SINAMICS G120X

Technical Slides
Unrestricted © Siemens 2020 siemens.com/sinamics-g120x

Unrestricted © Siemens 2020


Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 2
SINAMICS G120X: The seamless Pump & Fan drive
presents a solution for the Infrastructure market

The new SINAMICS G120X System is developed with


enhanced features for the water industry and HVAC
applications in the midrange segment.

The G120X offers wide power range from 0.75 to 630 kW /

G120X
1 to 700HP with seamless voltage classes

The optimum solution due to its out-of-the-box concept,


fast setup time and extremely simple operation
FSC, IP20
UL open type

Unrestricted © Siemens 2020


Page 3
SINAMICS G120X offers comprehensive functionality
and creates added value

Feature / Function Benefits


“Out-of-the-box” - Complete drive • Reduced cost and efforts for:
delivered together ready to switch on  ordering (1 article number), delivery
from 0.75kW - 630kW / 1- 700 HP and commissioning
Dedicated user interface and P&F
• Faster commissioning with improved
functions with optimized SAM 
user friendly setup
(webserver) and IOP-2
Optimized design: 3C3 coating +
•  Ability to work in harsh
extended operating temperatures 
environments (e.g. corrosive gases)
-20˚C to 45 …60˚C (with derating)1
EMC compliant (C1 + C2) and • Grid friendly design with reduced

integrated full DC-link choke harmonics and long cable length
• Reduced electromechanical
Safe Torque Off SIL 3 hardware  components and standard compliant
• Fit for digitalization and for cloud
Compatible with SINAMICS connect
and TIA Portal via GSD file
 based analytics
• PLC connectivity as a standard
• Simple installation, service and
Pluggable I/O terminal hardware  maintenance

Unrestricted © Siemens 2020 IOP-2: Intelligent Operator Panel 1


max. 55 ˚C for PROFINET version
SAM: Smart Access Module P&F: Pump and Fan
Page 4
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 5
SINAMICS drive position within the
“Continuous Motion” portfolio

Basic Midrange High-End

SINAMICS SINAMICS
… G120X G120
Pump & Fan 0.75 – 630 kW 0.55 – 250 kW
Variable Blocksize compact drive with The modular application -
torque control FW and usability approach specific drive system for
designed to fulfill pump & fan general plant and machinery
needs construction

SINAMICS SINAMICS SINAMICS


V20 G120C G120
Machinery/ 0.12 – 30 kW 0.37 – 132 kW 0.37 – 250 kW
Industry
Constant Basic, cost-effective, easy-to- The compact, cost-effective The modular application -
torque control operate compact drive (1/3 AC) and with optimized functions specific drive system for
drive general plant and machinery
construction

Unrestricted © Siemens 2020


Page 6
The SINAMICS G120X differentiates itself from the SINAMICS
V20 with dedicated features and improvements

Out of the Box 3C3 Communications


= 1 Article number coating PN, DP, BACnet

Usability:
-20-45 (..60)°C SINAMICS Motor temp. Terminals with
Operating

G120X
IOP-2 sensor PTC differential
temperature

UL + NEMA NEC
Long cable Improvements Motor support
24V connection
lengths PM, RSM
over the
SINAMICS V20 I/O terminals are
Seamless STO Power / voltage range pluggable and
SIL3 HW up to 630kW optimized

Extension module
Firmware: dedicated
Full DC-Link choke increases
P&F features
flexibility

SINAMICS G120X

PM: permanent magnet; RSM: reluctance synchronous motor

Ease of use / maintain Connectivity and integration Reliable, flexible & efficient Tailored for the water industry
Unrestricted © Siemens 2020
Page 7
The SINAMICS G120X differentiates itself from the
G120 (P) with dedicated features and improvements

SINAMICS
G120X
Extension module
Out of the Box 3C3
Full DC-Link choke increases
= 1 Article number coating
flexibility
Improvements
over the
I/O terminals are -20-45 (..60)°C
Long cable Firmware: dedicated SINAMICS G120P pluggable and Operating
lengths P&F features
optimized temperature

Seamless STO
SIL3 HW
SINAMICS G120X

Ease of use / maintain Connectivity and integration Reliable, flexible & efficient Tailored for the water industry
Unrestricted © Siemens 2020
Page 8
SINAMICS G120X
System Integration

PCS7-Integration via Typical controllers:


SIMATIC PDM • SIMATIC S7-1200
• SIMATIC S7-1500
• SIMATIC S7- 400
• Desigo PX
HMI

SINAMICS G120X

Wi-Fi

Setup via SAM (Webserver)


or IOP-2

Unrestricted © Siemens 2020


Page 9
G120X seamlessly blends into
GMC Digitalization

TIA Portal (GSD), TIA Portal (GSD), TIA Portal (GSD), IOP-2,
SINAMICS Web server, SINAMICS Web server, SINAMICS Web server,
IOP-2 IOP-2 Analyze MyDrives

APP:
in-cloud

Analyze My
Drives (AMD) Product Production Production Production Services
design planning engineering execution

Machine Machine Machine Machine Machine


data concept engineering commissioning operation services
in-line

SINAMICS connect
NX MCD, SIZER, E- DT Configurator, SIZE, SAM (webserver), SAM (webserver), IOP-2, SAM
in-machine

Plan IOP-2 IOP-2 (webserver), Analyze


2 wire

2 wire

2 wire
PTP

PTP

PTP

MyDrives

RS2321
G120X can… • ... simply be connected to the cloud
Up to 8
drives • ... visualize important operating states
G120X • ... show the need for service  AMD
1
RS232: SUB-D 9pol
Unrestricted © Siemens 2020
Page 10
Wiring example between G120X and SINAMICS Connect 300

G120X + SINAMICS Connect Wiring example RS232: SUB-D 9pol (female)

Pin Signal Use


TX1 1 DCD Data Carrier
detect
RX1
M 2 RxD Received data
PE1 3 TxD Transmited data
4 DTR Data terminal
ready
5 M Ground (GND)
6 DSR Data set ready
7 RTS Request to send
SINAMICS SINAMICS
G120X 8 CTS Clear to send
Connect
SINAMICS G120X SINAMICS Connect 9 RI Incoming call
Pin 2 TX1
Pin 3 RX1
Pin 5 M
Pin 5 PE1

Unrestricted © Siemens 2020


Page 11
With SINAMICS CONNECT it is possible to collect and upload
to MindSphere 21 parameters for further analysis

No Param. Name Description Unit No Param. Name Description Unit


1 r0026[-1] portX_Act_filtered_DC_l Filtered V 10 r0018[-1] portX_Firmware_versio Version of installed -
ink_volt 3) DC-link voltage n firmware
2 r0025[-1] portX_Act_filtered_outp Filtered [rms] voltage V 11 r0030[-1] portX_CO_Act_Filtered Torque generating A
ut_voltage applied to motor _current_Isq current component
3 r0032[-1] portX_Act_filtered_pow (Mechanical) shaft kW 12 r0037[0] portX_CO_Converter_t Heat sink deg.
er power emperature temperature C
4 r0022[-1] portX_Act_filtered_rotor Calculated rotor rpm
13 r0035[0] portx_CO_Act_motor_t Calculated motor deg.
_speed speed based on r0021
emperature temperature C
5 r0031[-1] portX_Act_filtered_torqu Electrical torque NM
e 14 r0945[0] portX_Fault_code_1 Recent fault trip 1 -

6 r0039[0] portX_Energy_consump Electrical energy used kWh 15 r0945[1] portX_Fault_code_2 Recent fault trip 2 -
t_Meter by converter since
16 r0945[2] portX_Fault_code_3 Recent fault trip 3 -
display was last reset
7 r0207[0] portX_Rated_converter Rated converter A 17 r0945[3] portX_Fault_code_4 Recent fault trip 4 -
_current current 18 r0945[4] portX_Fault_code_5 Recent fault trip 5 -
8 p0305[0] portX_Rated_motor_cur Nom. Motor current A 19 r0945[5] portX_Fault_code_6 Recent fault trip 6 -
rent from rating plate
20 r0945[6] portX_Fault_code_7 Recent fault trip 7 -
9 r0002[-1] portX_Converter_state Actual converter state -
21 r0945[7] portX_Fault_code_8 Recent fault trip 8 -

All data is transmitted as Double type and with a sampling cycle of 5s


Unrestricted © Siemens 2020
Page 12
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 13
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 14
The G120X offers different protection degrees with a
seamless system approach up to 630 kW / 700HP

Options
Blocksize Chassis
H J SD card

Voltage / Power @400V


G IP21 roof
Range Power range F top kit
kW up to… E
3AC200 – 240V D
B C IP20 / UL open
(0.75 – 55 kW / IP20 /IP21 kit1,2/ A E
IP20 Push Through push through kit
1 – 75 HP)
kit2
3AC380 – 480V UL open type

..132

..250

..400

..560
I/O ext. module

..7.5

...15

...37

...55
…3
Power:
(0.75 – 560 kW /
0.75 – 560 kW
1 – 700 HP)
(630kW @ 690V) NEW Filter B
1 – 700 HP Operator Wi-Fi (footprint)
3AC500 – 690V incl. Panel Webserver
(3 – 630 kW / Passive
4 – 700 HP) harmonic filter

or
Choke

IOP-2/ BOP-2 SAM


NEW Sinus filter
du/dt filter

1
Wall mounted w/o cabinet in lockable electrical room 2
IP21 kit/ IP20 PT-kit FS A-G as an orderable option SAM: Smart Access Module
Unrestricted © Siemens 2020
IOP: Intelligent Operator Panel
Page 15
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 16
SINAMICS G120X
Technical data – Seamless power range

Product data overview G120X G120X

3AC 200 – 240V Full DC-Choke, IEC 61000-3-12


0.75 – 55 kW / 1 – 75 HP DC Choke causes reduced line
-20%/+10% Harmonic Distortions harmonics and results in reduced cable
Voltage / diameter due to lower line current
3AC 380 – 480V
Power 0.75 – 560 kW / 1 – 700 HP
Range -20%/+10%
Connectable with e.g. sinus filter and
DC – LINK
3AC 500 – 690V du/dt filters
3 – 630 kW / 4 – 700 HP
-20%/+10%
C1 – 50m for frame size A-G
110%/60s1 or 135%/3s1 Public (IP20/ UL open type with ext. Filter B)
Overload Capability HO2 rating: 150%/60s1
C2 -
600s cycle
EMC Public – 150m for frame size A-G
-20°C to 45/ 60°C (derating)
5 according Industrial
Operating Temperature
to
EN 61800-3 C3 –
Industrial 100m for frame size H-J
IEC: NEMA:
Degree of Protection IP20/213 UL open type
Industrial up to 450m4
(unfiltered) (unscreened motor cable)
1
For FSH,J and cycle times please refer to the manual
4
Frame size A/B/C/D/E: 300m, F/G: 450m, H/J:200m
Unrestricted © Siemens 2020 2
HO: High Overload dimensioning
5
Until 55°C with PN version
Page 17 3
IP20 with roof top option
SINAMICS G120X
Technical data – Communication interfaces, options

Product data overview G120X


LEDs to indicate the status of
• 6 dig. inputs, 2 dig. outputs (relays) operation and communication
• 2 analog inputs 0 – 10V, 0/4 – 20mA
• 1 analog outputs 0 – 10V, 0/4 – 20mA
Inputs / Outputs / • 1 input for PTC/KTY/Pt1000/Pt100 (via AI)
Communication Interfaces motor sensor
• PROFINET, EtherNet IP
• Modbus RTU, USS, BACnet MS/TP
• PROFIBUS DP

