
The iron core of such CTs -> possess near-linear
magnetizing characteristics for the purpose of
compensating the fault level of the system being
protected.
– to achieve the magnitude of the fault in the secondary (15 to
20 times or more of Ir). In generators, it can increase up to 21.
Ir
• Secondary voltage of the CTs is defined by its
knee point voltage (kpv), Vk.
• Vk will depend upon
– the type of relay,
– its VA burden and
– the required stability of the system.
• It is common practice to make this at least twice the
relay setting voltage on the most severe through-
fault, Le. Vk ≥ 2Vft.
• Greater number of CTs means greater POC ->
A high POC may not be desirable, as it may
underprotect the system.
• It is advisable to apply the scheme individually
by dividing the system into more than one
circuit (example 15.6).
• 3 Suppressing system harmonics
• For instantaneous relay
– highly sensitive
– operate at low spill currents
• Instantaneous relay detects the residual current of the system,
due to third-harmonic components contained in the current, it
will operate.
• How To avoid operation of the relay under this condition? to
integrate a tuned filter at relay coil such as
– LC circuit to filter out the third-harmonic components.
– The capacitance of the filter circuit reduces a steep rising TRV (during a
momentary transient condition and protect the relay.
• 4 Limiting the peak voltage
High-impedance scheme -> can result in very high voltages across the CTs and the relay
especially during internal faults.
Voltage across the relay circuit must be limited to 3 kV in order to protect CTs and relay
(IEC60255-6).