Professional Documents
Culture Documents
These requirements demand very high quantities of outside air along with significant treatment of
this ventilation air
Infection Control
• In a hospital environment, there tend to be high
concentrations of harmful micro-organisms. From an
infection control perspective, the primary objective of
hospital design is to place the patient at no risk for
infection while hospitalized. The special technical
demands include hygiene, reliability, safety and energy-
related issues.
Main routes responsible for
infections
• contact transmission
• droplet transmission (>5μm microorganisms)
• airborne transmission (<5μm microorganisms)
• Such as Covid-19 virus
1- Isolation rooms :
• The infected patient can contaminate the environment. A single room with appropriate air handling and
ventilation is particularly important to protect all residents .
• Types of isolation rooms:
• 1.Airborne infection isolation (AII): refers to the isolation of patients infected with organisms spread via
airborne droplet nuclei <5 μm in diameter.
• 2.Protective environment (PE): is a specialized area for patients who have undergone allogeneic
hematopoietic stem cell transplant (HSCT). The patients whose immune mechanisms are deficient
because of immunologic disorders
• 3.Combined (AII/PE) rooms: are for patients suffering from a weakened immune system who also have
an airborne commun-icable disease. In this type of room, HVAC issues involve a combination of both AII
room and PE room considerations.
• 4. Contact isolation rooms: are for patients having a communicable disease that is not airborne.
Isolation rooms
requirements:
a variable range temperature capability relative humidity of 30 ٪ minimum and For ventilation , a minimum of 6 ach is
of 70° F to 75° F [21.1° C to 23.9° C] 60 ٪ maximum. recommended , of which a minimum of
2 ach must be outdoor air.
Pressure To protect the patient
from airborne
transmission of any
inside ICU
infection ,the pressure
must be positive.
The exhaust air
• Exhaust air is to be discharged to the outdoors.
• special consideration may be required for air exhausted to the
outdoors, such as from ICUs in which patients with
pulmonary infection are treated. In this case, the exhaust air
must be filtered to reduce the chances of spreading infection.
4- Emergency
Department
•The emergency room is an area of
particular risk because immune-
compromised, undiagnosed contagious
patient populations, all types of patients
and the medical staff often coexist there.
The purposes of the HVAC system in an operating room (OR) are to minimize
infection, maintain staff comfort, and maintain patient comfort. As indicated in Table
1, the recommended air change per hour (ACH) value has been 15 to 25 for 40 years.
The current recommendation in the FGI Guidelines (AGI 2010) and ANSI/ASHRAE/
ASHE Standard 170-2008 is 20 ach supply air including 4 ach of outdoor air (20%
outdoor air). Note that 100% outdoor air systems have not been recommended since
the early 1980s, although until very recently the U.S. Veteran’s Administration has
required 100% outdoor air systems. Operating rooms must be designed for a positive
pressure differential of 0.01 in. of water [2.5 Pa]. As discussed above, this will require
a 200–400 cfm [94–189 L/s] offset. Although ANSI/ ASHRAE/ASHE Standard 170-2008
does not require continuous monitoring, various authorities having jurisdiction
(AHJs) frequently request or require monitoring of temperature, relative humidity
(RH), and dew point in ORs.
Table (1) Recent
History of HVAC
Standards for ORs
Classification of Surgeries
The surgical suite contains operating rooms as well as substerile rooms,
clean supply, sterile corridor, preoperative preparation, and postoperative
recovery care (postanesthesia care unit [PACU]). Common usage of the
term “OR” is often intended to include both the surgical room and these
support areas. In some hospitals, other spaces, such as locker rooms,
doctor ’s lounges, control desks, anesthesia workrooms, and even surgical
waiting areas, may be included in the general term. The OR special
environment, however, embraces only the restricted area of the surgical
suite. Surgeries may be classified as shown in Table 2.
Table (2)
Classifi cation
of Surgeries
Typical OR Layout
Figure 1 shows a schematic operating
room. As indicated, a typical internal
cooling load is 2 to 3 tons [7.0 to 10.6 kW].
With an air change rate of 20 and supply
air at 47°F to 50°F [8.3°C to 10.0°C], the
system can provide 6 to 7 tons [21.1 to
24.6 kW] of cooling, roughly twice the
actual load. Thus, in almost all operating
rooms, the required ACH drives the size of
the HVAC system, not the internal load.
Typical Operating
Room (OR) Requirements
Operating
Room Cooling
Loads
6- Outpatient clinic