I/O Extension Module2,3 • 2DI, 2AO, 4DO (relay), 2x Pt1000 or Ni1000


• SD card
• IP21 roof top kit
• IP20 PT-kit as an option/ FS A-G
Options • I/O extension module1
• Smart Access Module
• Input and output filters
1.5 mm2 cable per clamp, pluggable
Terminal Hardware
1 plug with double clamps2
Standards CE, UL, cUL, EAC, KC3, RCM

1
Only one piece can be connected per drive 3
Only available in 400V version
Unrestricted © Siemens 2020 2
Allows to easily multiply potentials
Page 18
SINAMICS G120X
Technical data

Product data overview G120X STO terminals (examples)

Safety Integrated STO SIL 3 HW1

Memory card (SD card)


FSA-C
Yes
Below the CU
Real-time Clock Yes

BOP-2 Yes

IOP-2 Yes
FSD-G
WEBSERVER (SAM) Yes Behind the CU

• Switching frequency 4kHz (or 23) to 16Khz STO A

(with derating) Enable/disable


Motor support • Asynchronous
incl. 3rd party IE4 • V/f control linear, parabolic STO B

• Sensorless vector mode


• Reluctance motor (Siemens, 3rd party2 ) Not used

• Permanent magnet2

1
Wiring example can be found in the manual chapter 4.2.8 / FAQ available in SIOS
Unrestricted © Siemens 2020 2
Please contact the Competence Center team.
Page 19 3
Minimum possible pulse frequency is determined by the power range – please refer to manual
Safe Torque Off (STO) – Safety integrated functionality

Safe Torque Off functionality Wiring example according to EN13849-1/IEC 61508


A converter with active STO function prevents energy supply to Using a SIRIUS 3SK2 safety relay inside a control cabinet for FSA
the motor, so it can no longer generate torque at the motor shaft. … FSG corresponding to PL e and SIL 3

Requirements with SINAMICS G120X:


1. Both switches on the converter for enabling/disabling STO
are in the ON position.
2. A higher-level control system is required to select the STO
safety function, to monitor and get feedback from the
converter.

Prerequisites for reaching SIL 3/PL e1:


3. Suitable higher-level controllers
• SIRIUS 3SK12: Single-channel static feedback circuit
SIRIUS 3SK2: Two-channel dynamic feedback circuit
• MSS 3RK3: Two-channel dynamic feedback circuit
• SIMATIC: Feedback circuit monitoring in the safety
program
4. Forced checking procedure (test stop) every 3 months

1
Prerequisites for SIL 2/PL d are available in the OPI
Unrestricted © Siemens 2020 2
Permissible for converters FSH and FSJ, not for FSA … FSG
Page 20
Compliant 3C2 / 3C3 coating on circuit boards

Class
Environment parameters 3C2 3C3
Units
IEC 60721-3-3: 2002
Mean Max Mean Max
Sea salt mg/m3 Salt mist • FSA ... FSG: Protected according to 3C3 to EN
Sulphur dioxide mg/m3 0.3 1 5 10 60721‑3‑3
Hydrogen sulphide mg/m3 0.1 0.5 3 10
Chlorine mg/m3 0.1 0.3 0.3 1 • FSH/FSJ: Protected according to 3C2
Hydrogen chloride mg/m3 0.1 0.5 1 5 according to EN 60721-3-3
Hydrogen fluoride mg/m3 0.01 0.03 0.1 2
Ammonia mg/m3 1 3 10 35
Ozone mg/m3 0.05 0.1 0.1 0.3
Nitrogen Oxides mg/m3 0.5 1 3 9
Accessories:

• The standard BOP-2 can be • The I/O extension module is


• The IOP-2 can be operated in
operated in 3C2/3C3 class coated to be used in 3C2/3C3 class
3C2/3C3 class environments.
environments. environments.

1
The values refer to a temperature of 20°C and a pressure of 101.3 kPa
Unrestricted © Siemens 2020 2
Mean values are expected long-term values. Max. values are limit or peak values, occurring over a period of time no longer than
Page 21 30min/day
SINAMICS G120X
IP20: Mechanical installation & dimensions

Side-by-side mounting until 50°C1 ambient temperature IP20


Add.
Height mm (inch)
Power Width Depth depth
Frame
range (kW) mm w/o With incl. CU With I/O
size
 380-480V (inch) screening screening mm (inch) extension
plate plate module
FSA 0.75 – 3 73 (2.8)  232 (9.1) 330 (13) 209 (8.2) 27 (1.1) 2
FSB 4 – 7.5 100 (3.9) 275 (10.8) 383 (15.1) 209 (8.2) 27 (1.1) 2
FSC 11 – 15 140 (5.5) 295 (11.6) 423 (16.7) 209 (8.2) 27 (1.1) 2
FSD 18.5 – 37 200 (7.9) 472 (18.5) 625 (24.6) 239 (9.4) 27 (1.1) 2
FSE 45 – 55 275 (10.8) 551 (21.7) 729 (28.7) 239 (9.4) 27 (1.1) 2
FSF 75 – 132 305 (12) 709 (27.9) 969 (38.1) 360 (14.2) 27 (1.1) 2
1255
FSG 160 – 250 305 (12) 999 (39.3) 360 (14.2) 27 (1.1) 2
(49.4)

FSH 315 – 400 548 (21.6) 1696 (66.7)  - 393 (15.5) 27 (1.1) 2

FSJ 450 - 560 801 (31.5) 1621 (63.8)  - 393 (15.5) 27 (1.1) 2

Clearance distance: mm (inch)


FSA-C: A= 80 (3); B= 100 (4); FSD-G: A= 300 (12), B= 350 (14);
Minimum spacing at the front: 100mm FSH-J: A= 0 ; B: 250 (8)
FSA – FSG: Side-by-Side mounting without space between drives
FSH – FSJ: requires 30mm distance between drives
1
FSA,B,C: 50mm between each other when ambient temperature >50°C
Unrestricted © Siemens 2020 2
Additional depth of 11.8 mm/9.8 mm is required with an operator panel/ SAM
Page 22 mounted onto the I/O Extension Module
SINAMICS G120X
IP20: Wiring and interface

Wiring example: PN Interface

FS B FS A…C

PROFINET connections

Line supply Motor

Unrestricted © Siemens 2020


Page 23
SINAMICS G120X
IP21 roof top kit: Mechanical installation & dimensions

Side-by-Side1 mounting without space


between the converters IP21 KIT dimensions

A B C D Ø
Frame
Clearance mm mm mm mm mm
size
(inch) (inch) (inch) (inch) (inch)
FSA 5.5
FS E FS F FS G 42 (1.7) 25 (1) 92 (3.6) 54 (2.1) 306 (12)
(0.2)
FSB 5.5
63 (2.5) 25 (1) 120 (4.7) 80 (3.1) 306 (12)
(0.2)
FSC 5.5
94 (3.7) 25 (1) 160 (6.3) 118 (4.6) 306 (12)
(0.2)
FSD 300 (37.1) 28 (1.1) 218 (8.6) 170 (6.7) 323 (12.7) 6 (0.2)
FSE 300 (37.1) 28 (1.1) 293 (11.5) 230 (9.1) 323 (12.7) 6 (0.2)
FSF 300 (37.1) 28 (1.1) 323 (12.7) 270 (10.6) 323 (12.7) 6 (0.2)
FSG
300 (37.1) 28 (1.1) 323 (12.7) 270 (10.6) 323 (12.7) 6 (0.2)

IP21 top cover on the control cabinet panel using two M5 screws
(tightening torque: 6 Nm (53.1 lbf.in)

1
Until 50°C, then 50mm between each other
Unrestricted © Siemens 2020
Page 24
SINAMICS G120X - IP20 Push Through Kit :
Mechanical installation & dimensions

Note: degree of protection for PT parts IP20 PT KIT


Outside the cabinet is IP20

Depth
Height mm (inch)
FS A-C FS D-G mm (inch)
Frame Width
size mm (inch) H - with H1- w/o
screening screening T1 T2
plate plate
FSA 126 (5) 390 (15.4) 300 (11.8) 160 (6.3) 57 (2.2)
FSB 153 (6) 450 (17.7) 345 (13.6) 153 (6) 66 (2.6)
FSC 191 (7.5) 473 (18.6) 361 (14.2) 154 (6.1) 65 (2.5)
FSD 271 (10.6) 647 (25.5) 514 (20.2) 142 (5.6) 98 (3.9)
FSE 360 (14.2) 773 (30.4) 600 (23.6) 145 (5.7) 93 (3.7)
FSF 396 (15.6) 1003 (39.5) 749 (29.5) 185 (7.3) 185 (7.3)
FSG
384 (15.1) 1275 (50.2) 1026 (40.4) 184 (7.2) 188 (7.4)

Drilling dimensions can be found within the operation instructions.

Unrestricted © Siemens 2020


Page 25
SINAMICS G120X – I/O extension module:
Dimensions, interface overview

Dimensions: I/O extension module (wiring diagram):

Interface overview:
Interface to an Hole for fixing
1 4
operator panel screw

Switch for AI 2
2
(temp/current)

Terminal strips
5
X203 and X204 r0719 = 1, I/O ext. is recognized

Terminal strip Interface to Note: The I/O Extension Module does not support the mounting in the
3 6
X202 converter door of a control cabinet.

Unrestricted © Siemens 2020


Page 26
Operator Panels
IOP-2 and BOP-2

Intelligent operator panel (IOP-2) Basic operator panel (BOP-2)


Intelligent commissioning & configuration tool Enhances the interface & communication capabilities

• Easy commissioning of standard applications via various • Commissioning wizard


assistants • 2-line display with text display
• Knowledge of parameter structure not necessary • Diagnostics for parameter display without auxiliary function
• Serial commissioning through clone function • Serial commissioning through clone function
• Diagnosis due to clear text display, usable on-site • Key operation with menu structure
• Integrated support function to troubleshoot errors • Door mounting available
• Simplified Update of languages, assistants and FW via USB

Unrestricted © Siemens 2020


Page 27
NEW IOP-2 available functionalities
from V2.4 and V2.5

V2.4 Available V2.5 HF1 (NEW!)


• Automatic Restart now! • A new status screen setup with the
• Boost possibility to change between scalar,
• Bypass mode bar graph, or trend view screens and
• Cavitation protection add/change parameters directly from
• Condensation protection the main menu,
• Deragging
• Dual ramp • Improved command data set (CDS)
• First pipe filling allows easy setup of I/Os for different
• Flying restart CDS,
• Frost protection
• Hibernation mode • The Application Setup has new
• Skip frequencies functions: Multi-pump control and
• PID Controller Jogging.
• Adapting Kp and Tn
• Programmable timers
• Cascade control
• Load monitoring
• Efficiency optimization

Unrestricted © Siemens 2020


New FW can be downloaded here: https://support.industry.siemens.com/cs/ww/en/view/109762019
Page 28
Smart Access Module
Webserver via Wi-Fi

Smart Access Module (SAM) Mobile Device View


(Additional WLAN Access Point required)
Faster setup with improved wizards

• A faster setup mode is presented for the G120X to fulfill the


branch applications (Pump, Fan, Heavy-duty)
• In parallel, the classic quick setup is kept for the rest of the G120
family

-F i
Wi

Up to 50m

SAM: Smart-Access-Module
Unrestricted © Siemens 2020
Page 29
Smart Access Module
Presents a new quick setup mode

Application Motor I/O Important Motor Config. Is


selection data configuration (key) parameters ID Finished

Prefilled standard Preselected standard Prefilled


macro

The new G120X SAM’ setup mode enables a faster P&F setup solution
Unrestricted © Siemens 2020
Page 30
New upgrade of SAM FW 01.03.01 includes the new
application setup for G120X

New application setup menu New user interface improvements

• Additional I/O terminals are


included in the I/O
configuration and diagnostic

• New guidance information


is provided in JOG mode

• Improved 87 Hz selection is
available on motor data page

• Hints for motor connection are


provided for Star and Delta

The new SAM FW supports the G120X specialized P&F application setup
Unrestricted © Siemens 2020
New FW can be downloaded here: https://support.industry.siemens.com/cs/ww/en/view/109769429
Page 31
PLC connectivity can be performed via cyclic or acyclic
communication using the GSDML file

• The GSDML file enables the SINAMICS


HMI G120X to be operated via PROFINET by
making the device known to the configuration
tools such as TIA Portal.

