Lecture Set 6:
Differential Protection
Pilot leads
Differential Protection
• The over-current relay connected in the spill path is
wired to trip the two circuit breakers on either side
of the equipment being protected.
• The following rule can be applied in order to trace
the currents in the circuit:
“ When current enters the dot mark on the primary
side of the CT the current must leave the similarly
marked dot mark on the secondary side.”
• For the operating condition of normal load flow, the
currents transformed by the two CTs, being equal in
magnitude as well as in phase, just circulate on the
secondary side.
• There is no tendency for the current to spill into the
over-current relay.
Differential Protection
If the protected equipment is either a 1 : 1 ratio
transformer or say a generator winding or a busbar, the
two currents on the primary side will be equal. Hence the
ratios of the two protective CTs will also be identical. The
CT secondary circuits are so connected that in case the
conditions are normal, the secondary currents simply
circulate through the 'pilot' leads connecting the two
secondary windings.
•
Simple Differential Protection
Through Fault Stability and Stability Ratio:
• The higher the stability ratio, the better is the ability of the
system to discriminate between external and internal faults.
• The stability ratio can be improved by improving the match
between the two CTs
Percentage Differential Protection
Solution to the problem:
The solution to this problem is the percentage differential
relay.
Torques produced in the relay: i. Operating ii. Restraining
The simple differential relay can be made more stable, if
somehow, a restraining torque proportional to the 'through
fault' current could be developed - the operating torque
still being proportional to the spill current.
Ia + Ib + Ic = Ileak = 0
Earth Leakage Protection (Three phase load)
Operation under fault condition:
During the earth leakage situation, the net mmf acting
on the core is (Ileak) ampere-turns. This causes a flux
to be produced. A voltage is induced in the pick-up
winding causing the OC relay connected across it to
operate.
Ia + Ib + Ic = Ileak