SECTION 1- SCOPE
General
General
General
General
1.1.3 The purchaser will specify SI dimensions or US
customary dimensions.
1.1.6 Appendix B: Design and construction of foundations
under flat bottom oil storage tanks.
1.1.7 Appendix C: Requirements for pan-type, pontoon-
type and double deck- type external floating roofs.
1.1.12 Appendix H: Requirements for an internal floating
roof in a tank that has a fixed roof at the top of the
tank shell.
General
General
General
General
1.1.21 Appendix R: Load Equations
1.1.22 Appendix S: Requirements for the construction of
austenitic stainless steel tanks.
1.1.23 Appendix T: Requirements for inspection
(summary).
1.1.24 Appendix U: Requirements for UT examination, in
lieu of radiography.
1.1.25 Appendix V: Requirements for external pressure
(vacuum).
1.2 Limitations
General
SECTION 2: MATERIALS
SECTION 3: DESIGN
3.10 Roofs
3.10 Roofs
3.10.2.2 Roof plates - minimum nominal “t” of 3/16” (7.65 lbs.
per sq. ft., 0.180” plate or 7 gauge sheet).
NOTE: Self-supported roofs may require thicker plate.
3.10.2.3 Supported cone roof plates shall not be attached to the
supporting members, unless approved by the purchaser.
3.10.2.4 Internal-External structural members must have a
minimum nominal “t” (in any component) of 0.17”.
3.10 Roofs
3.10 Roofs
3.10.2.6 Frangible roof general information.
3.10.2.7 Roof plates may be stiffened by welded sections, but
not connected to girders-rafters.
3.10.4.1 Supported cone roofs slope 3/4’ in 12’ (or greater).
3.10.4.4 Rafters shall be spaced so that in the outer ring,
their centers are not more than 2 ft. (6.28 feet),
measured along the circumference. The maximum
spacing for inner ring rafters (i.e., ‘Jack” rafters) is
5.5 feet.
3.10 Roofs
3.10.4.5 Roof Columns
Structural shapes or steel pipe is acceptable. If pipe, it must
be sealed (or provisions for draining or venting made).
3.10.4.6 Rafter and Column Base Clips
a. Outer row rafter clips - welded to tank shell.
b. Column-base clip guides - welded to tank bottom to
prevent lateral shift.
c. Other structural attachments - welded, bolted or
riveted.
SECTION 4- FABRICATION
SECTION 5- ERECTION
5.2.2 Bottoms
5.2.3 Shells
5.2.3.1 Misalignment in completed vertical joints over 5/8”
thick, shall not exceed 10% of plate “t”, with a maximum
of 0.125”. Misalignment in completed vertical joints 5 /
8” thick and less thick shall not be greater than 0.06”.
5.2.3.3 The reverse side of double-welded joints (prior to the
application of the first bead to the second side), must be
cleaned by chipping, grinding or melting out.
5.2.3.4 Joints exceeding 1 1 / 2” base metal “t”
No pass over 3/4” thick is permitted.
5.2.3 Shells
5.2.3.5 Requirement for a procedure that minimizes the potential
for underbead cracking, in group IV through VI material.
5.2.3.6 After any stress relief (but before hydro), welds attaching
nozzles, manways and cleanout openings shall be visually
and magnetic particle or die penetrant tested.
5.2.4.1 Shell-to-bottom welds, inside, shall be checked by visual
and any of the following: magnetic particle, PT solvent, PT
water washable, diesel test or right angle vacuum box.
5.2.3 Shells
Remember………”In
Service” Storage Tanks
governing Standard is
API 653!
We only use API 650 when
instructed to do so…….
Remember………”In
Service” Storage Tanks
governing Standard is
API 653!
We only use ASME sec V
when instructed to do so…….
SECTION 7- WELDING
PROCEDURE/QUALIFICATIONS
H.1 Scope
Subsection 3.10 of this standard is applicable
except as modified in this appendix.
H.3 Materials
H.3.2 Steel
H.3.3 Aluminum
H.3.4 Stainless Steel
Same general provisions as for external floating roofs.
13. Per API 650, external floating roof deck plates having
support leg or other rigid penetrations closer than
____ inches to lap weld seams must be full fillet
welded not less than 2 inches on 10 inch centers.
a. 6
b. 12
c. 14
d. 18