Typical
controllers:
SIMATIC
• PCS7 integration • S7-1200 • The G120X is able to communicate together
• TIA Portal (GSD file) • S7-1500
with a PLC in a cyclic or acyclic way.
Wi-Fi • S7-400

STO SIL 3 • Cyclic communication: data is • Acyclic communication: data is


transferred in each bus cycle. transferred when required, without
3SK…
Setup via creating a permanent
• The controller sends control words communication load.
IOP-2 or SAM
and setpoints to the drive and
receives status words and actual • It takes significantly longer than
values from the SINAMICS drive the cyclic transfer, but larger data
GSDML file can be found in SIOS can be transferred.
DriveLib (TIA Portal) LAcyCom library
Unrestricted © Siemens 2020
Page 32
SINAMICS function blocks library can be used as an intuitive
interface for controlling the SINAMICS G120X with a CPU

Function blocks for S7-1200/1500 Compatible with G120X Benefits


• Easy reading/writing of multiple parameters

• SINA_PARA • Tested function blocks with intuitive


(FB286) interface  ready to use in TIA Portal
Load memory Work memory
without know-how protection and with
acyclic an innovated block interface
157234 bytes 16411 bytes

• Easy reading/writing of 1 parameter • Simplified controlling by SIMATIC S7


• SINA_PARA_S
via PROFIBUS/PROFINET
(FB287)
• Supports cyclic/acyclic data
Load memory Work memory
93871 bytes 7129 bytes
acyclic exchange between the drive and
SIMATIC S7
• Simple speed control
• Low CPU utilization levels for S7-
• SINA_SPEED 1200/1500
(FB285)
Load memory Work memory
cyclic
DriveLib (TIA Portal) 16717 bytes 941 bytes

SINAMICS motion control functions are intuitive, powerful, "lean" and free of charge!
Unrestricted © Siemens 2020
Page 33
SINAMICS G120X conquers TIA Portal Openness

What it is? How can I get it?


• API interface for WinCC and • From STEP 7 professional or
STEP 7 in TIA Portal. WinCC V13 SP1 onward, TIA
• It can be used to create your Portal Openness is included
own applications, e.g. a code in the delivery of STEP 7 or
generator for HMI images WinCC in TIA Portal.
and PLC software blocks.

TIA Portal
“Openness”
Benefits for G120X Related documents
• Remote parametrization/ • Intro + demo of TIA
commissioning of multiple Openness:
drives on the same network https://support.industry.sieme
ns.com/cs/de/en/view/10871
with SIMATIC PLC 6692
• Creation, modification and • Application description
general management of G120X:
parameter lists https://support.industry.sieme
ns.com/cs/ww/en/view/10977
7633
Unrestricted © Siemens 2020 API: Application programming interface

Page 34
The G120X extension of the TIA Add-in “Startdrive V16: Edit
parameters in several drives” enables setup via PLC

TIA Openness Add-in Benefits

• The extension of the TIA Add-in for the G120X enables • No need of manual configuration
the setup of drives with the same characteristics
(same motor data) by copying a giving configuration to all • Easy setup of one or several G120X frequency
selected drive objects converters by using a SIMATIC PLC and
function blocks for acyclic communication

Easy solution for remote setup of your G120X using a PLC via TIA Openness
Unrestricted © Siemens 2020
Download link
Page 35
SINAMICS G120X FDI Package (IEC 62769) allows device
integration for process automation into PCS7 (SIMATIC PDM)

FDI package PDM V9.1 G120X FDI package


Integration into PDM

Import • Supports only PROFINET fieldbus


communication

Stand-alone or PCS7
• Allows remote communication between
SIMATIC PDM Available PDM options: drive and operator
(Process Device Manager) • As stand-alone version
• It’s an universal, manufacturer- • Integrated into SIMATIC PCS7
independent tool for configuration,
parameter assignment, • Integrated into the STEP 7 eng.
• Enables Upload/Download of drive data, as
commissioning, diagnostics and tool of SIMATIC S7
maintenance of devices. well as factory reset via PC
• Integrated into the SIMATIC PCS7
Maintenance Station
• Integrated into the SIMATIC
SIMATIC PDM V9.1 SIOS Maintenance Station PDM FDI Package can be found in SIOS
Unrestricted © Siemens 2020
Page 36
SINAMICS G120X PN FDI Package V2.01.00:
With new features and improvements!

Basic setup – Quick Startup:


NEW • Following IOP-2 basic setup principle to write the
07/20 motor details directly online on the drive
User Defined List (UDL):
• Designed to improve the upload performance
between the host software and the drive
• Very flexible to define
• Limited to 30 parameters
• Can be saved into the project and imported/exported
into other drive’s configuration as part of the Expert
list
Improved diagnostics
• Quick troubleshooting without consultation of the
manual
• Introduces Alarm & Fault text description
• New signaling for bit diagnostic (status & control
words)

The FDI package can be downloaded it via: https://support.industry.siemens.com/cs/ww/en/view/109778847


Unrestricted © Siemens 2020
Page 37
Free Function Blocks for logic operations are now available
for SINAMICS G120X from FW V1.03

Free Function Blocks (FFB) FFBs (No. of blocks)


AND (3) XOR (3)
• The FFB are modules that enable logic or mathematical
Logic blocks
operations by combining several states (e.g. access control, OR (3) NOT (3)
plant status) to a control signal (e.g. ON command) required for
controlling the drive system in a wide variety of applications. Subtrac- Multiplier
• FFB are only available on G120X FSA … FSG. Adder (2)
tor (2) (2)
Calculation
• There is a limited no. of FFB. The converter has 2 adders for blocks
Divider Compara
instance, ADD 0 and ADD 1. If you have already configured 2 (2) -tor(2)
adders, then no other adders are available
Pulse
• Runtime groups: In order to activate a FFB, the user must ON time OFF
Timer blocks generator
(3) delay (3)
assign it to a runtime group. (3)

Runtime group 4 5 6 Memory block RS flip-flop (3)


Time slice 64 ms 128 ms 256 ms
ADD, SUB, MUL, DIV, NCM, MFP, Breaker block Analog switch (2)
PDE, PDF, NSW, LIM, LVMAND, OR,
XOR, NOT, RSR Control block Limiter (2)
ADD, SUB, MUL, DIV, NCM, MFP,
PDE, PDF, NSW, LIM, LVM
Complex block Limit monitor (2)

Unrestricted © Siemens 2020


Page 38
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 39
SINAMICS G120X
Motor Control

Motor control

• Parabolic v/f characteristic for square law torque at


radial pumps, radial and axial fans, and radial
compressors with low dynamic requirements
V/f characteristic • Linear v/f characteristic for constant torque at positive
displacement pumps and compressors with low
dynamic requirements
• Flux reduction via ECO mode

• Simple control with field orientation enables stable


Flux current control
operation under varying load

• Field orientated control mode for demanding drives with


speed control and higher dynamic requirements
Sensorless vector mode • Optimized control modes for Siemens synchronous
reluctance motors
• Stable operation together with large motors

Unrestricted © Siemens 2020


Page 40
SINAMICS G120X
Protective Functions

Protective functions
• Over/under voltage and phase loss
• Overcurrent, overload i2t
Converter • Over temperature of control unit and power module
• Broken wire monitoring of the analog inputs
• Monitoring of 3 external faults/warnings

Motor
• Temperature monitoring with and without temperature
sensor
G120X
• Speed monitoring, blocking and stalling monitoring
• Torque monitoring for dry run protection or belt
Drive monitoring
• Protection against frost, condensation, cavitation
Protection
Communication • Detection of missing telegrams, bus interruption

• Buffer for 8 fault cases with each 8 faults incl. fault value
Fault buffer and time stamp
• Buffer for 56 warnings incl. warning value and time stamp

Unrestricted © Siemens 2020


Page 41
SINAMICS G120X
Basic Functions

Basic functionality

• Analog value 0 – 10V / 0/4 – 20mA with broken wire


monitoring
• Fixed speed values direct or binary coded
Set point selection • Motorized potentiometer
• Communication interface
• PID controller for process values

• Minimum speed, maximum speed, ramp generator with


Set point channel
smoothening
• Control word and status word according PROFIdrive
Control and feedback
profile

• 3 control data sets, to be switched during operation, for


Data sets local/remote operation or manual/automatic mode
• 3 motor data sets for different motors and control modes

• Simple configuration of the terminals by selectable


Selectable macros
macros

Unrestricted © Siemens 2020


Page 42
SINAMICS G120X
Simple configuration of the terminals by selectable macros

Default terminal settings – Macros


Terminal 41 42 43 44 45 461 47 48 49 511 521 541 551 573
Setpoint Setpoint Setpoint
AI 0 Setpoint Setpoint Setpoint Setpoint Setpoint
local - - - -
local
-
local
-
PID actual PID actual PID actual Setpoint
PID actual PID actual PID actual
AI 1 -
value value value
-
remote value value value
- - - - -
Speed Speed Speed Speed Speed Speed Speed Speed Speed Speed Speed Speed Speed Speed
AO 0 actual value actual value actual value actual value actual value actual value
actual value actual value actual value actual value actual value actual value actual value actual value
Current Current Current Current Current Current
Current Current Current Current Current Current Current Current
AO 12 actual value actual value actual value actual value actual value actual value
actual value actual value actual value actual value actual value actual value actual value actual value
ON / OFF2 ON / OFF2 ON / OFF2
DI 0 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2 ON / OFF2
local local
ON / OFF2
local
Jogging 1
Service Service Fixed ON / OFF2 Service Service ON / OFF2 ON / OFF2
DI 1 - -
pump 1 pump 1 setpoint 1 remote
-
pump 1 pump 1
-
remote
-
remote
Jogging 2
Service Service Fixed Service Service
DI 2 - -
pump 2 pump 2 setpoint 2
- -
pump 2 pump 2
- - - - -
Service Fixed Service
DI 3 - - -
pump 3 setpoint 3
- - -
pump 3
- - - - -
Manual ↔ Manual ↔ Manual ↔ Local ↔ Manual ↔ Manual ↔ Local ↔ Local ↔ Local ↔
DI 4 -
Auto Auto Auto
-
Remote
-
Auto Auto
-
Remote
-
Remote Remote
DI 5 Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault Ackn. fault
DO 0 Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault
DO 1 Operation Operation Operation Pump 1 Operation Operation Operation Operation Operation Operation Operation Operation Operation Operation
DO 2 RDY op. RDY op. Pump 1 Pump 2 RDY op. RDY op. RDY op. Pump 1 Pump 2 RDY op. RDY op. RDY op. RDY op. RDY op.
DO 3 Alarm Alarm Pump 2 Pump 3 Alarm Alarm Alarm Pump 2 Pump 3 Alarm Alarm Alarm Alarm Alarm

