Transformator

PLTU Jabar 2
Pelabuhan Ratu

Pemeliharaan Listrik
UBOH PLTU Jabar 2 Pelabuhan Ratu
Tegangan Operasi (AC) PLTU Jabar 2
Pelabuhan Ratu
 150 kV
 20 kV
 6,3 kV
 400 V
 230 V
Jenis – Jenis Transformator
 Transformator Tenaga
 Transformator Tegangan (PT)
 Transformator Arus (CT)
Tipe - Tipe Transformator
 Oil Immersed Transformer
 GT, UAT, SST
 Dry Type Transformer
 Trafo trafo 6.3 kV/ 400V
Pemakaian Sendiri (PS)
PLTU Jabar 2 Pelabuhan Ratu
Transformator Pada PLTU Jabar 2
Palabuhanratu
 Main Transformer (GT) 20kV/150kV
Transformator Pada PLTU Jabar 2
Palabuhanratu
 Unit Auxiliary Transformer (UAT) 20kV/6.3kV
Transformator Pada PLTU Jabar 2
Palabuhanratu
 Station Service Transformer 150kV/6.3kV
Transformator Pada PLTU Jabar 2
Palabuhanratu
 6,3 kV/400V auxiliary transformer
Kode Model Transformer
1. Untuk fasa:
 S : 3 fasa
 D : 1 fasa
 GT
2. Tipe pendingin :
 F : air cooling
SFPZ-420000/157.5TH
 FP : oil and air cooling
 C : Dry type
- : oil cooling

3. Kumparan transformator :
-
 UAT
: double winding
 S : three winding
SFF10-45000/20W3
4. Material kumparan :
- : tembaga
 L : aluminium
 G : alumanum

5. Mode tegangan regulasi :


 Auxiliary transformer
SCB10-2000/6
- : no load tap changer
 Z : on load tap changer
Proteksi
Main Transformer & UAT
 87G: differential protection for generator
 51G: Over-current protection
 46G: negative phase sequence over-current protection
 59G: Over-voltage protection
 60G: Voltage balance protection
 81G: Under/over frequency protection
 78G: Pole slipping protection
 32R: Reverse power protection
 40G: Field failure protection
 64G: Stator earth fault protection
 21G: Back up impedance protection
 59/81: Over-fluxing protection
 87L: differential protection for branch
 67: Distance protection for transmission line
 87B: Differential protection for busbar
 50BF: Breaker failure protection
 87T: Differential protection for GT
 51N: Earth fault protection for GT
 64REF: Restricted earth fault
 63: Bucholz protection
 63P: Pressure relief
 49: Temperature
 87U: Differential protection for UAT
 95U: Voltage controlled IDMT over-current for UAT
 51U: Over-current with IDMT for branch
 51NU: Earth fault protection for branch
Proteksi
Station Service Transformer (SST)
 87L: Differential protection for branch
 67: Distance protection for transmission line
 87B: Differential protection for busbar
 50BF: Breaker failure protection
 87T: Differential protection
 64REF: Restricted earth fault
 95T: Voltage controlled IDMT over-current
 51N: Earth fault protection
 63: Bucholz protection
 63P: Pressure Relief
 49: Temperature protection
 25: Synchronizing device
Proteksi
Transformator 6,3kV/400V
 50: Instantaneous Over-current
 46: Asymetric Overload
 51: Over-current with IDMT
 11: Lose of phase
 16: 3 phase fuse protection
 51N: Earth fault with IDMT
Hatur NuHun… ..… ^_^