Professional Documents
Culture Documents
To cite this article: Takahiko Miyazaki, Bidyut Baran Saha & Shigeru Koyama (2016):
Analytical Model of a Combined Adsorption Cooling and Mechanical Vapor
Compression Refrigeration System, Heat Transfer Engineering, DOI:
10.1080/01457632.2016.1195135
To link to this article: http://dx.doi.org/10.1080/01457632.2016.1195135
Refrigeration System
2
Program for Leading Graduate School, Green Asia Education Center, Kyushu University, Japan
ABSTRACT
reduce the consumption offossil fuels for air-conditioning by utilizing waste heat. Performance
predictions of combined adsorption and mechanical vapor compression systems require detailed
dynamic modeling because the transitional characteristics explain the nature of the adsorption
system. It is, however, desireable to simplify the model for practical use at engineering stages.
Since the mechanical vapor compression system is based on the steady state thermodynamic cycle,
a semi-steady state modeling of adsorption cycles would be functional for analysis of combined
systems. In our study, the analytical solution of transient simulation for adsorption cycles was
combined with the steady state mathematical model of the mechanical vapor compression system.
The performance of the combined system was analyzed based on the model developed with taking
into account the cycle time of the adsorption cycle. The results show the performance
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
Kyushu University, 6-1 Kasuga koen, Kasuga 816-8580, Japan. E-mail: tmiyazak@kyudai.jp
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
INTRODUCTION
Adsorption cooling systems provide cooling effect with utilization of low-grade thermal
energy such as solar thermal energy and industrial waste heat. The energy saving potential is
enormous when this kind of thermal energy is abundant. On the other hand, an adsorption system
tends to be bulky and it requires a large amount of heat input due to low coefficient of
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
Despite that a number of advanced adsorption cycles [1-3] have been proposed for
designed as conventional two-bed configuration and usually one of the simplest heat recovery
technique is applied to them [4]. The main reason for manufacturers to hesitate to use advanced
cycles would be the cost. To realize many of advanced cycles, it is necessary to employ multibeds
and complex pipework. In addition, a sophisticated automatic control system has to be used to
make the system work at the optimal conditions. Therefore, the increment of manufacturing cost
one of the reasonal options to facilitate the application of adsorption cycles to small to medium
scale applications, such as automobiles, houses and commercial buildings. The hybrid system will
be well-matched with mechanical power driven air conditioners, gas engine heat pumps, and
cogeneration systems, and the system effectively reduces the fossil fuel consumption of the vapor
compression cycle by using waste heat. In these applications, the cooling capacity of the
adsorption cycle can be relatively small because the adsorption cycle will work as an assit of the
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
main vapor compression cycle. Therefore, the size of adsorption heat exchangers can be
minimized, and the additional cost for the adsorption cycle will be curtailed.
A hybrid system using ammonia as refrigerant for both adsorption and mechanical vapor
compression cycles was proposed by Lychnos and Tamainot-Telto [5]. The driving heat source of
the adsorption cycle was the compressor exhaust heat, and the adsorption cycle and the
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
mechanical vapor compression cycle were combined in parallel. In our previous study, the
analysis of adsorption cooling cycle and vapor compression cycle [6]. The reduction of
mechanical compressor power was calculated for two configurations, namely, cascade type and
subcool type.
In the present study, two types of vapor compression-adsorption hybrid cycle were
analyzed mathematically. The adsorption cycle performance was analyzed in semi-setady state,
which was derived from an analytical solution of transient simulation for adsorption cycles. The
performance of the hybrid system was analyzed with taking into account the cycle time of the
adsorption cycle by the integration of the semi-steady state analysis of the adsorption cycle and
the thermodynamic steady state of vapor compression cycle. The paper reports the analytical
model for adsorption cycles and the performance characteristics as well as the energy saving
The schematics of the conventional vapor compression cycle and two types of hybrid cycles are
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
cycle are evaporator, compressor, condenser and expansion valve, as shown in Figure 1a. The
hybrid scheme I is that the adsorptin cooling cycle is used for sub-cooling of the refrigerant
condensate of the vapor compression cycle (Figure 1b). In this scheme, the enthalpy difference in
evaporator is expanded by the sub-cooling, which results in reduction of refrigerant mass flow
rate to produce a certain quantity of cooling effect compared with that by the conventional vapor
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
compression cycle. The cooling capacity of the adsorption cycle can be relatively small because
In the hybrid scheme II, the evaporator of the adsorption cycle works as the condenser of
the vapor compression cycle. By the cascading evaporator/condenser, the adsorption cycle as a
topping cycle and the vapor compression cycle as a bottoming cycle are connected as a kind of
two-staged compression system (Figure 1c). The condenser temperature of the vapor compression
cycle can be much lower than the ambient temperature, and therefore, the reduction of the
compression work as well as the increase of the enthalpy difference in evaporator are achieved.