1
For converters with USS fieldbus interface
Unrestricted © Siemens 2020 2
With I/O extension module
Page 43 3
For converters with PROFIBUS or PROFINET fieldbus interfaces
SINAMICS G120X brings the best pump and fan control
ensuring energy-saving and protection

Selected FW functions
Starting pumps/fans Operating phase Stopping phase

Economy mode Support of PMSM + RSM1


Deragging

Energy savings calculator Bypass mode

Multi-pump STO
Pipe filling PID Hibernation Condensation
control SIL 3
protection
Power on
Keep-running mode Multi-speed set point Frost
Dual ramp ON/OFF2 protection
Fire mode (ESM) Rotation monit. w. sensor

Blocking-, leakage-, dry-running protection


Flying
restart Cavitation protection Other protections
NEU
Real time clock 3 programmable timer Free Function Blocks

Unrestricted © Siemens 2020 Fan & Pump 1


Refer to the manual
Pump control Energy saving Protection set point conditioning General
Page 44
control
Pump Control features allow to regulate, operate and protect
the complete system

Function Benefits

• Allows the use of several smaller


pumps, instead of one large pump
• Soft start with a ramp-up speed
• Multi-pump1 control 
• Enables option to switch off pumps
G120X simultaneously or using reverse
sequence
Software
features • Smooth water flow speed control on
• Pipe filling mode  empty pipes
• Protection against hammer effect

Pump control • Self-ability to clear clogs on the


• Deragging mode  pump’s impellers before operation
• Reduced maintenance efforts

1
Multi-pump control function is supported for same power rating pumps until <30kW
Unrestricted © Siemens 2020
Up to 6 pumps: 2 pumps (+4 with I/O extension module)
Page 45
Multi-pump control allows for the control of several pumps
using just one frequency converter

Multi-pump control Feature/ Function

Allows the of use several smaller pumps, which


can be switched in and out as required, instead of
one large pump

Control up to 2 (6 with ext. module) pumps by


integrated PID controller, using:

• Pump switchover
• Stop mode
• Service mode

Related parameters: p29520 … p29549

Note: when using the multi-pump control function for more


than two pumps, check r0719 = 1 to ensure that the I/O
Extension Module is recognized after installing the module.

Multi-pump control function is supported for same power rating pumps until <30kW.
Unrestricted © Siemens 2020
Up to 6 pumps: 2 pumps (+4 with I/O extension module)
Page 46
Multi-pump control
Pump switchover

Feature / Function
With pump switchover enabled, the inverter
3AC monitors the operation status of all running pumps:
1. If the continuous operating hours of the pump in
inverter operation exceed the threshold, the
inverter switches off the pump and then
switches in an idle pump to keep constant
output power
2. If the continuous operating hours of a pump in
line operation exceed the threshold, the inverter
first switches off the pump, switches out the
inverter-controlled pump to line operation,
10 hours 10 hours 10 hours 10 hours and then switches in an idle pump to run in
Pump1
inverter operation to keep constant output power
Pump2 Pump3 Pump4

p29522 = 0: next pump according fixed sequence


p29522 = 1: next pump according op. hours.
Unrestricted © Siemens 2020
Page 47
Multi-pump control
Stop mode

Feature / Function
Two stop modes are available as follows:
3AC
Normal stop
• Set p2370 = 0, All pumps running in line
operation are switched off simultaneously as
soon as the stop command is received.
• The pump in inverter operation stops under the
control of the inverter.
Sequence stop
• Set p2370 = 1, The pumps running in line
operation stop one by one in the reverse
sequence in which they are switched on. There is
Stop 1 Stop 2 Stop 3 Stop 4 a delay time (p29537) between every pump stop.
• The pump in inverter operation stops under the
control of the inverter after the other pumps are
switched off.

Unrestricted © Siemens 2020


Page 48
Multi-pump control
Service mode

Feature / Function
3AC

When a pump is in service mode, the inverter locks


the corresponding relay allowing to perform
troubleshooting of the pump without interrupting
the operation of other pumps.

Related parameters: p29540 … p29544

Run 2 Run 3 Run 4

Unrestricted © Siemens 2020


Page 49
Multi-pump control
Cascade control

Feature/ Function
Consists of the speed-controlled main motor and
up to three other motors that are switched-on or
off via contactors or motor starters, depending on:

• A fixed arrangement
• The operating hours

The PID deviation serves as the input signal for


activating the other motors. The contactors or
motor starters are switched by the drive's digital
outputs.

Usability: applications that require between 1 and


4 motors to be run at the same time depending on
load, so that e.g. highly variable pressure ratios or
flow volumes can be corrected

2 pumps (+2 with I/O extension module) Related parameters: p2200 … p2387
Unrestricted © Siemens 2020
Page 50
Pipe filling mode
Dismiss the hammer effect at the starting phase

Pipe filling mode Feature / Function

After each power-up, pipe filling mode allows the


inverter to fill the pipe slowly to avoid the
hammer effect when the converter works for the
first time after each power-up.

If the pipe filling is interrupted (for example, a fault


occurs), the function continues after the inverter is
recovered
Output
2 filling modes are available:
Operation
• Time mode
• Pressure mode
Pipe filling

Time Related parameters: p29610 … p29615


Valve open

Unrestricted © Siemens 2020


Page 51
Pipe filling mode
Setting up the function

Time mode Description Param.


p29611 = 0 0 = disable
Pipe filling p29610
1 = enable
0 = based on specified time
Filling mode p29611
1 = based on actual pressure feed.
=900 rpm (factory), sets the speed
Speed applied to the motor for the pipe p29612
filling
Pressure mode =50s (factory), sets the duration
Time p29613
time of the filling
p29611 = 1
=10% (factory); If p29611= 1
Filling
defines the threshold for stopping p29614
threshold
Depends on the filling via actual PID feedback
internal PID =0s (factory); If p29611= 1 monitors
the duration time for
Monitoring
“actual pressure >= threshold” p29615
time
The pipe filling stops if the duration
time is reached

Unrestricted © Siemens 2020


Page 52
Deragging mode
Cleans blockage from impellers and protects the pump

Deragging mode Feature / Function


The deragging function is used to clean any
clogs/ obstructions on the pump impeller, pipes
Speed or valves.

This function consists on running the motor


forward and on reverse to clean the impeller.
Time
Deragging mode can be enabled after power-up,
for every run or with an input signal.
(p29591).

an Related parameters: p29590 … p29598


cle
s
It’

Unrestricted © Siemens 2020


Page 53
Deragging mode
Setting up the function (1/2)

Description Param.
Deragging mode
1 = on first run after power-on
Switch on 2 = on every start p29590
3 = via binector-input
Binector input If p29590= 3, source of input source p29591
=500 rpm (factory), sets forward
Forward speed p29592
speed setpoint for deragging
=500 rpm (factory); sets reverse
Reverse speed p29593
speed setpoint for deragging
=5s (factory), sets ramp time from 0
Ramp up time p29594
to forward/reverse speed setpoint
Ramp down =5s (factory), sets ramp time from
p29595
time forward/reverse speed setpoint to 0
=5s (factory), duration time at each
Forward time p29596
forward speed
p1110 “inhibit negative direction” needs to be set to 0 =5s (factory), duration time at each
Reverse time p29597
to allow reverse mode → p1110 = 0. reverse speed

Unrestricted © Siemens 2020


Page 54
Deragging mode
Setting up the function (2/2)

Deragging mode Description Param.


Value from 1 to 999;
No. of cycles p29598
Number of cycles to be repeated

p1110 “inhibit negative direction” needs to be set to 0


to allow reverse mode → p1110 = 0.

Unrestricted © Siemens 2020


Page 55
Fan Control features allow to increase availability and
customize fan operation

Function Benefits

• Attempts to catch the running load and


• Flying restart  automatically restart the inverter after
power restore

G120X  • Allows to automatically acknowledge


Software • Automatic restart
all faults
features
• Up to 4 parametrizable frequencies
• Skip frequency bands  can be skipped

Fan control • Allows day/night switch-over of room


temperature
• Real-time clock and • Includes summer/winter clock

timer change
• Faults and alarms are provided with a
time stamp

Unrestricted © Siemens 2020


Page 56
Flying restart reduces starting times after brief power failures

Auto flying restart of pump and fans Feature / Function

After the ON command, the "flying restart" function


initially synchronizes the inverter output frequency
to the motor speed and then accelerates the motor
up to the set point.
Typical applications:
• Synchronization on a fan rotating even after
power failure
• The fan impeller is driven by the air flow
• Search current and search speed are adjustable.
• Searching also in the negative direction of
rotation (fan rotates in the reverse direction)

Unrestricted © Siemens 2020


Page 57
Automatic restart increases availability

Automatic restart Feature/ Function

Includes two functionalities after a fault that allow


to:
Automatic Restart (AR)
Auto Auto Auto • Automatically acknowledge all faults
No auto
No AR ack. ack. faults
ack. faults
ack. • Automatically switch-on the motor again.
faults if ON/OFF =1 faults

No auto Auto Auto Auto


Events recognized as power failure:
p1210 =0 • Fault F30003 (undervoltage in the DC link), after
switch on switch on switch on switch on
(default)
motor motor motor motor
line voltage has been briefly interrupted.
After After
After After
p1210= 1 power
power
power
power
p1210= 26 • After all power supplies have been interrupted
failure & failure &
failure
faults
failure
faults and all the energy storage devices in
the inverter have discharged to such a level that
p1210=4 p1210=6 p1210=14 p1210=16 the inverter electronics fail.

Unrestricted © Siemens 2020


Page 58
Skip frequency bands to avoid vibration and premature wear
and tear

Critical motor speeds can be skipped Feature / Function

Speed bands exist in the set point channel to


prevent unwanted motor speeds.
The drive traverses through the set skip frequency
bands on the ramp function up / down generator,
but permanent operation in the set skip frequency
bands is not possible. This prevents an unwanted
speed from being permanently pending.
Advantages:
• Avoidance of resonance in the mechanical
system (e.g. pipelines / vent ducts)
• Reduced material fatigue
• Reduced noise pollution
• 4 skip frequency bands with mean speed and
bandwidth parameterizable

Unrestricted © Siemens 2020


Page 59
Real-time clock for autonomous time-controlled operations

Real-time clock Feature / Function


Time
stamp
Real-time clock module
The real-time clock is a hardware clock in a chip,
which consists of a counter and a watch crystal as
the clock generator.
An energy accumulator is located in the device, so
that the clock does not stop when the device is
turned off.
It comprises the clock time in a 24 hour format
and the date in the "day, month, year" format.
It must be set once during commissioning. After
Faults and alarms are provided with a time stamp a power supply interruption, the real time clock
based on the real-time clock. This allows their clear continues to run for approx. 5 days.
relation with other activities in the production process,
which may be related to the faults or have not them
caused at all.

Unrestricted © Siemens 2020


Page 60
Timer functionality

Timer for controlling tasks Feature / Function

Operating principle and functional diagram of a timer


switch The timer function, along with the real time clock
in the inverter, offers the option of controlling when
signals are switched on and off.
Examples:
• Day/night switching of a temperature control
• Switching a process control from weekday to
weekend.

