You are on page 1of 92

Full Digital Voice Alarm System

SX-2000

SX-2000
Reggane Project Training
SX-2000 Reggane Project
1
Training
Agenda

• Introduction
• Components
• Installation & Startup
• Design
• Programming

SX-2000 Reggane Project


TOA Electronics GmbH 2
Training
Introduction
Definition: De-centrlized network based audio management system
integrated Public address and voice alarm

• Air ports
• Hi- rising building
Dedicated Network
• Complex shopping centers
• Factories
• Sub-way ( rail stations)
• Complex residential
compunds

SX-2000 Reggane Project


TOA Electronics GmbH 3
Training
Introduction
Product Features
• 20 bus system ( 16 Audio + 4
Emergency)
• 64 inputs + 32 local
• 256 zone
• 32 EV messages
• 64 remote microphones
• 512 Priority levels
• 14 16 control inputs
• 1416 control outputs
• 1000 x 32 event log
• 100 x 32 fault log

SX-2000 Reggane Project


TOA Electronics GmbH 4
Training
Agenda

• Introduction
• Components
• Installation & Startup
• System Design
• System Programming

SX-2000 Reggane Project


TOA Electronics GmbH 5
Training
System Components
Components overview
BGM
SX-2000SM

Switch

Inputs
Module SX-2100AI VP/DA
Amps.
1 1

. . .

. . .
8
SX-2000AO 8

RM-200SF SX-2000CI VP-Amps.


9 9

...

. . .
16

SX-2100AO Stby.
16

RM-200SA
SX-2000CO

SX-2000 Reggane Project


TOA Electronics GmbH 6
Training
System Components
System Manager (1/3)

SX-2000SM system controller


• Contains the system configuration setting
• 1 unit is required per system
• 8 control inputs ”Monitored”
• 8 control outputs (NO & NC)
• Status out (CPU/General fault NO & NC)
• LAN Connection
• Analogue audio link

SX-2000 Reggane Project


TOA Electronics GmbH 7
Training
System Components
System Manager (2/3)

System indications System control


• Network status indication • Fault acknowledge
• Operation mode • Fault rest
• Fault status • Lamp test
• Buzzer fault

SX-2000 Reggane Project


TOA Electronics GmbH 8
Training
System Components
System Manager (2/3)
DIP Switch
RESET USB CF-CARD ON (SETTING)
ACCESS

12345678

Behind the protected cover


• Reset press < 1 sec.
• USB Firmware update
• Access LED reading/writing CF-Card indication
• CF-Card contains system setting, audio and log data
• DIP-Switch setting 1 2
ON Enable Log data Enable access to
written on CF Card data card

OFF Disable Disable  Eject


SX-2000 Reggane Project
TOA Electronics GmbH 9
Training
System Components
System Manager (3/3)
DC output (24 VDC, 100 mA)
C4 C3 C2 C1 DC OUT C5 C4 C3 C2 C1
ANALOG LINK SX LINK
1 1
OUT2 OUT1 B A LAN
STATUS
DS LINK
OUTPUT
2 2

C8 C7 C6 C5 LAMP RES ACK C8 C7 C6

Dual DC Links Status Control control Analog SX LINK + LAN


power to output outputs inputs bypass MAC address connection +
input 2 DS (CPU & outputs MAC address
general Lamp test, Reset,
fault) acknowledge input
SX-2000SM Rear
• 8 control inputs with surveillance
• 8 control outputs (switch-over contacts: NO and NC)
• Control inputs for Reset, Acknowledge and lamp test
• DC power output (24 VDC, 100 mA)
• LAN port
• System bus link ports (A and B)
• 2 Analogue bypass ports
SX-2000 Reggane Project
TOA Electronics GmbH 10
Training
System Components
Audio Input Unit (1/6)

SX-2100AI Audio Input Matrix


• Up to 8 units, 4 input card per each unit
• 8 channel w/ volume control and ON/OFF button
• 16 control Input / 16 control output
• Audio level display per channel
• Fluorescent display ( Emergency, Fault, etc.)
• Audio Monitor w/volume control and ON/OFF button
• Four free programmable function keys

SX-2000 Reggane Project


TOA Electronics GmbH 11
Training
System Components
Audio Input Unit (2/6)
Front Panel Status
indication:
Function buttons Display for text, - power
Monitor for BGM pattern level meter and Menu - CPU off
speaker or gen. broadcast other indications buttons - standby

Protection cover Channel on/off button Channel Monitor


or for activation of volume volume,
general broadcast pattern control on/off
(on/off switch)