The energy saving effect of the cascading scheme will be larger than that of the subcooling
scheme, while the cooling capacity of the adsorption cycle for the cascading scheme has to be
much larger than that for the sub-cooling scheme because the heat given to the adsorption cycle
through the cascading evaporator/condenser is the sum of the evaporator enthalpy difference and
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Many researchers have established the mathematical models of adsorption cycles with
various adsorbent-adsorbate pairs [7-9]. The most commonly used model is the lumped parameter
model, and the validity of the model was shown by the comparison with experiment in some
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
refrigeration/heat pump, the transient variations of adsorption uptake and adsorber, evaporator
Adsrotption uptake is expressed by the linear driving force approximation as in the form
of Eq.(1).
^ = km(W-w) (1)
dt
time.
ACCEPTED MANUSCRIPT
where (Mc) represents the total heat capacity including the
flow rate and specific heat capacity of the heat transfer fluid. T
ACCEPTED MANUSCRIPT
s = (Ti -T o )/ (T i -T) = 1 -exp(-NTU). Mad and Qad are the mass of the adsorbent and the heat of adsorption,
respectively.
The heat balance equations for evaporator and condenser could be derived in a similar manner to the
adsorber. dT dw
(Mc) m
f C (T -
f T)-M
ad Lref (3)
dt dt
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
where, Lref denotes the evaporation heat of refrigerant. The sensible heat transfer by the liquid refrigerant
flow from condenser to evaporator is ignored in this model. (Mc) for evaporator and condenser includes the
heat capacity of the refrigerant liquid and the heat exchanger itself.
Transformation of Eqs.(1)-(3) into dimensionless form facilitates to solve the equations analytically.
Using the dimensionless variables and parameters summarized in Table 1, Eqs.(1)-(3) can be rewritten as Eqs.
(4)-(6). dt=-L(o-t)
dr a (4)
where, O denotes the dimensionless form of equilibrium uptake, and O = 0 or 1 for desorption
or adsorption, respectively.
d
l=iL (0i-0)+1 # (5)
dr WK K dr
where, 6 { denotes the dimensionless temperature at the inlet of the heat
transfer fluid, and 6 t = 0
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
precooling, and adsorption. Generally, adsorption cooling system is cyclically operated by these
four processes. Therefore, cyclic boundary conditions have to be determined to solve Eqs. (4)-(6).
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
The cyclic boundary conditions were given at at T = 0 and 1, which is the beginning of the
) = = (fd)T=1 and (fd)T=0 = (^a)r=1. The connecting conditions at T = Tpr should be also given
a T 0
as f
'aX=v = (f)T=Tpr and (fdX=Tpr = OdX=V , Tpr is the dimensionless pre-
heating/cooling time. The subscripts a and d denotes the adsorption including pre-cooling and the
desorption including pre-heating processes, and f is the adsorption uptake during the pre-
g
heatin /coolin
g period. Similarly, (0\)T=o=(Oi)T=i , (^'d)T=0=(^a)T=1 , (^'e)T=0=(^e)T=1 ,
(9\)T=T = (9C)T=T for adsorbers, evaporator and condenser temperatures, where the subscripts e
Finally, the analytical solutions of Eqs.(4)-(6) could be obtained as the following form.
The adsorption uptakes during the pre-heating/cooling period are constant and they are the
minimum and maximum adsorption uptakes during the cycle. They were given by Eqs.(7) and (8).
fa=1-C (7)
fd =C (8)
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
exp
(11)
v, a J
C' 7
1
exp - Ti + exp
Vay a
1
C
1 (12)
exp - TL + exp
VaJ a
Equation (11) and (12) showed that the minimum and maximum adsorption uptakes during the
cycle were the functions of pre-heating/cooling time and the time constant of adsorption.