Unrestricted © Siemens 2020


Page 61
Set-point operation features allow to increase availability
and optimize pump and fan operation

Function Benefits
• Maximized operation time by avoiding
common issues w/o manual
intervention
• Personalized protection measures,
such as:
• Keep running mode  • Reduced PWM frequency, speed and
G120X output current
Software • Auto flying restart of P&F
features • Kinetic buffering to skip interruption

• Increased flexibility to regulate


• PID controller 
processes (levels, pressures, etc.)
Set point Op.
• Optimized pump operation
• Dual ramp function  • Shorter start/stop time
• Minimizes wearing of the pump
• Up to 16 fixed frequency settings that
• Multiple speed set points 
enable multi-speed operation

Unrestricted © Siemens 2020


PWM: Pulse Width Modulation
Page 62
Keep running mode
To keep maximum availability

Feature / Function
Overheat
Reduce PWM frequency Enables all possible functions to keep the
inverter away from faults and from tripping, by
applying configurable measures like:

Reduce speed • Reduction of the output speed and PWM


Overload
frequency to avoid over-temperature and
overload problems

Reduce output current • Catching running load and automatically


restarting the inverter after power disruption
Low-voltage (switches on drive while motor is running)
Auto flying restart pump
• Using kinetic energy from the load to skip short
and fan
time power interruption
Power interruption
Kinetic buffering to skip
Related parameters: p29630; p0290, p1210…p1240
interruption

PWM: Pulse Width Modulation


Unrestricted © Siemens 2020
Page 63
PID controller

Proportional, integral, and derivative controller Feature / Function


The PID enables simple process control such as
line pressure, fill level, temperature, flow, tension
Block diagram of a PID technology control control or load balancing.
• The technology controller is implemented as a
PID controller (controller with proportional,
integral, and derivative action)
• Set point are specified via analog value, fixed set
points, motorized potentiometer, fieldbus
• The P, I and D components can be set separately
„
Example: Technology controller as a level controller • The “I” component can be locked when the
control output is limited „
Control mechanism on a • Display and entry of set point and actual values in
closed loop feedback technological dimensions

Unrestricted © Siemens 2020


Page 64
Dual ramp mode
Optimizes pump operation

Feature / Function

The dual ramp function allows the user to


Speed parameterize the inverter so that it can switch
from one ramp rate to another when ramping
up or down to a set point.

Quick Fast
As a result, the inverter can be started
starting stopping smoothly and stopped quickly.
Time
Related parameters: p29570…p29580

No-return valve

Unrestricted © Siemens 2020


Page 65
Dual ramp
Setting up the function (1/2)

Description Param.

In %, sets the scaling of the ramp


Ramp-up scaling 1 p29570
up time (p1120) on 1st ramp
In rpm, speed threshold to be
Threshold speed 2 compared with actual speed at p29571
the end of 1st ramp going up
In %, sets the scaling of the ramp
Ramp-up scaling 2 p29572
up time (p1120) on 2nd ramp
Ramp-down In %, sets the scaling of the ramp
p29573
scaling 1 down time (p1121) on 1st ramp
In rpm, speed threshold to be
Threshold speed 3 compared with actual speed at p29574
the end of 1st ramp going down
Ramp-down In %, sets the scaling of the ramp
p29575
scaling 2 down time (p1121) on 2nd ramp

Unrestricted © Siemens 2020


Page 66
Dual ramp
Setting up the function (2/2)

Ramp-up scaling input Description Param.


p1120
CO: Ramp-up In %, displays the actual output
r29576
CI: p29578 CO: r29576 CI: p1138 X scaling output of the ramp-up scaling
CO: Ramp-down In %, displays the actual output
scaling r29577
scaling output of the ramp-down scaling
Ramp-down scaling input Sets signal source for scaling the
p1121
CI: Ramp-up ramp-up time of the ramp-
p29578
scaling input function generator when p1138 is
CI: p29579 CO: r29577 CI: p1139 X BICO to r29576.
scaling Sets the signal source for scaling
CI: Ramp-down the ramp-down time of the ramp-
CI: Ramp-function signal source for scaling the ramp- p29579
generator ramp-up up time of the ramp-function p1138 scaling input function generator when p1139 is
time scaling generator. BICO to r29577.
CI: Ramp-function signal source for scaling the ramp- Sets the signal source to enable
Dual ramp enable p29580
generator ramp- down time of the ramp-function p1139 the dual ramp function.
down time scaling generator.

p1120: ramp up time (s) │ p1121: ramp down time (s)

Unrestricted © Siemens 2020


Page 67
Multiple speed set points

Up to 16 fixed frequency settings that Feature / Function


enable multi-speed operation
This function can be used to specify preset
speed frequency set points.

The fixed set points are defined in parameters


and selected via binector inputs.
The digital inputs or the corresponding bits in the
PROFINET telegram, for instance, can be used
for external control here.

Both the individual fixed set points as well as the


effective fixed set point are available via a
connector output for further interconnection (e.g.
with connector input p1070 CI: Main set point).
Two methods are possible to select a fixed speed setpoint:
This function helps in implementing very simple
p1016: Selection mode
applications in which it should be switched only
1. p1016 = 1, Directly selecting a fixed speed setpoint
between a few dedicated speeds.
2. p1016 = 2, Selecting the fixed speed setpoint, binary

Unrestricted © Siemens 2020


Page 68
Multiple speed set points
Setting up the function (1/2)

Directly selecting a fixed speed setpoint; p1016 = 1


Description Param.

BI: Fixed speed


setpoint selection, p1020
bit 0
• Sets the signal source for
selecting the fixed speed
setpoint
BI: Fixed speed
setpoint selection, • Selects the required fixed p1021
bit 1 speed setpoint using p1020 ...
p1023
BI: Fixed speed • The number of the resulting
setpoint selection, fixed speed setpoint effective p1022
p1001 CO: Fixed setpoint 1 [rpm] bit 2 is shown in r1024
p1002 CO: Fixed setpoint 2 [rpm]
BI: Fixed speed
p1003 CO: Fixed setpoint 3 [rpm] setpoint selection, p1023
p1004 CO: Fixed setpoint 4 [rpm] bit 3

Unrestricted © Siemens 2020


Page 69
Multiple speed set points
Setting up the function (2/2)

Selecting the fixed speed setpoint, binary; p1016 = 2


Description Param.

BI: Fixed speed • Sets the signal source for


setpoint selection, selecting the fixed speed p1020
bit 0 setpoint

• Depending on the binary


BI: Fixed speed
combination of the source
Setpoint setpoint selection, p1021
signals, 16 fixed setpoints can
source bit 1
p1070
be selected (including 0rpm
BI: Fixed speed when there is no signal)
setpoint selection, p1022
bit 2 • The number of the resulting
fixed speed setpoint effective
BI: Fixed speed is shown in r1024
p1001 CO: Fixed setpoint 1 [rpm]
setpoint selection, p1023
…. bit 3
p1015 CO: Fixed setpoint 15 [rpm]
Links fixed speed value r1024
Setpoint channel
to the setpoint p1070
value
Full binary table can be found in the OPI (refer to Table 6-46)

Unrestricted © Siemens 2020


Page 70
Energy saving functionalities increase operation
performance and ensure reduced losses

Function Benefits
• Ensures best performance and lowest
losses on low dynamic loads (P&F)
• Eco mode 
• Optimizes output voltage to reduce
the load’s energy consumption
• Allows automatic pump switch off
G120X • Hibernation mode
(sleep mode) and wakeup by fixed set
Software  point or offset
• Saves energy, reduces mechanical
features
wear and noise
• Switches the motor between inverter
• Bypass  and line operation to reduce energy
Energy saving consumption
• Calculates the energy saving and flow
• Energy/ flow calculator 
values without the external meters

 • Operation of high efficiency motors to


• Support of PMSM + RSM
ensure more energy saving

Unrestricted © Siemens 2020 PMSM: Permanent Magnet Synchronous Motor


RSM: Reluctance Synchronous Motor
Page 71
ECO mode
Advanced energy saving/ motor control technology
Voltage Voltage
100% Feature / Function
80%

• Economy mode works by slightly changing the


Energy
output voltage (via excitation current) either up
saving
Without
ECO or down in order to find the minimum input power.
ECO

Speed Speed
• Allows energy saving during low dynamic load,
such as pump and fan applications without
knowledge of the characteristic curve.

• If the load is changed, the control can adapt to


normal dynamic control to give the best
performance.

Related parameters: p1300


When p1300
= 4, U/f control with linear characteristic and ECO
= 7, U/f control for a parabolic characteristic and ECO

Unrestricted © Siemens 2020


Page 72
Hibernation mode with PID
Smart features to save more energy

f
Feature / Function

Z Z
Sleep Z PID with hibernation allows to switch the pumps
to sleep mode when the drives are only being
deployed temporarily (by fixed set point or if the
Wake up offset is smaller than the setting) to avoid wasting
energy by:
T

• Frequently starting and stopping the pump during


low-load period causing increased pipe pressure
Energy and energy waste.
Operating Operating
Saving
• High pressure in the pipes that can cause
increased water loss even when the demand is
low.

Unrestricted © Siemens 2020


Page 73
Hibernation mode with PID
Setting up the function (1/2)

Hibernation mode using an external setpoint without boost Description Param.


=0 rpm (factory), lower limit of the
Minimum
motor speed, independently of the p1080
speed
speed target value.
Maximum =1500 rpm (factory), sets the highest
p1082
speed possible speed
=10s (factory), ramps-up the speed
Ramp-up
setpoint from 0 rpm up to the p1120
time
maximum speed (p1082) in this time
=10s (factory), ramps-down the speed
Ramp-down
setpoint from maximum speed to 0 rpm p1121
time
in this time
=0 rpm (factory), Sets the speed for
the start of the "hibernation mode"
Speed start function.
p2390
of hib. mode The total speed of this activation
threshold is the sum of the minimum
speed p1080 and p2390
Hib. mode =120s (factory), sets the delay time for
p2391
delay time the "hibernation mode" function

Unrestricted © Siemens 2020


Page 74
Hibernation mode with PID
Setting up the function (2/2)

Description Param.
Hibernation mode using an external setpoint without boost
Restart
speed =0 rpm (factory), sets the starting
relative w/o speed to restart the motor for the p2393
technology "hibernation mode" function
controller
=0s(factory), before the drive is finally
Boost time switched off (hibernation mode), the
p2394
period setpoint speed is moved to the boost
speed p2395 for the time set in p2394
=0 rpm (factory), the motor is
accelerated to the hibernation mode
boost speed p2395 for the hibernation
mode boost time period p2394 before
Boost speed p2395
it is brought to a standstill via the down
ramp of the setpoint channel (p1121)
and subsequently switched
off (pulse inhibit)

Unrestricted © Siemens 2020


Page 75
Bypass mode

Feature / Function

When induction motors connected to a converter


are frequently operated in the rated motor speed
range, unnecessary losses are incurred.

In Bypass mode it is possible to "bypass" the


inverter electrically as soon as the motor
frequently operates close to its rated speed.

This helps to avoid inverter losses and increase


overall efficiency.