SX-2000 Reggane Project


TOA Electronics GmbH 12
Training
System Components
Audio Input Unit (3/6)
Rear Panel

16 control inputs
16 control outputs

DC 4 module slots Analogue link SX link


input (input & output) A+B

SX-2000 Reggane Project


TOA Electronics GmbH 13
Training
System Components
Audio Input Unit (4/6)
SX-200RM Remote Microphone Interface
• For 2 remote microphones
• 2 RJ45 connectors
• Power supplied through cable

SX-2000 Reggane Project


TOA Electronics GmbH 14
Training
System Components
Audio Input Unit (5/6)
2-Channel Input Module
D-921F
• 24 bit AD converter
• Setting by software
• Input level D-921E
• Phantom power
• D-921F w/ XLR
• D-921E w/screw terminal block

SX-2000 Reggane Project


TOA Electronics GmbH 15
Training
System Components
Audio Output Unit (1/4)

SX-2000AO Audio output Matrix


• Up to 32 units
• 8 balanced Line outputs
• Emergency line w/ control input
• 8 channel w/ volume control and ON/OFF button
• 8 control Input / 8 control output
• Fluorescent display ( Emergency, Fault, etc.)
• Audio Monitor w/volume control and ON/OFF button
• Four free programmable function keys
SX-2000 Reggane Project
TOA Electronics GmbH 16
Training
System Components
Audio Output Unit (2/4)
Rear Panel

DC
power 8 control 8 control Line CI/CO Emergency Line
input outputs inputs outputs link with control input
LINE OUTPUT
4 3 2 1

CI/CO LINK EMERGENCY EMERGENCY CUTOFF


LINE INPUT DC 24V INPUT

8 7 6 5

Earth Analog SX bus


connector link link

SX-2000 Reggane Project


TOA Electronics GmbH 17
Training
System Components
Audio Output Unit (3/4)

SX-2100AO Audio Input Matrix


• Up to 32 units
• 8 balanced output for VP amplifiers
• Surveillance for 8 speaker lines /8 zones amplifier /1standby amplifier
• 2 local audio input and control (for local broadcast)
• 8 channel w/ volume control and ON/OFF button
• 8 control Input /8 control output
• Audio level display per channel
• Fluorescent display ( Emergency, Fault, etc.)
SX-2000 Reggane Project
TOA Electronics GmbH 18
Training
System Components
Audio Output Unit (4/4)
Rear Panel
DC
power 8 control 8 control 2 links Standby Link to 8 zone
input outputs inputs to DS amp out amplifiers

Earth Standby 100-volt amplifier CI/CO Analog SX bus Local


connector amp in and zone connection link link link inputs
(100V)

SX-2000 Reggane Project


TOA Electronics GmbH 19
Training
System Components
Audio Input / Output (1/2)
Front Panel Display (AI-AO) Key lock Only AO units:
General fault Text display when volume and 1: SX-2000CI
- system failure Communication Information of channel elements 2: SX-2000CO
- configuration failure function buttons are locked connected
- communication

COM
FAULT KEY LOCK
EMERGENCY
FADER

LEVEL LEV
EL

Level meter Level meter Level Emergency Only Monitor Monitor


shows shows meter mode SX-2100AO: level on
fader level active local input meter
position level

SX-2000 Reggane Project


TOA Electronics GmbH 20
Training
System Components
Audio Input / Output (2/2)
USB RUN ID NUMBER RESET SETTING
ON

A B 12345678

Behind the protected cover


• USB Firmware update

1
RUN Indication

ON Disable front panel output
Unit ID setting switch volume control and
• Reset press < 1 sec. channel key operation
• DIP-Switch setting OFF

SX-2000 Reggane Project


TOA Electronics GmbH 21
Training
System Components
Control Input (1/2)

SX-2000CI Front Panel


• Up to 32 units
• 32 Monitored control inputs
• 32 Front LED indicators

SX-2000 Reggane Project


TOA Electronics GmbH 22
Training
System Components
Control Input (2/2)
Rear Panel
Link from
Link to SX-2000AO
DC power SX-2000CO SX-2100AO
input 32 control inputs (through) SX-2000CO

Functional 24 VDC Through


Earth output enable switch
connector (100 mA)

SX-2000 Reggane Project


TOA Electronics GmbH 23
Training
System Components
Control Input
USB RUN ID NUMBER RESET SETTING
ON

12345678

Behind the protected cover


• USB Firmware update
• RUN Indication
• Unit ID Not used
• Reset press < 1 sec.
• DIP-Switch Not used

