You are on page 1of 40

TRANSFORMER PROTECTION

07/19/22 M L SHESHADRI 1
• INTRODUCTION
• Power transformer is a vital link in power
system. Therefore we have to have a reliable,
secured and fast acting protection system for
the transformer. This will minimize the
damage to the transformer in case of internal
fault. The protection system should also have a
proper backup protection scheme to take care
of un-cleared system fault.

07/19/22 M L SHESHADRI 2
 TYPES OF FAULTS IN TRANSFORMER
 Phase to ground faults and phase to phase
faults.
 Inter turn faults
 Core faults 
 Phase to ground faults and phase to phase
faults:
 The magnitude of the fault current mainly
depends on the source impedance, type of
earthing, location of the fault etc., Phase to
phase faults are however rare

07/19/22 M L SHESHADRI 3
 TYPES OF FAULTS IN TRANSFORMER
 Inter turn faults:
 Most of the transformer failures are due to
inter turn fault. Transformers are subjected to
impulse voltages like switching transients
which will be several times more than its rated
voltage. This results in failure of insulation
between the turns. Current in the short
circuited winding will be very high compared
to the terminal current.
07/19/22 M L SHESHADRI 4
 TYPES OF FAULTS IN TRANSFORMER
 Core faults:
 A conducting bridge across the laminated
structure of the core will result in increase in
eddy currents and increase in core
temperature. This finally may result in
deterioration of oil or winding insulation
resulting in failure of transformer. In oil filled
transformers this type of fault is detected by
carrying out Dissolved Gas Analysis. If the
problems become more serious the gas evolved
will operate protective device like Bucholtz
relay and Pressure relief device.
07/19/22 M L SHESHADRI 5
 Source of abnormal stress in a transformer
  The source of abnormal stress in transformers is
 Overload
 System faults
 Over voltage / reduced system frequency 
 Overload:
 It causes increase in copper loss, which results in
increase of winding temperature. If the transformer is
overloaded continuously, the oil gets deteriorated
resulting in reduced insulation and other consequence
thereafter. It is the temperature rise that decides how
long we can overload the transformer and there should
be proper cooling of transformer oil.
07/19/22 M L SHESHADRI 6
• Source of abnormal stress in a transformer
• Over voltages:
• Transient over voltages results in inter-turn faults.
Power frequency over voltages results in increase of
iron losses due to over fluxing and stress on insulation
will also increase. Over fluxing will result in heating of
core bolts and failure of its insulation. This causes more
losses due to short - circuiting of eddy current path. 
• Reduced system frequency:
• This will have similar effect as that of over voltage and
results in increase of flux. Therefore the transformers
should not be operated at high voltages and low
frequencies. 

07/19/22 M L SHESHADRI 7
• PROTECTION TOOLS FOR TRANSFORMERS

• To protect the transformers from the above-mentioned


faults, following protection and safety devices are
used.
• The degree of protection schemes depends on
application, voltage and MVA ratings. 

• Surge diverters (Lightning Arresters)


• Circuit breakers
• Over-current and Earth fault relays (Directional/non
directional) for HV/LV
• Differential relay
• Restricted earth fault relay (HV/LV)
• Over fluxing relay
• Bucholtz relay
07/19/22 M L SHESHADRI 8
• PROTECTION TOOLS FOR TRANSFORMERS

• Oil and winding temperature indicators


• Oil surge protection for OLTC
• Pressure relief valve for main tank
• Oil level indication
• Protection of tertiary winding (OCR/EFR)
• Monitoring of insulating system (Oil/Paper)
• Capacitance and Tan-delta (DDF) monitoring of
bushing and windings. 
07/19/22 M L SHESHADRI 9
07/19/22 M L SHESHADRI 10
•  PROTECTION TOOLS FOR TRANSFORMERS

• Backup directional over current and earth fault relays


both on HV and LV side of the transformer.

• These relays are provided on either side of the


transformer. It will have IDMT characteristic. It will
also have high set instantaneous unit. The current
setting should be set above expected maximum load
current (To take care of possible over load of the
transformer on account of loss of one of the parallel
transformer). 

07/19/22 M L SHESHADRI 11
• PROTECTION TOOLS FOR TRANSFORMERS

• Differential protection: This protection takes


care of transformer internal faults. Generally bay
CT's are connected to this protection. The relay
should have proper restraint characteristic such
that it will not operate for inrush current during
charging. Instantaneous over current element,
adjustable bias settings, and harmonic current
restraints are the other features of this relay.

07/19/22 M L SHESHADRI 12
PROTECTION OF TRANSFORMERS
 Difficulties in Differential protection
 As the pilot wire lengths of CTs are not the
same due to location of CTs on either side of
the transformer to obtain a equipotential point
on pilot wires becomes difficult.

 To over come this problem adjustable resistors


in series with pilot wires are introduced and is
adjusted at site.