There are 2 options to switch between converter


operation and line operation:
• Via control command (p1267.0 = 1)
• Depending on the speed (p1267.1 = 1)

Unrestricted © Siemens 2020 Bypass function is only supported on induction motors up to <30 kW
Page 76
Bypass mode
Setting up the function (1/4)

Method 1: Changeover for activation via a control command Method 2: Changeover depending on the speed
p1267.0 = 1 p1267.1 = 1

• If the speed setpoint r1119 lies above the bypass speed threshold
• The converter switches the motor between converter operation and p1265, the converter switches the motor to line operation
line operation depending on the bypass control command p1266 • If the speed setpoint falls below the bypass speed threshold, the
converter switches the motor to converter operation
Unrestricted © Siemens 2020
RFG: ramp function generator
Page 77
Bypass mode
Setting up the function (2/4)

Bypass mode

Description Param.
= 0s (factory), sets the de-magnetizing
Motor de- time (for ind. motors) after the
excitation converter pulses have been canceled. p0347
time The pulses cannot be switched in
(enabled) within this delay time
Bypass = 0, bypass diactivated (factory)
p1260
configuration = 3, bypass without synchronization
Bypass dead = 1s (factory), sets the dead time for
p1262
time non-synchronized bypass
= 1s (factory), sets delay time to switch
Debypass
back to converter operation for a non- p1263
delay time
synchronized bypass
= 1s (factory), sets delay time to switch
Bypass delay
back to line operation for a non- p1264
time
synchronized bypass

Unrestricted © Siemens 2020


Page 78
Bypass mode
Setting up the function (3/4)

Bypass mode
Description Param.
Bypass
=1480 rpm (factory), sets the speed
speed p1265
threshold to activate the bypass
threshold
BI: Bypass
Sets the signal source for the control
control p1266
command to the bypass
command
Bypass =0000 bin (factory), sets the source
changeover that should initiate the bypass:
p1267
source = 00: via signal (BI: p1266)
configuration = 01: via reaching the speed threshold

Unrestricted © Siemens 2020


Page 79
Bypass mode
Setting up the function (4/4)

Bypass mode
Description Param.
[00] Comd switch motor - PM
[01] Comd switch motor - line supply
CO/BO:
[05] FB signal switch motor power unit
Bypass
[06] FB signal switch motor line supply r1261
control/
[07] Bypass command (from p1266)
status word
[10] Bypass in process sequence
[11] Bypass enabled
Signal source for the feedback signal
BI: Bypass of the bypass switch:
switch [0] = 1261.0 (factory): switch motor-
p1269
feedback drive supply
signal [1] = 1261.1 (factory): switch motor-line
supply
Bypass
switch [0] =1000 ms (factory): motor-drive
p1274
monitoring [1] = 1000 ms (factory): motor-line
time

Comd: command
Unrestricted © Siemens 2020 FB: feedback
Page 80
Energy savings calculator
Estimate the running data without sensors

Feature / Function
3AC
1000111 00110001
• Without having a power meter or flow meter, the
G120X can estimate the energy saving from
Energy meter 110010 10000 the flow characteristic associated with a
01011000 mechanical flow control and the measured
electric power that is drawn.
• The calculation is suitable for centrifugal pumps,
fans, radial and axial compressors, for instance.

Flow meter To set the characteristic, it is required from the


pump manufacturer:
• The flow characteristic associated with 5 selected
speeds.
• At constant speed, the power drawn associated
with 5 flow rates, corresponds to the line
frequency and mechanical throttling of the flow
rate.

Unrestricted © Siemens 2020


Page 81
Energy savings calculator
Setting up the function (1/2)

For the energy-saving display of a fluid-flow machine, a typical


flow characteristic P = f(n) with 5 points along the
characteristic is required Description Param.
In %, specifies the power (P) of
Fluid flow machine
point 1 using as a reference the p3320
power point 1 (P1)
motor rated power
In %, specifies the speed (n) of
Fluid flow machine
point 1 using as a reference the p3321
speed point 1 (n1)
motor rated speed
Fluid flow… (P2) … p3322
r0041 = energy Fluid flow… (n2) … p3323
savings
Fluid flow… (P3) … p3324
Fluid flow… (n3) … p3325
Fluid flow… (P4) … p3326
The characteristic comprises the following value pairs:
Power (P) / speed (n): • p3320 / p3321 --> point 1 (P1 / n1) Fluid flow… (n4) … p3327
• p3322 / p3323 --> point 2 (P2 / n2)
• p3324 / p3325 --> point 3 (P3 / n3) Fluid flow… (P5) … p3328
• p3326 / p3327 --> point 4 (P4 / n4)
• p3328 / p3329 --> point 5 (P5 / n5)
Fluid flow… (n5) … p3329
Unrestricted © Siemens 2020
Page 82
Energy savings calculator
Setting up the function (2/2)

Description Param.

p0043 Process Energy In kWh, shows energy values at


Energy display
display the output of the converter
CO: Energy
Floating point 32 Int 32 [0] = Energy balance1 (sum) r0039[0..2]
display
Meas./ [1] = Energy drawn
CO: r0039 CO: r0042 [2] = Energy fed back
Calc
kWh Wh
When p0040 = 0 --> 1
Reset energy
The displays are reset (r0039,
Process energy display info handling consumption p0040
r0041) and the parameter is
display
automatically set to zero.

Energy In kWh, shows the saved


consumption energy referred to 100 operating r0041
Sets the signal source to saved hours
enable/reset r0042.
BI: Enable energy
BI: p0043 = 1 signal: p0043 In Wh, shows same values as
usage display CO: Process r0042[0..2]
The process energy display is r0039 but in different units and
enabled in r0042 energy display
data type (Integer32)

Unrestricted © Siemens 2020 1


Energy balance = Energy drawn – Energy fed back
Page 83
Support of high efficiency motor
Allows to save more operating energy cost

Feature / Function

G120X supports motors with IE2, IE3,IE4


Low efficiency
SynRM (Siemens, 3rd party1) and PMSM1
Life time cost

motors
Uses Sensorless vector control that allows to lower
g the output with higher performance
g S avin
in
Grow
With higher performance motors it is possible to
achieve greater energy savings in comparison
with traditional solution

Operating time

Break even point

Unrestricted © Siemens 2020 PMSM: Permanent Magnet Synchronous Motor 1


Please contact your Siemens partner
RSM: Reluctance Synchronous Motor
Page 84
Protection features monitor current status in order to
increase safety of personnel and machinery

Function Benefits
• Frost protection If temp. • Turns the motor automatically to avoid

falls below threshold freezing and motor damage
• Condensation protection • Keeps the motor warm to prevent

via DC current condensation
• Sends status and protects the pump
G120X • Cavitation detection  by tripping or sending alarms to reduce
Software the maintenance efforts
features • Pump blockage, • Monitors the output torque and speed
pipe leakage and  range to avoid abnormal situations,
dry running protection extending the lifetime of the pumps

Protection • No load, torque • Indicates load’s power interruptions


and rotation monitoring  • Monitors torque/speed to know
(with sensor) gearbox and fan belts status

• Keeps fans working without controller



• Fire mode (ESM) to extend ventilation and survival time
on critical situations
Unrestricted © Siemens 2020
Page 85
Condensation and frost protection
avoids damage to the motor and pump

Feature / Function

Condensation protection:
Motors in a humid and cold environment can
develop condensation which could cause motor
failure.
This problem can be avoided by slightly
(humid air → condensed water)
increasing the temperature of motor surface by
applying a DC current to keep the motor warm to
prevent condensation.

Frost protection:
The water frozen inside of a pump can cause
damage. The slow movement of the impeller
while it’s not being operated or when the
surrounding temperature falls below a threshold
can prevent damage.

Related parameters: p29622.. p29624


Unrestricted © Siemens 2020
Page 86
Condensation and frost protection
Setting up the function (1/2)

Condensation protection Frost protection

• OFF1: enables condensation protection • OFF1: enables frost function


• OFF3: OFF3 disables the condensation protection function • OFF3: OFF3 disables frost protection function
• OFF2/fault: the motor stops and the condensation protection • OFF2/fault: the motor stops and the frost protection function is
function is deactivated deactivated

OFF1: OFF1 ramp, OFF2: pulse suppression, OFF3: quick stop (OFF3 ramp)
Unrestricted © Siemens 2020
Page 87
Condensation and frost protection
Setting up the function (2/2)

Protection enabled
Frost Description Param.
p29622 = 1 & p29623 ≠ 0
protection Sets the signal source to enable.
Frost / cond. value • If p29622= 1, protection is initiated
&
• If the converter is stopped and
Converter p29623 = 0 Condensation p29622= 1, protection is applied as
is stopped protection BI: Frost/ follows:
p29624 ≠ 0
condensation - If p29623 ≠ 0, frost protection is
p29622
protection activated by applying the specified
Before enabling the condensation and frost protection: enable speed to the motor;
- If p29623 = 0, and p29624 ≠ 0,
p0840 = r29659.0; p1143 = r29640.0 condensation protection is activated
p0844 = r29659.1; p1144 = r29641
by applying the specified current to
p0840 BI: ON / OFF (OFF1) the motor
p0844 BI: No coast-down / coast-down (OFF2) signal source 1 In rpm, specifies the speed applied to
Frost protect.
p1143 BI: Ramp-function generator, accept setting value the motor when frost protection is p29623
speed
p1144 CI: Ramp-function generator setting value active
r29659 CO/BO: Command status is for ON/OFF1, OFF2 Condensation = 30% (factory), specifies the DC
r29640 CO/BO: shows actual output of the extended setpoint channel sel.
protection current as % of rated current applied to p29624
current the motor
r29641 CO: Extended setpoint channel setpoint output [rpm]

Unrestricted © Siemens 2020


Page 88
Cavitation protection
Keeps cavitation damage away

Feature / Function

The impeller from the pump can be damaged by


little bubbles which are generated by the pressure
gap when the pump is running at high speed and
the water can not be supplied as required.
Available head of water

The cavitation protection generates a warning


when cavitation pressure thresholds are
Required head of water

reached. If the inverter gets no feedback from the


pump transducer, it will trip to prevent cavitation
damage.

Note: cavitation protection depends on the internal


PID controller of the drive.

Warning Related parameters: p29625.. p29627

Stop

Cavitation is the formation of vapor cavities in a liquid,


Unrestricted © Siemens 2020
small liquid-free zones ("bubbles" or "voids")
Page 89
Cavitation protection
Setting up the function

Cavitation protection
Description Param.

Enables and defines the reaction of


cavitation protection.
0= cavitation prot. is deactivated
Cavitation
1= cavitation prot. is enabled and p29625
protection enable
will generate a fault F52960
2= cavitation prot. is enabled and
will generate a warning A52961

Cavitation = 40% (factory), defines the


protection feedback threshold (as %) for p29626
threshold triggering a fault/alarm

= 30s (factory), sets the time for


Cavitation which cavitation conditions have to
p29627
protection time be present before a fault/alarm is
triggered

Unrestricted © Siemens 2020


Page 90
Pump blockage, leakage & dry running protection
Protects the pump from abnormal load situations

Feature / Function
Torque

Warning The inverter can keep track of the speed, current


Blocked
and the torque of the motor to determine
Leakage Stop abnormal load situations:
• Insufficient torque can indicate leakage or dry-
running
Dry run Speed
• Excessive torque (and current) together with
low speed can indicate machine blockage
• Insufficient motor current indicates that the
power transmission from the motor to the load
is interrupted (no load)

Pump monitoring: Fan monitoring:


Load monitoring • Blockage • Blockage
configuration p2193 • Leakage • Torn belt (broken belt)
• Dry running

Unrestricted © Siemens 2020


Page 91
Pump blockage, leakage & dry running protection
Setting up the function (1/3)

Pump blockage, leakage & dry running protection


Description Param.