SX-2000 Reggane Project


TOA Electronics GmbH 24
Training
System Components
Remote Microphone (2/4)
RM-200SA remote microphone

Gooseneck microphone Removable labels


allow each language

Selection indicators

Covered emergency button

Status indicators
Talk button
13 free programmable buttons

SX-2000 Reggane Project


TOA Electronics GmbH 25
Training
System Components
Remote Microphone (3/4)
RM-200SA rear panel

USB
connector
(not used) Setting DIP switch

DC POWER IN
LINK SP MIC
EXTERNAL
MIC IN
Extension
24V

connector
USB RM LINK for RM-210

DC power RJ45 link External microphone input jack


input jack connector
Microphone volume control
Speaker volume control

SX-2000 Reggane Project


TOA Electronics GmbH 26
Training
System Components
Remote Microphone (4/4)
RM-210 Extension unit

• 10 Functions keys
• 4 Units max. for RM-200SA
• 5 Units max. for RM-200SF

SX-2000 Reggane Project


TOA Electronics GmbH 27
Training
System Components
Power Amplifier
• VP-2122 Power Amplifier Overheat
Green: on
2x120Watts indicator
Red: standby

• VP-2241Power Amplifier
1x240Watts

• VP-200VX Power Amplifier


Input module

SX-2000 Reggane Project


TOA Electronics GmbH 28
Training
System Components
Power Supply
• VX-200PS power supply unit

• VX-2000PF Power supply frame

• Drive up to 420W VP
amplifier
• 2 DC output
• 2 fuses
• 2 LED Indicator

SX-2000 Reggane Project


TOA Electronics GmbH 29
Training
Agenda

• Introduction
• Components
• Installation & Startup
• Design
• Programming

SX-2000 Reggane Project


TOA Electronics GmbH 30
Training
Installation
PFP-1
Rack Configuration VP-2064

VP-2122
PFP-1
VP-2241

VP-2241
PFP-1
SX-2000SM
SX-2000AI
SX-2000/2100 AO
SX-2000CO
SX-2000CI

VX-2000PF

PFP-1
VX-2000DS
PFP-1

5U for Battery space

SX-2000 Reggane Project


TOA Electronics GmbH 31
Training
Installation
Power connection (1/3) No redundancy
4 3 2 1

Parallel connection to DC input


8 7 6 5

Any
SX-2000
unit

VX-2000DS

SX-2000 Reggane Project


TOA Electronics GmbH 32
Training
Installation
Zone Amplifier (2/3) SX-2100AO
8 VP-2000 series amplifiers can be connected via Cat5/RJ45 cable

Zone amplifier outputs

SX-2100AO

Zone amplifier inputs (100V) Zone

VP-2000 series amplifier

SX-2000 Reggane Project


TOA Electronics GmbH 33
Training
Installation
Control Input/output Connection
SX-2000CI, one can be connected per SX-2100

SX-2100AO

CI/CO LINK
THROUGH DATA SX-2000CI

SX-2000 Reggane Project


TOA Electronics GmbH 34
Training
Installation
Control Input terminals(1/5)
SX-2000SM
• 8 Monitored control Inputs
• DC OUT C5 C4 C3 C2 C1
Lamp test
• Fault Acknowledge
• Fault Rest

LAMP RES ACK C8 C7 C6

SX-2000 Reggane Project


TOA Electronics GmbH 35
Training
Installation
Control Input Connection (2/5)
SX-2100AI
• 16 control Inputs
• Internal driven (Left)
• External driven (Right)

Power +
supply –

With external power supply


SX-2000 Reggane Project
TOA Electronics GmbH 36
Training
Installation
Control Input Connection (3/5)
SX-2000AO / SX-2100AO
• 8 control Inputs
• Internal driven (Left)
• External driven (Right)

Power +
supply –

With external power supply

SX-2000 Reggane Project


TOA Electronics GmbH 37
Training
Installation
Control Input Connection (4/5)
SX-2000CI
• 32 control Inputs

SX-2000 Reggane Project


TOA Electronics GmbH 38
Training
Installation
Control Input Connection (5/5)
Monitored control Inputs SX-2000SM / SX-2000CI
• Recommended cable , twisted pair
• Up to 10 meters
10 kΩ

Control input 10 kΩ

SX-2000 Reggane Project


TOA Electronics GmbH 39
Training
Installation
Control Output

• Dry relay contacts, 40VDC, 2 – 300mA


• Normally closed or normally opened
• SX-2000SM
• SX-2100AI, 16
• SX-2100AO, 8

SX-2000 Reggane Project


TOA Electronics GmbH 40
Training
Installation
Remote Microphone
RM-200SA & RM-200SF
• Each remote microphone must be connected to a single port
• Cable length about 800 meter.

