You are on page 1of 6

DCPR 47 – FIRE SAFETY

• TRAVEL DISTANCE :

• X= TRAVEL DISTANCE
WITHOUT WITH
SR. NO. USER
SPRINKLERS SPRINKLENRS
1. RESI., EDUCATIONAL & INSTITUTIONAL 22.50 30.00

BUSINESS, INDUSTRIAL, ASSEMBLY, MERCHANTILE,


2. 30.00
HAZARDOUS, STORAGE, STARRED CATEGORY HOTELS

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)


•REQUIREMENTS OF EXITS
•REGULATION 48

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)


DCPR 48(5) – EXIT REQUIREMENT
• ADDITIONAL STAIRCASE :

• A) FOR RESIDENTIAL BUILDINGS:


1) HEIGHT BETWEEN 32 MT. AND UP TO 70 MT.
ADDITIONAL STAIRCASE OF 1.50 MT REQUIRED IF
TRAVEL DISTANCE EXCEED SPECIFIED LIMITS OR
IF FLOOR AREA ON ANY FLOOR EXCEEDS 500.00 SQMTS.

2) HEIGHT > 70 m,


TWO ENCLOSED TYPE STAIRCASE OF MINM. 2.00 MT.

• B) FOR NON-RESIDENTIAL BLDGS. ABOVE 32 MT HEIGHT FOR INSTITUTIONAL AND FOR


SPECIAL BLDGS.
 TWO STAIRCASES SHALL BE PROVIDED.

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)


DCPR 48(8) – EXIT REQUIREMENT
• REFUGE AREA :
• REQUIRED FOR BLDGS. HAVING HT. > 32 MT.
• REQUIRED AREA = 4% OF HABITABLE FLOOR AREA. MAY BE ALLOWED 4.25%.
• EXCEES AREA SHALL BE COUNTED IN FSI.
• 1ST REFUGE AREA AT 24 MT ABOVE GR. LVL OR 1ST HABITABLE FLOOR IF PODIUM IS
PROPOSED WHICHEVER IS HIGHER.
• THEREAFTER AT EVERY 7TH HABITABLE FLOOR.

• FOR BLDGS. HT. UP TO 70 MT.


ALTERNATIVE FOR PROVIDING REFUGE AS CANTILEVER PROJECTIONS AT
ALTERNATE MID-LANDINGS OF THE STAIRCASE.

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)


DCPR 48(9) – EXIT REQUIREMENT
• CONTROLLED LOWERING DEVICE :
• FOR BLDGS. HAVING HT. > 70 MT.
• A) FIRE ESCAPE CHUTE –
 FIRE ESCAPE CHUTE SHAFTS/S REQUIRED FOR EVERY WING ADJACENT TO STAIRCASE.
 ACCESS AT EVERY FLOOR LEVEL FROM LOBBY AREA OR FROM STAIRCASE MID-
LANDING.
OR
• B) FIRE TOWER –
 SHALL BE PROVIDED AT LANDING/MID-LANDING LEVEL WITH SMOKE CHECK LOBBY
WITH FIREMAN LIFT BEING INTEGRAL PART OF THE STAIRCASE.
 REQUIRED ON THE EXTERNAL FACE OF THE BUILDING AS APPROVED BY CFO.

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)


DCPR 48(9) – EXIT REQUIREMNT
• FIRE TOWER (NBC):

SANCTIONED DEVELOPMENT PLAN 2034 PEATA(I)

You might also like