In rpm, sets the highest possible


Maximum speed for the motor.
p1082
speed Max. speed = Fmax filter / pole pair
number (r0313)

0= U/f ctrl with linear charact.


Open-loop/
1= U/f ctrl with linear charact. & FCC
closed-loop
2= U/f ctrl with parabolic charact.
control p1300
4= U/f ctrl with linear charact. & ECO
operating
7= U/f ctrl for parabolic charact. & ECO
mode
20= Speed ctrl (encoderless)

Setting the load monitoring configuration: Blockage In rpm, sets the upper speed threshold
upper for blockage monitoring of a pump or p2165
0: Monitoring is switched-off threshold* fan
1: Monitoring torque and load drop
Load
2: Monitoring speed and load drop
monitoring p2193 Blockage
configuration
3: Monitoring load drop In Nm, sets the torque threshold for
4: Monitoring pump and load failure torque p2168
blockage monitoring of a pump or a fan
5: Monitoring fan and load failure threshold*

Unrestricted © Siemens 2020 *When using the control mode "U/f control" (p1300 < 10), the "Blockage protection" becomes active when the current limit is reached.
Page 92
Pump blockage, leakage & dry running protection
Setting up the function (2/3)

Pump blockage, leakage & dry running protection


Description Param.
Sets the response when evaluating the
load monitoring.
0= Load monitoring disabled
1= A07920 for torque/speed too low
Load 2= A07921 for torque/speed too high
monitoring 3= A07922 for torque/speed out of tol. p2181
response 4= F07923 for torque/speed too low
5= F07924 for torque/speed too high
6= F07925 for torque/speed out of tol.
7= Pump/fan load monitoring as alarm
8= Pump/fan load monitoring as fault
= 150 rpm (factory), sets the speed/
Speed
torque envelope curve for load p2182
threshold 1
monitoring
= 900 rpm (factory), sets the
Speed
speed/torque envelope curve for load p2183
threshold 2
The monitoring is not active below speed threshold 1 and above monitoring
speed threshold 3

Unrestricted © Siemens 2020


Page 93
Pump blockage, leakage & dry running protection
Setting up the function (3/3)

Pump blockage, leakage & dry running protection


Description Param.
= 1500 rpm (factory), sets the
Speed
speed/torque envelope curve for load p2184
threshold 3
monitoring
Torque In Nm, sets the speed/torque
p2186
threshold 1 envelope curve for load monitoring
Torque In Nm, sets the speed/torque
p2188
threshold 2 envelope curve for load monitoring
Torque In Nm, sets the speed/torque
p2190
threshold 3 envelope curve for load monitoring
Torque In Nm, threshold to identify dry
threshold, no running operation for pumps or belt p2191
load breakage for fans
= 10s (factory), sets the delay time to
Delay time p9192
evaluate the load monitoring

Unrestricted © Siemens 2020


Page 94
Fire mode
Essential Service Mode (ESM)

Feature / Function

During Fire mode, the inverter attempts to


operate the motor for as long as possible
ON (ignoring the OFF signal) despite irregular
set point ambient conditions to improve the air circulation
and survival time on critical situations
Keep fans working to give the
pressure in the stair well to
force the fireproof door close
to reduce the spread of fire
and smoke

Fire
door
The pump system also can use
ESM to keep fire-fighting
system running

Unrestricted © Siemens 2020


Page 95
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 96
SINAMICS G120X
Line side components

AC/DC chokes & line harmonic filters EMC line filters

Used to smooth voltage peaks or to Limit the high frequency conducted


bridge commutating dips. They reduce emissions of drive systems in the
the effects of harmonics on the inverter frequency range (50 kHz – 30 MHz) and
and the line supply. provide a contribution to EMC.

Frame size A B C D E F G H J
SINAMICS G120X IP20
External line reactor - AC choke required
Integrated DC chokes THDi = 39.4% (EN 61000-3-12) -
External Line harmonics filters1 - THDI <5% (IEEE519) -
Integrated EMC filter 400V C2 (EN 61800-3) C3 (EN 61800-3)
External EMC filter 400V C1 footprint (EN-61800-3) (new) C1 (EN-61800-3) - C2 (EN 61800-3)
Integrated EMC filter 690V - C2 (EN 61800-3) C3 (EN 61800-3) C3 (EN 61800-3)
External EMC filter 690V - C2 (EN 61800-3)

Unrestricted © Siemens 2020 EMC: Electromagnetic Compatibility 1


FSG (250 kW/300 HP) with 2x 132 kW connected in parallel
THD: Total harmonic distortion
Page 97
SINAMICS G120X - Line side components
Cable length with/without external options (1/2)

Maximum permissible motor cable length (screened / non screened) in meters 1


Frame size A B C D E F G H J
SINAMICS G120X 3AC200V
Unfiltered 150/300 200/300 300/450 -
SINAMICS G120X 3AC400V
Unfiltered 150/300 200/300 300/450 150/200
External C1 filter EN61800-3 50/- 502/- - - -
Integrated C2 EN61800-3 150/- 150/-3 150/- - -
Integrated C3 EN61800-3 150/- 200/- 150/-4
External C2 filter 150/-
External C3 with UF drive 50/- - -

Unrestricted © Siemens 2020


1
The values apply to a pulse frequency at the factory setting 3
2 kHz pulse frequency for FSF 75 kW and 90 kW
2
Additional installation of ferrite sleeves is required 4
For lengths of 100 -150m w. add. basic interference suppression module (on request) –
Page 98
Article-No A5E03378158
SINAMICS G120X - Line side components
Cable length with/without external options (2/2)

Maximum permissible motor cable length (screened / non screened) in meters 1


Frame size A B C D E F G H J
SINAMICS G120X 3AC690V
Unfiltered - - - 200/300 300/450 150/200
Integrated C2 EN61800-3 - - - 100/- - - - -
Integrated C3 EN61800-3 - - - 150/- 150/-4
External C2 filter 150/-
External C3 with UF drive - - - 50/- - -

The values apply to a pulse frequency at the factory setting


1 3
2 kHz pulse frequency for FSF 75 kW and 90 kW
Unrestricted © Siemens 2020 2 Additional installation of ferrite sleeves is required 4
For lengths of 100 -150m w. add. basic interference suppression module (on request) –
Page 99 Article-No A5E03378158
SINAMICS G120X offers the line harmonic filter FN3440 from
Schaffner as an option to reach IEEE519 <5%

Used with G120X

Schaffner series of line harmonic filters


FN 3440 FN 3441 FN 3450 FN 3451 FN 3452 FN 3453
For 6-pulse diode rectifier
Yes   Yes   Yes  
without DC-link choke

For 6-pulse diode rectifier with


  Yes   Yes   Yes
8% DC-link choke
For SCR1 rectifier Yes   Yes   Yes  
Operating frequency 50 Hz 50 Hz 60 Hz
Nominal operating voltage 3x 380 to 415V AC 3x 440 to 500V AC 3x 440 to 480V AC

Frequent questions: 1
SCR: Silicon-Controlled Rectifier

1. Why do we use FN 3440 and not FN 3441?


Because our 6 pulse rectifier has a 3% DC link choke
Unrestricted © Siemens 2020
Page 100
FN3440 line harmonic filter:
Article number structure

G120X Power rate HAWA3 Article number


5.5 kW (7.5 HP) UAC: FN3440 6 112 E2 XXJRX
FSB UAC: FN3440 8 112 E2 XXJRX
7.5 kW (10 HP)
UAC: FN3440 11 113 E2 FAJRX
Legend:
11 kW (15 HP)
FSC UAC: FN3440 15 113 E2 FAJRX
15 kW (20 HP) ### Power rating in kW (HP)
18.5 kW (25 HP) UAC: FN3440 19 113 E2 FAJRX
22 kW (30 HP) UAC: FN3440 22 115 E2 FAJRX ### Terminal designation
FSD UAC: FN3440 30 115 E2 FAJRX
30 kW (40 HP)
E2 for IP20
37 kW (50 HP) UAC: FN3440 37 115 E2 FAJRX
45 kW (60 HP) UAC: FN3440 45 115 E2 FAJRX F with fan
FSE UAC: FN3440 55 115 E2 FAJRX X without fan
55 kW (75 HP)
75 kW (100 HP) UAC: FN3440 75 116 E2 FAJRX A with power supply
90 kW (125 HP) UAC: FN3440 90 116 E2 FAJRX X without power supply
FSF UAC: FN3440 110 118 E2 FAJRX
110 kW (150 HP)
J with trap disconnect jumper
132 kW (200 HP) UAC: FN3440 132 118 E2 FAJXX
160 kW (200 HP) UAC: FN3440 160 118 E2 FAJXX 1) R with RC damper
FSG 200 kW (250 HP) UAC: FN3440 200 118 E2 FAJXX 1) X without RC damper
250 kW (300 HP) 2x UAC: FN3440 132 118 E2 FAJXX 1) 2)
1)
Only operation in "Vector control" mode is permitted. "U/f control" mode is not permitted.
2)
Parallel connection between two Line Harmonics Filters of 132 kW each.

Unrestricted © Siemens 2020


Page 101
SINAMICS G120X
Load side components

Output reactor Sinusoidal filter (sine wave) Dv/dt Filter plus VPL

• Reduces the voltage stress on the • Limits the rate of rise of voltage and • Limits the voltage rate-of-rise and the
motor windings. the capacitive currents. typical voltage peaks according to the
• Enables long motor cable applications • Supplies almost perfect sinusoidal limit value curve to IEC/TS 60034-17.
by reducing capacitive currents. voltages so that standard motors can
be used without special cables.

Frame size A B C D E F G H J
SINAMICS G120X 3AC
Output reactor 400V - E
Sinusoidal filter 400V E (new) E -
Dv/dt Filter plus VPL 400V - E
Output reactor 690V - E
Sinusoidal filter 690V -
Dv/dt Filter plus VPL 690V - E

Unrestricted © Siemens 2020 VPL: voltage peak limiter E = External placement


Page 102
SINAMICS G120X - Load side components
Cable length with/ without external options

Maximum permissible motor cable length (screened / non screened) in meters


Frame size A B C D E F G H J
SINAMICS G120X 3AC400V
Unfiltered 150/300 200/300 300/450 150/200
Output reactor
- 350 / 525 525 / 800
Dv/dt Filter plus VPL 300 / 450
Sinusoidal filter 200 / 300 200 / 300
SINAMICS G120X 3AC690V
Unfiltered 200 / 300 300 / 450 150 / 200
Output reactor -
350 / 525 525 / 800 300 / 450
Dv/dt Filter plus VPL

Unrestricted © Siemens 2020


Page 103
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

3.1 System overview

3.2 Components

3.3 Functions

3.4 Options

3.5 Tools

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 104
The SINAMICS G120X is implemented in a complete range of
tools for easy selection and configuration

Available tools Status

Project 03/2020 Enables network calculation Simaris


SIMARIS
Design 10/2020 and dimensioning
DT- Configurator
Allows efficient selection and
DT-C Yes configuration of your drive  SIZER / TST
updated

SinaSave
V3.19  Supports step-by-step configuration of
SIZER the mechanical system
V4/ TST SINAMICS Selector App

