OIL LINK UNIT/HIGH FUSE

UNIT

Oleh
RAIS BIN MAAT
Ketua Program Kejuruteraan
Elektrik
APA ITU OLU/HFU
• Satu pengasing (isolator) yang boleh
menyambung dan memutuskan bekalan
11kV secara manual sahaja
• Sebahagian daripada sistem gegelang sistem
pembahagian 11kV
• Menggunakan minyak sebagai interrupting
medium
• Tidak boleh membuka dan menutup jika
terdapat litar pintas
SUBSTATION

GEN MSB Tx RMU


OLU/HFU/OLU
RMU
C.BREAKER
RMU 11KV
Rating Unit 500 1000
kVA kVA
Rated voltage kV 12 12
Withstand voltage 1 minute kV rms 28 28
Impulse withstand voltage kV 75 75
Frequency Hz 50 50
Load Break Switch nos 2 2
Rated current disconnector A 630 630
Fuse switch nos 1 1
Rated current A 200 200
Fuse rating A 63 80
DISTRIBUTION TRANSFORMER
Rating Unit 500kVA 1000kVA
Voltage ratio at no load V 11/.433 11/.433
Off circuit tapping % 2.5, 5 2.5, 5
Withstand voltage 1 minute kV 28 28
Impulse withstand voltage kV 75 75
Frequency Hz 50 50
Vector group Dyn11 Dyn11
Type of cooling ONAN ONAN
L.V BOARD
Rating Unit 500kVA 1000kVA
Rated current A 800 1600
Rated voltage V 1000 1000
Incoming disconnector A 800 1600
Outgoing Fuseway at 20 C A 400 400
Outgoing fuse rating A 160 160
C.T ratio (class 0.2) 800/5A 1600/5A
MD meter nos 3 3
P.F meter nos 1 1
kWh meter nos 1 1
ENCLOSURE
Internal Arc testing IEC 1330 18.4 kA 1 sec
Clause 6
Temperature rise test IEC Class 10 enclosure
1330 Clause 4.1
Index Protection (IP) IP 35
Sound Level test 60 dBA
Material/Thickness Electro Galvanised
sheet/3.0mm
Base Frame Hot dipped Galvanised C-
Channel
OLU/HFU

Oil Link Unit


High Fuse Unit
OIL LINK UNIT
OIL
LINK
UNIT
HIGH
FUSE
UNIT
HIGH
FUSE
UNIT
HIGH
FUSE
UNIT
OLU
KEDUDUKAN OLU
• OFF
• ON
• BUSBAR EARTHED
• CABLE EARTH and LOCKED
KEDUDUKAN HFU
• ON
• OFF
• BUSBAR EARTHED
• FUSE EARTHED
• CABLE EARTHED
KEDUDUKAN KABEL
• ON
• OFF
• EARTHED
OLU ON
OLU ON
OLU ON
OLU OFF
OLU OFF
OLU OFF
CABLE EARTH
SWITCH OFF –
CABLE IS NOT
EARTHED
CABLE EARTH
SWITCH ON –
CABLE IS
EARTHED
CABLE EARTHED
HIGH FUSE UNIT
• Consist of a switch disconnector or a circuit
breaker to connect and disconnect supply
from busbar
• Followed by 3 nos HT fuses for overcurrent
protection for transformer
• Followed by HT cable to be connected to
transformer
POSITIONS OF HFU
• ON
• OFF
• EARTHED
• FUSE EARTH OFF
• FUSE EARTH ON
CABLE EARTH,
FUSE EARTH
CABLE OFF,
FUSE EARTHED
SWITCH OFF,
CABLE ON,
CABLE IS
NOT EARTH