5 to 2 MW solar
KUMBHA
5 Y Connectors
7 MC4 Connectors
14 Control cable
23 Earthing strips
24 Lightening Arrestors
25 LA Down conductor
26 Conduit pipe
b Ultasonic Anemometer
c Panel Temp. Sensor
d Ambient Temp. Sensor
Fire Detection & Protection System in MCR /
30 Extinguishers
a Sand Buckets
Cable glands
Cable glands
38
39
Cable Lugs
40 Cable Ties
1 Topographical survey
2 Soil testing/Boreholes/Pull Out test
3 Foundations for
MCR
Transformer
Inverters
ACCB's
Switchgear
4 Module Cleaning System
Underground tank for Water Storage
Piping
Drainage sytem
5 Perimeter lighting foundation works
LED lights
GI Poles
6 Security Room/Cabin
7 Cable trenches
Note:
a.) The above mentioned quantities of AC Cables are based on tentative location of inverter actual quanti
Project -0.5 to 2 MW solar projects in Maharashtra for CEL
KUMBHARI-921.60 KW BOQ
ents clearly states that it’s a NO DEVIATION tender,deviation either technical or commercial will lead to cancellation/rejection.
I/P- 1000V DC, 15Amp I/P- 1000V DC, 15Amp (For 6 sq mm cable )
O/P-1000V DC, 30 Amp O/P-1000V DC, 30 Amp (6 sq mm cable)
MC4 Pair, 1000V DC, 30Amp (For 6 sq mm MC4 Pair, 1000V DC, 30Amp, Material should be same as use at
cable ) SMU side
1C, solar frade, Copper, 1.1 KV, electron beam XLPO outer sheath,
Black color, DC cables complying to TUV 2PfG 1169/09.07 for
1.1 Kv, 1C 6sqmm Cu solar cable service life expectency of 25 years. DC cable for positive current
should have RED line on black outer sheath. Flame retardent, UV
resistent
1C, Aluminium, 1.1 KV, XLPE. Cable size decision based on full
1.1 Kv 1C 240 sqmm Al Ar XLPE Cable
power voltage drop from Solar Panels to Inverter below 1.5%.
1C, Aluminium, 1.1 KV, XLPE. Cable size decision based on full
1.1 Kv 1C 240 sqmm Al Ar XLPE Cable power voltage drop from Inverter to Transformer below 2.0%.
25x3 mm GI strip
50x6 mm GI strip
25 SQ mm Cu GREEN EARTHING CABLE
ESE type as per NFC 17-102, three zone protection level, three
107 Meter radius LA
earth pits per LA
400 sq mm Al coated ring type Lugs should tinned Copper, solder less crimping. Ferruls should be
weather resistent
95 sq mm Cu coated ring type
Outdoor, UV-resistent
Special requirement
All Buildings with RCC frame strucutre & brick wall partition, M25
concrete
All M25 grade
Pre-fab strucutre
All RCC trenches, 100mm wall & base slab for 750mm deep
trench & 150mm for > 750mm depth
External trench min. 100mm above FGL to avoid rain water filling
in trench.
Transformer Pit should be minimum 1/3rd of transformer Oil
volume, to be filled with granite gravel
of 40mm size with 300mm free space above gravel fill.
Fire barrier Wall (RCC min. 230mm thick or masonry min. 300mm
thick)
1.8m height fencing with Main gate and 2nd gate.
Insurance Certificate for warehouse to be submitted before start
of I&C work.
To house Inverter, VCB, UPS, SCADA, Auxillary Panel and space for
testing, operations & maintenance, spare store and O&M staff
es are based on tentative location of inverter actual quantity may vary as per the location of inverter transformer and HT Panel.
to cancellation/rejection.
151 Nos.
8 Nos.
1210 Meter
277 Meter
18 Meter
20 Meter
60 Meter
145 Meter
10 Meter
1 set
1 set
1210 Meter
120 Meter
5 Meter
1 Nos.
40 Meter
1000 Meter
900 Meter
120 Nos.
60 Nos.
220 Nos.
85 Nos.
90 Nos.
1 Set
1 Set
16
12
2
32 Nos.
24 Nos.
6 Nos.
mer and HT Panel.