Determines energy saving potential


SinaSave 2021 and ROI of your application SINAMICS QR code

SINAMICS Allows quick and easy selection of


Yes inverters on your mobile
Selector App

QR code Allows fast & convenient product


Yes identification for support services
for Support

Wide range of tools allow easy selection and configuration of the drive system
Unrestricted © Siemens 2020
Page 105
The G120X is now included into SIMARIS project and design
to assist electrical planners in working faster and better

!!
NE W SIMARIS project
for determining the space
requirements of distributing
systems and the budget as
well as creating technical
specifications

!!
E W SIMARIS design
N facilitates electrical network
planning, including short-
circuit current calculation
and network dimensioning

Unrestricted © Siemens 2020 Available to download now: www.siemens.com/simaris/download


Page 106
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 107
SINAMICS G120X top 5 highlights include seamless,
cost efficient, robust, time saving and digitalization features

Seamless,
• Wide power and voltage range = 0.75 kW … 630 kW/1 ... 700 HP SINAMICS G120X
• 1 Article number = Fast and simple to order, runner types on
simple, stock
time saving • Out of the box = Easy handling

• DC-link choke = No external input chokes


Cost efficient • Long cable lengths = Reduced need for output chokes
• Energy efficiency solutions in focus (G120X+RSM)

• 3C3 coating = Operation under harsh environments


Robust • Integrated DC- Link choke enhances grid/device protection
and reliable
• Safety functions = STO SIL3 functionality
G120X FSC, IP20 with SAM
UL open type

Dedicated • DT-Configurator/SSAPP = Improved selection, incl. bidding text


to segments • Firmware = dedicated features e.g. Deragging, Multi Pump Control

• SINAMICS connect for cloud based analytics


Fit for • Smart Access Module comfortable setup and diagnostics
digitalization • Communication via PROFINET, PROFIBUS, Modbus RTU,
BACnet G120X FSA .. J, IP20
RSM Reluctance Synchronous Motor | SSAP SINAMICS Selector APP UL open type
RSM: Reluctance Synchronous Motor
Unrestricted © Siemens 2020
SSAP: SINAMICS Selector APP
Page 108
SINAMICS G120X
Top highlights – Water market

Ease of use / maintain Connectivity and integration

• Out-of-the-Box: ready to switch on • PROFINET, PROFIBUS and Modbus as a standard


• User friendly interfaces • Easy and simple integration
• One supplier - one system responsibility • Segment specific drive based functionality to preserve facilities (e.g.
deragging mode)
• Support of PCS7 systems
(with the G120X FDI package + SIMATIC PDM)

Reliable, flexible & efficient Tailored for the water industry

• Integrated drive protection • Use in 1st and 2nd environment applications


• Fit for W/WW grids • Several protection degrees to be used w/o. cabinets
• Operation in harsh environments / 3C3 coating • Emergency STOP via STO SIL3 HW capability as a standard
• Flexible operation with different motor types • Segment specific overload characteristic + power boost
• Long cable lengths ensuring EMC compliance

Unrestricted © Siemens 2020


Page 109
SINAMICS G120X
Top highlights – HVAC market

Ease of use Connectivity and integration

• Out-of-the-Box: ready to switch on • Modbus RTU, BACnet MS/TP, USS as a standard


• Easy diagnostics • Easy and simple commissioning via panel/SAM
• One supplier – one system responsibility • Specific drive based functionality like “Fire Mode”
• Real time clock for control and diagnostics with time stamps

Reliable, flexible & efficient Tailored for HVAC applications

• Limited harmonics level ( IEC 61800-3-12 ) • Several protection degrees to be used w/o. cabinets
• Flexible operation w. different motor types • EMC conformity C1 + C2
• Efficient “self adapted” P&F operation • Emergency STOP via STO SIL3 HW as a standard

Unrestricted © Siemens 2020


Page 110
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 111
SINAMICS G120X
Power Electronic

Topology SINAMICS G120X


Design
The power electronic consist of
• a 6 pulse rectifier with diodes
• an integrated dc choke
• a DC link circuit with electrolytic capacitors
• a pulse inverter with IGBTs for the motor control
Advantages
• The integrated dc choke limits the height of the charging
current, further on the harmonic currents are limited in a way as
with a converter with a 4% ac choke
• The power factor  amounts to almost 0.9, so that only little EMC
reactive power is received • THDi = 39.4%, PWHDi = 33.9%
Output voltage • Compliance with EN61000-3-12 for a RSC > 120
• Compliance with category C2 acc. EN 61800-3 for a cable length
Output voltage approx. 96% (HO), 96% (LO) of 150m
Output power
• The output current is constant in a way that HP values according
NEC at 3 AC 480V are met

RSC: short circuit ratio THDi : total harmonic distortion


Unrestricted © Siemens 2020 PWHDi: partial weighted harmonic distortion
Page 112
SINAMICS G120X
DC choke in the frequency converter

Reduction of harmonics on the line side


Without choke With AC choke With DC choke

THC/Iref = 90.7% THC/Iref = 50.5% THC/Iref = 39.4%


PWHC/Iref = 37% PWHC/Iref = 20.1% PWHC/Iref = 33.9%
Cos phi = 0.99 Cos phi = 0.98 Cos phi = 0.99
λ= 0.73 λ= 0.87 λ= 0.92

THC = total harmonic current 2 ≤ n ≤ 40 Cos phi = offset factor


PWHC = partial weighted harmonic current 14 ≤ n ≤ 40 λ = power factor
Unrestricted © Siemens 2020
Page 113
G120X is implemented in SIZER V3.19

Unrestricted © Siemens 2020


Page 114
Calculation of Harmonics
Schaffner

PQS Power Quality Simulator

• PQS is a Power Quality Simulation tool for planners,


consultants and application engineers
• It enables the accurate modelling and simulation of
low voltage 3-phase network topologies
• Simulation of power, current and voltage at all network
nodes
• PQS supports the proper selection of harmonics
mitigation technologies
• The tool verifies the compliance with selected power
quality standards
• It provides comfortable reporting features
• Particularly suitable for systems with variable speed
drives

https://siemens-product-partner.schaffner.com/tools-and-ti
ps/
Unrestricted © Siemens 2020
Page 115
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 116
The specialized solution for midrange
W/WW & HVAC applications

Pumps Fans / building auto. Chillers


HVAC

• Pump operation on • Centrifugal / axial fan operation for • Operation of chillers on


- Heating systems, - Air conditioning systems and
- Air handling units, roof top units
- Water supply of buildings - Refrigeration technology
- Pressure booster stations - Air exhaust systems, tunnels, garages
- Cooling water systems - Refrigeration

Secondary
Pumps Blowers
processes
Water/WW

• Radial and axial pump operation in water • Efficient operation and control of blowers • Pump & fan systems to support industrial
segments: supply, treatment, wastewater, e.g. to control the oxygen level in WW processes such as boiler feed water, ventilation,
transfer and irrigation, well pumps, treatment processes saltwater injection, dust collection, water
transfer, fume control, water supply, etc.
centrifugal pumps, ….

Unrestricted © Siemens 2020


Page 117
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 118
The new 16 digit article number structure makes
the G120X easier to order

New ordering method Out-of-the-Box

Article number Customer

6 S L 3 2 x x - x Y x x x - x x x 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Ready
to switch on!
Digit Description Options
6 Coating type ( 3C2 / 3C3 ) Standard 3C2, Enhanced 3C3 coating
Protection class (opt.
7 IP20/UL open type
service switch)
8 User interface Blank; BOP-2; IOP-2

10 Voltage class 3AC200V -240V; 3AC380V-480V; 3AC 500V-690V

11
Power range 0,75KW … 630KW / 1 … 700HP
12

13 I / O extension With ; Without

14 EMC class UFi, FiA, FiB SINAMICS G120X is ready out


15 Communication Interface PN, PROFIBUS DP; Modbus+BACnet MS/TP+USS of the box
Unrestricted © Siemens 2020
Page 119
The new 16 digit article number makes
the G120X easier to order
HP2
Key kW
(400V)
16 2.2 3
18 3 4
20 4 5
22 5.5 7.5
24 7.5 10
26 11 15
28 15 20
30 18.5 25
32 22 30
34 30 40
36 37 50
38 45 60
40 55 75
42 75 100
44 90 125
46 110 150
48 132 200
50 160 250
52 200 300
54 250 400
56 315 -
58 355 450
60 400 500
62 450 -
64 500 600
66 560 700
68 630 -
1
C2: FS A-G; C3: FS F-J 3
In preparation
Unrestricted © Siemens 2020 2
400V
Page 120
Deliver fast to our customers –
Target values for ramp up products

Europe

Make-to-Stock
3-5 days
Make-to-Order Asia
8-10 days
Make-to-Stock
SINAMICS G120X 3-15 days

Americas Make-to-Order
Make-to-Stock Parts 10-15 days
Make-to-Stock • SINAMICS G120X: 0.75 kW –
3-15 days 132 kW, 400V, 3C2, IP20, PN,
IOP-2, UF/F SINAMICS G120X
Make-to-Order *FSD and above only UF
10-15 days

SINAMICS G120X
All delivery times may vary due to specific country policies
Unrestricted © Siemens 2020
Page 121
Agenda

1 General

2 Positioning in portfolio, system integration

3 Product

4 Value-added topics

5 Harmonics calculation

6 Applications and references

7 Ordering data and selection

8 Service support and documentation

Unrestricted © Siemens 2020


Page 122
Service Protect
Unique in the market SINAMICS G120X with 7 ½ ext. warranty

Siemens Service-Offering
With Service Protect you will receive a product exchange or repair in a service case within
the contract period.
Customer’s drivers and goals
+ 3 years
NEW Extended coverage
Ensure availability Standard + 6 month
Warranty FOC with Product
24 month Registration
Reduce costs + 5 years
Extended coverage

Optimize Asset Management Register your drive and receives an initial 6 month free of charge (FOC) extended coverage
via https://myregistration.siemens.com/

Customer benefits
• Safeguard your investment for an extended period
• Ongoing support by Siemens service experts throughout the entire product lifecycle
• Opportunity to cover the SINAMICS drive for up to 7 years + ½ via the product registration

Unrestricted © Siemens 2020


Page 123
SINAMICS G120X
Documentation

Pages per
Content overview Languages Delivery
document

G120X
HW + FW +++
Operating instructions

IOP-2
Installation + wizards ++
Operating instructions

G120X Installation + quick


+
Getting started commissioning

Protective devices UL and IEC protective


+
product information functions

Hardware/spare options
Mounting +
Compact inst. instructions

Download Printed
Unrestricted © Siemens 2020
Page 124
SINAMICS G120X
Supporting Material

Documentation Training Material Tools & Selection Info & Promotion Service & Support
• Technical Slides • Demo cases • Catalogue • Sales Slides • Industry
• Operating instruction • Standard application • DT-Configurator • Water Online Support world
s examples • SIZER • HVAC wide
• Getting started • Tutorial videos • SinaSave1 • Brochures • Industry Online Supp
• Protective devices • Unboxing + SAM tutorial • Simaris • Starter kits ort App
product information • SSAPP • G120X Website • Technical Support Re
• Compact inst. quest
• Image database
instructions • DAM
• Industry Mall

1
Available during 2021
Unrestricted © Siemens 2020
Page 125
SINAMICS G120X
The seamless pump and fan drive

www.siemens.com/sinamics-g120x

Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may
not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
All product designations, product names, etc. may contain trademarks or other rights of Siemens AG, its affiliated companies or third parties.
Their unauthorized use may infringe the rights of the respective owner.

siemens.com

Unrestricted © Siemens 2020