SX-2000 Reggane Project


TOA Electronics GmbH 41
Training
Installation
Remote Microphone

RM-200SA connection
Direct connection

SX-2000 Reggane Project


TOA Electronics GmbH 42
Training
Installation
SX-Network (1/9)
Switch recommendation
• Managed switch
• The Switch must provide the Spanning Tree Protocol (STP; IEEE
802.1D) or Rapid Spanning Tree Protocol (RSTP; IEEE 802.w)
• For long distances (> 100 m) it should provide a fibber optic link
• It should have a DC power input with a range of 20 - 40 V DC To be
powered by the SX-2000 system including battery backup

Network recommendation
• Physical separated from other network
• Data should not go through than more 7 hops

SX-2000 Reggane Project


TOA Electronics GmbH 43
Training
Installation
SX-Network (3/9)
Non-Redundant Network with redundant Unit Connection
• Connect Link A and B to the switches
• Single connection between switches

SWITCH

Location 1

SWITCH

Location 2

SX-2000 Reggane Project


TOA Electronics GmbH 44
Training
Installation
SX-Network (4/9)
Full Redundant Network 1
• Connect Link A and B to the switches
• Double connection between switches

SWITCH

Location 1

SWITCH

Location 2

SX-2000 Reggane Project


TOA Electronics GmbH 45
Training
Installation
SX-Network (5/9)
Full Redundant Network 2 (recovery when Switch fails)
• Connect Link A and B to separate switches
• Single connection between the switches where the SM is connected to

SWITCH SWITCH

Location 1

SWITCH SWITCH

Location 2

SX-2000 Reggane Project


TOA Electronics GmbH 46
Training
Startup
Impedance Initialisation (1/3)
• Open the security cover of the SX-2100AO
• Set Dip switch no. 8 to ON

USB RUN ID NUMBER RESETON SETTING

12345678

SX-2000 Reggane Project


TOA Electronics GmbH 47
Training
Startup
Impedance Initialisation (2/3)

Menu item no. 4 for impedance is now available

All or single zones


can be initialised

Open line range setting

Short circuit range setting

SX-2000 Reggane Project


TOA Electronics GmbH 48
Training
Startup
Impedance Initialisation (3/3)
Adjustable Tolerance Range
• Short circuit, 5% … 50% (default) of nominal impedance

• Line Break, 101% … 200% (default) … 800% of nominal


impedance

Short circuit setting range Open line setting range

minimum range Default range

SX-2000 Reggane Project


TOA Electronics GmbH 49
Training
Startup
Volume Adjustment
Volume Setting by the Front Panel Volume Controls
• Input volume: all except emergency microphones can be set

• Output volume: all can be set, will be bypassed in emergency


mode
• After setting, set dip-switch 1 to on, to inhibit access to front
panel volume control during operation

SX-2000 Reggane Project


TOA Electronics GmbH 50
Training
Agenda

• Introduction
• Components
• Installation & Operation
• Design
• Programming

SX-2000 Reggane Project


TOA Electronics GmbH 51
Training
Desgin
Supplementary Tool
Fill in yellow blanks.

Equipment
o l
o
• System Manager (SM) Units Modules Q'ty


T
Power supply for SX-
Audio Input (AI) SX-2000SM   1 2000SM

y
  0 VX-2000DS no. Terminal no.
• Remote Microphone (RM)
r
SX-200RM 0 Basic connection (A)
SX-2100AI D-921E/F 0

a
   
• Audio Output (AO)
t
D-922E/F 0 Redundant connection (B)
D-936R 0    

n
• Contol Input /Output (CICO) RM-200SF   0 DC connection check:

e
RM-200SA   0 Connect basic power supply
• VP RM-210
SX-2000AO
  0
  0

m
SX-2100AO   0

e
SX-2000CI   0

l
SX-2000CO   0

p
VP-2064   0
VP-2122   0

p
VP-2241   0
VP-2421   0

S
    VP-200VX 0
  0
VX-2000PF
VX-200PS 0
VX-2000DS   0
   

Version 1.0

SX-2000 Reggane Project


TOA Electronics GmbH 52
Training
Agenda

• Introduction
• Components
• Installation & Operation
• Design
• Programing

SX-2000 Reggane Project


TOA Electronics GmbH 53
Training
Design

SX-2000 Reggane Project


TOA Electronics GmbH 54
Training
System Programing
Authentication

Default superuser password is: Superuser

SX-2000 Reggane Project


TOA Electronics GmbH 55
Training
System Programing
Basic Setting

SX-2000 Reggane Project


TOA Electronics GmbH 56
Training
System Programing
System settings

SX-2000 Reggane Project


TOA Electronics GmbH 57
Training
System Programing
System settings (System manager)