07/19/22 M L SHESHADRI 13
PROTECTION OF TRANSFORMERS
 Difficulties in Differential protection
 CT ratio errors during short circuits occur
during short circuits due to inherent CT
characteristics differences arising out of
magnetic circuits, saturation conditions and
unequal dc components in the short circuit
currents. This may result in operation of relay
even for external faults.

 To overcome this difficulty, the percentage


differential relay, or biased differential relay is
used.
07/19/22 M L SHESHADRI 14
PROTECTION OF TRANSFORMERS
 Magnetising inrush current

 When the transformer is energised a large current (6 to


10) times the normal current will rush through the
winding and differential relay may operate though
there is no fault in the transformer.

 This difficulty is overcome by providing harmonic


restraint to the differential relay. The magnetising
current contain a large content of several harmonics
and this is utilised for obtaining restraining torque
during switching in of the transformer.

07/19/22 M L SHESHADRI 15
PROTECTION OF TRANSFORMERS
 Difficulties in differential protection

 Tap changing causes change in transformation


ratio of a transformer. Thereby the CT ratios do
not match with the new tap settings, resulting
in current in pilot wires even during healthy
condition.

 This is taken care of by the biased differential


relay.
07/19/22 M L SHESHADRI 16
TRANSFORMER PROTECTION

07/19/22 M L SHESHADRI 17
07/19/22 M L SHESHADRI 18
PROTECTION TOOLS FOR TRANSFORMERS

 Restricted earth fault protection: This


protection is also meant for internal fault of
transformer. External CT's are connected in
Neutral Circuit to this protection. Its minimum
operating sensitivity will be 10 % of the
nominal current. The relay may be high
impedance or low impedance type.  

07/19/22 M L SHESHADRI 19
07/19/22 M L SHESHADRI 20
07/19/22 M L SHESHADRI 21
07/19/22 M L SHESHADRI 22
•  PROTECTION TOOLS FOR TRANSFORMERS

• Over fluxing protection:

• This relay is phase to phase connected. It operates on


the principle of measurement of voltage to frequency
ratio. It will have inverse time characteristic and it
should be compatible with transformer over fluxing. It
provides an independent alarm with a definite time
delay. v/f settings available are between 100 % to 130
% of rated value. To take care of all possible operating
conditions it is recommended to connect this relay on
both side of the transformer. In some case where only
one relay is provided it is connected on the untapped
winding. 

07/19/22 M L SHESHADRI 23
•   PROTECTION TOOLS FOR TRANSFORMERS

• Protection of tertiary winding


• Depending on the method of bringing out the tertiary terminal protection
is to be decided i.e. OCR / EFR relays.

• Mechanical protections (transformer mounted)


• Bucholtz Relay / pressure relief device will protect the transformer when
gases are released due to fault in the transformer.
 
• In addition to the above tripping relays, the following annunciation relays
are provided for the transformer.
• a. Bucholtz alarm
• b. Oil level low alarm.
• c. Oil/winding temperature high alarm.
• d. Unhealthy power supply for cooling system alarm.
• e. Fan/pump failure alarms.

07/19/22 M L SHESHADRI 24
PROTECTION OF TRANSFORMERS
BUCKHOLTZ RELAY

07/19/22 M L SHESHADRI 25
07/19/22 M L SHESHADRI 26
PROTECTION OF TRANSFORMERS
 TEMPERATURE

Temperature monitoring protection:

Oil and winding temperature monitors are provided


with stage operation for alarm and trip circuit. In case
of higher capacity transformer, auto start of fans and
pumps are initiated from the two stages provided
additionally.

07/19/22 M L SHESHADRI 27
PROTECTION OF TRANSFORMERS

07/19/22 M L SHESHADRI 28
07/19/22 M L SHESHADRI 29
PROTECTION OF TRANSFORMERS
 PRESSURE RELIEF VALVE
 The pressure relief valve plays a significant
role in the protection of power transformer. A
major fault inside the transformer result in
immediate vapourisation of the oil resulting in
rapid build up of gaseous pressure. The
pressure must be released within few
milliseconds to avoid tank rupture.
 A pressure relief valve is the remedy to the
above situation.
07/19/22 M L SHESHADRI 30
PROTECTION OF TRANSFORMERS
PRESSURE RELIEF VALVE

07/19/22 M L SHESHADRI 31
07/19/22 M L SHESHADRI 32
PROTECTION OF TRANSFORMERS
MAGNETIC OIL LEVEL GAUGE

07/19/22 M L SHESHADRI 33
07/19/22 M L SHESHADRI 34
PROTECTION OF TRANSFORMERS
 BREATHER

07/19/22 M L SHESHADRI 35
PROTECTION OF TRANSFORMERS
THERMO SYPHON FILTER

07/19/22 M L SHESHADRI 36
07/19/22 M L SHESHADRI 37
PROTECTION OF TRANSFORMERS
AIR CELL

07/19/22 M L SHESHADRI 38
PROTECTION OF TRANSFORMERS- DIELECTRIC
DISSIPATION FACTOR

07/19/22 M L SHESHADRI 39
 Take care of the protection system

07/19/22 M L SHESHADRI 40

You might also like