How to service & prevent for Multi V IV Oil Pipe Liquid Seal
Application date 02. 11. 2015.
Overview

■ Subject : How to service Multi V IV Oil Pipe Liquid Seal


(caused by EEV abnormal operation or internal blockage)
■ Applied Model : ARUB180LTE4, ARUN180LTE4, ARUB200LTE4, ARUN200LTE4
■ Applied S/No : 2013(From 306KA~ to 312KA~)
※ TB was published by the existing A-127 is re-issued with the P/No change(page.2,3)
Content

1. Liquid Seal?
-. Liquid Oil & Ref. gas Trapped in closed pipe section.
-. In case of rapid Temperature raise, It make huge pressure inside.
-. In case of Multi V IV Oil pipe`s EEV failure, liquid seal could happened .
Oil pipe circuit diagram Oil pipe in detail

Oil EEV
Strainer High Pressure
ref. with oil

Check Valve

Oil equalization circuit Liquid seal could happen


on this pipe

2. Cause of Liquid seal:


-. EEV abnormal operation or EEV internal blockage

3. Applied Model & S/No ( Multi V IV 2Comp. Model)


-. Applied Model : ARUB180LTE4, ARUN180LTE4, ARUB200LTE4, ARUN200LTE4
-. Applied S/No : 2013(from 306KA~ to 312KA~)
Content

4. Service guide for oil pipe damage


1) Since Jan 2014, Oil pipe EEV assembly has by-pass capillary tube to prevent liquid seal.
By-pass capi. release & prevent abnormal high pressure rise in case of EEV failure.

2) In case of Oil pipe damage for Multi V IV 2 comp 2013 product,


replace damaged Pipe and New EEV Assembly.
- EEV assembly(SVC Loc No : 552200E) : New SVC Part(AJR74488601)
- Pipe assembly(SVC Loc No : 352111B) : AJR73964301
- If necessarily, change check valve and check valve upper connector
Check Valve(P/No : 5220A30004A)
Check Valve Upper Pipe (P/No : MJU64912701)

EEV Assy on Exploded View

Bypass Capi.

AJR74488601

※ changed P/No

MJU64912701
5220A30004A
Content

5. Preventive Setting to avoid oil pipe damage


1) Multi V IV 2 comp 2013 product, it can have bypass effect by SW & Dip switch setting.
This setting oil EEV fixed on 200pls so it always has some amount of Ref. bypass.
Before : EEV 70pls (compressor on), Fully open ( compressor off)
After : EEV 200pls always. It allow 24L/min(0.1Mpa pressure) bypass
※This setting recommended when start up for Multi V IV 2comp. 2013 production
as preventive action.
2) How to set
Step1. Main PGM on boarding
Heat Pump : testSuper4_controlOilEEV200_141114.mot
Heat Recovery : svcSync4_ver14.1_OilEEVCtrl200_141112a.mot
Setp2. Outdoor PCB Dip switch setting
Put all Dip s/w
System Stop PCB Reset
Slave down
Master Unit
Unit
After 1min.
Wait 1min. for EEV normal positioning
Put Dip #5 up

Set the menu to


“SVC”
With “◀” &“▶” then push “◎” button.
Heat Pump /
Set the menu to With “◀” &“▶” then push “◎” button. Heat Recovery model:
“SE11” Displayed current pulse Same “SE11”

Set the target With “◀” &“▶” then push “◎” button.
pulse(20) The number means the target pulse divided by 10
Target Pulse : 200 pulse

Wait 1min. for


EEV moving

Step3. Check movement with LGMV (option)


- During 30 sec, the EEV stays at 40pulse then increase as 200pls in 30sec
Step4. Remove Oil EEV cable on External PCB to fix EEV on 200pls
- When power reset, external PCB do EEV initialization operation.
This operation do EEV full close & open again, so it needs to disconnect to fix EEV position.
Step5. Put Dip #5 down. and Main PCB reset
- If It was slave unit, before reset pcb dip s/w must go back to original position.
★Do not PCB reset before remove Oil EEV cable on External PCB.
Remove Oil EEV connector on External PCB
Content

■ PCB On-boarding Manual

1-1 On-boarding Tool 1-2 On-boarding Process


1. Connect Jig : PC  USB To
RS232 Cable  Jig Box Cable
1. Computer
 PCB
2. USB To RS232 Cable
3. Jig Box
4. Main Controller Connect Cable
5. Short Key

CN_CNVSS CN2

Main Micom Short Key : CN2


Main Micom On-Boarding Port : CN_CNVSS

2. Connect ‘Short Key’


3. Check LED Lamp ‘off’ after ‘Reset
button’ Click
4. Run On-Boarding Program
5. Remove ‘Short key’ after completing
On-Boarding
6. Check LED Lamp ‘on’ after ‘Reset
Button’
Content

1-3 On-boarding Install Program


3. ‘Next’ Click
Files needed for on-boarding are two

1. Setup_fdt4.9.exe(Like Main PCB to External PCB)


 On-Boarding Install File

Check!!
2. Cycle.fpf4
 Main PCB On-Boarding Running File
4. ‘Next’ Click

1-4 Program Installation and Operation

FDT 4.90 Install


1. setup_fdt4.9.exe Click

2. ‘Next’ Click
5. ‘Next’ Click
Content

6. ‘Next’ Click 9. ‘Finish’ Click

On-Boarding Program Run


7. ‘Next’ Click Check!!
Main PCB : cycle.fdf4

Check!!

Main Device Check ‘R5F64112’

8. ‘Next’ Click
Content

1-5 On-Boarding Trouble Guide


3. Open On-Boarding File(.Mot)

1. Error No 15024 : Boot failed

 Check Connecting On-


Boarding Cable
 Check Short key and LED Off
 Check Main Power

4. Program Flash Click 2. Error No 16194 : ID code check


failure

 Check Device
Main : R5F64112

 Run correct Running file

3. Error No 15060 : Error while


opening the port
5. On-Boarding finish (Check
Verification)

 COM Port used Other


Program

4. LED off after On-Boarding


 Click ‘Reset Button’ after remove ‘Short
key’
5. LED off after remove short key
 Check Main /Sub Micom and Re-
Onboarding

You might also like