SX-2000 Reggane Project


TOA Electronics GmbH 58
Training
System Programing
System settings (AI-upper)

SX-2000 Reggane Project


TOA Electronics GmbH 59
Training
System Programing
System settings (AI-lower)

SX-2000 Reggane Project


TOA Electronics GmbH 60
Training
System Programing
System settings (AO-upper)

SX-2000 Reggane Project


TOA Electronics GmbH 61
Training
System Programing
System settings (AO-lower)

SX-2000 Reggane Project


TOA Electronics GmbH 62
Training
System Programing
System settings (RM-200SA)

SX-2000 Reggane Project


TOA Electronics GmbH 63
Training
System Programing
System settings (RM-200SF)

SX-2000 Reggane Project


TOA Electronics GmbH 64
Training
System Programing
System settings (CI)

SX-2000 Reggane Project


TOA Electronics GmbH 65
Training
System Programing
System settings (CO)

SX-2000 Reggane Project


TOA Electronics GmbH 66
Training
System Programing
Surveillance (1/2)

SX-2000 Reggane Project


TOA Electronics GmbH 67
Training
System Programing
Surveillance (2/2)

SX-2000 Reggane Project


TOA Electronics GmbH 68
Training
System Programing
System settings (Priority)

SX-2000 Reggane Project


TOA Electronics GmbH 69
Training
System Programing
Pattern setting (Zone)

SX-2000 Reggane Project


TOA Electronics GmbH 70
Training
System Programing
Pattern setting (BGM)

SX-2000 Reggane Project


TOA Electronics GmbH 71
Training
System Programing
Pattern setting (General Broadcasting)

SX-2000 Reggane Project


TOA Electronics GmbH 72
Training
System Programing
Pattern setting (Control output)

SX-2000 Reggane Project


TOA Electronics GmbH 73
Training
System Programing
Pattern setting (Emergency Sequence)

SX-2000 Reggane Project


TOA Electronics GmbH 74
Training
System Programing
Pattern setting (Emergency broadcast)

SX-2000 Reggane Project


TOA Electronics GmbH 75
Training
System Programing
Pattern setting (Failure output)

SX-2000 Reggane Project


TOA Electronics GmbH 76
Training
System Programing
Event setting (System event)

SX-2000 Reggane Project


TOA Electronics GmbH 77
Training
System Programing
Event setting (SM event)

SX-2000 Reggane Project


TOA Electronics GmbH 78
Training
System Programing
Event setting (AI event-upper)

SX-2000 Reggane Project


TOA Electronics GmbH 79
Training
System Programing
Event setting (AI event-lower)

SX-2000 Reggane Project


TOA Electronics GmbH 80
Training
System Programing
Event setting (AO event-upper)

SX-2000 Reggane Project


TOA Electronics GmbH 81
Training
System Programing
Event setting (AO event-lower)

SX-2000 Reggane Project


TOA Electronics GmbH 82
Training
System Programing
Event setting (RM-200S(A))

SX-2000 Reggane Project


TOA Electronics GmbH 83
Training
System Programing
Event setting (RM-200SF)

SX-2000 Reggane Project


TOA Electronics GmbH 84
Training
System Programing
Event setting (CI event)

SX-2000 Reggane Project


TOA Electronics GmbH 85
Training
System Programing
Utility (Logfile /Logonline)

SX-2000 Reggane Project


TOA Electronics GmbH 86
Training
System Programing
Utility (System status)

SX-2000 Reggane Project


TOA Electronics GmbH 87
Training
System Programing
Utility (Audio in/out status)

SX-2000 Reggane Project


TOA Electronics GmbH 88
Training
System Programing
Utility (Control in/out status)

SX-2000 Reggane Project


TOA Electronics GmbH 89
Training
System Programing
Menu (File)

• Setting Data Export into CSV


• RM Label Data Export

TOA Electronics GmbH 90


System Programing
Menu (Communication)

Direct Access

• to Settings
• Log file
• configuration

SX-2000 Reggane Project


TOA Electronics GmbH 91
Training
Thank you
for your attention

SX-2000 Reggane Project


TOA Electronics GmbH 92