The adsorber temperatures during the pre-heating/cooling period was a function of time,
( \
T
6\ = D 'exp
(13)
v J
( \ T
6\ = 1 - D 'exp
v ^b J (14)
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
( \
T
0a = D exp + O b ex p I -
(15)
V J a,
( \ T
6d = 1 - D exp Ob e x p I -
-
(16)
V ^b J a,
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
f , \ f , .A f ,
1 -Ob exp 1 1 1 1 1
—
exp — —
- exp — —
Tpr
D' = V ^b J V^b V ^b aJ V^b a
J P1 (17)
1 + exp
f ■, \ ( ,^
1 -o_ 11 11
exp --1+ exp — pr
D =
T
Va J
a
1 V^b J
(18)
1 + exp
V ^b J
Equations (19) and (20) express the temperature of the condenser and evaporator, respectively,
( \ T
Q'e = ^ch,i + ' p F ex (20)
V ^e J
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
( \ T
-
Oeexp ^- ^
9 e = ^ch,i - F eXp (22)
V Qe J
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
where, Q and O are defined by a similar manner as those for adsorbers. The constants are given
by: f,A f, .A f,
O
cexp 1 1 1 1 1
-
exp exp Tpr
— —
-
E' = (23)
1J J
V Qc J VQc o V Qc o
1 - exp
V Qc J
f,A f, .A f,
O
e ex
p
1 1 1 1 1 (24)
-
exp exp Tpr
— —
-
F' =
1J J
V Qe J VQe o V Qe 0
1 - exp
V Qe J
f ■, \ ( , ^
11 11 (25)
exp --I exp
-
— T
pr
E =
V oJ
0
V Qc J
1 - exp
V Qc J
fi\ f,^
1 1 1 11
exp --I exp
-
— T
pr
F =
(26)
V oJ
0
V e J
Q
1 - exp
V Qe J
The calculated cooling capacity and coefficient of performance (COP) were affected by the
effective adsorption uptake at the design temperatures because it determined the driving force
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
of adsorption and desorption in the beginning of the adsorption and desorption processes. If the
effective adsorption uptake was calculated in accordance with the boundary condition
temperatures, namely, hot water inlet, cooling water inlet and chilled water inlet temperatures, the
driving force of the adsorption and desorption processes would be overestimated because the
discrepancy between the boundary conditions and the actual heat exchanger temperatures was
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
large in the beginning of the process. Therefore, the design temperature for the estimation of
effective adsorption uptake was given by considering the temperature efficiency of heat
exchanger. Figure 2 illustrates the effective adsorption uptake by the temperature boundary
conditions and by the design temperature. The design temperatures were given based on the
where, Ti and To are inlet and outlet temperatures of heat transfer fluids, respectively. sdenotes the
heat transfer effectiveness, which is equivalent to the temperature efficiency in this case. The outlet
temperatures of heat transfer fluids were chosen to fit the predicted cooling capacity and COP with
the experimental values within a reasonable range, and they were given as T i±3K for adsorbers and
The maximum and the minimum adsorption uptakes for the theoretical adsorption cycle
(29)
Wmin= f(T T)
deg,c deg,d
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Then, the effective adsorption uptake of the design condition is given as W max - Wmin. The
function of adsorption uptake was given as the form of adsorption isotherm equation. For silica
B(T )
P ref (30)
W = A(T)
V adPJ
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
where, A(T) and B(T) are functions of adsorbent temperature and given as:
The cooling capacity and COP of the adsorption cycle can be predicted using the
analytical model described above. The predicted results were verified by comparison with
experimental results from a literature [12]. The adsorbent and refrigerant were silica gel and
water, and the heat capacity and heat exchanger characteristics were taken from [12].
Figures 3 and 4 show the cooling capacity and COP as a function of chilled water inlet
temperature, respectively. The results showed a good agreement between the experiment and
analytical model. When the temperature boundary condition was changed, the analytical model
can be adjustable using the design temperatures, which is reasonable for practical heat exchanger
characteristics.
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
The performance of the vapor compression cycle was analyzed as a theoretical vapor
compression cycle with some practical parameter settings for the degree of superheat at the outlet
compressor. The heat exchange processes in evaporator and condenser were simplified by using
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
temperature efficiency. The thermophysical properties of refrigerant for the vapor compression
Calculation conditions
The performance of two types of hybrid cycles, namely, sub-cooling type and cascading
type, was predicted by the combination of semi-steady state model for adsorption cycle and
thermodynamic analysis of vapor compression cycle. The fixed parameters of the system were
summarized in Table 2. Provided that low grade heat source, such as cogeneration heat output
or solar thermal energy, was available as requested, the energy saving effect of the hybrid
system was defined as the improvement in the COP of vapor compression cycle. The COP of
the vapor compression cycle was given as Eq.(33), and the energy saving effect was determined
as Eq.(34).
where, COPVCC denotes the COP of vapor compression cycle without any
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Figure 5 shows the the energy saving effects of two type of hybrid cycles as a function of
cooling effect by the adsorption cycle in terms of temperature decrease. In case of sub-cooling
type, the cooling effect represents the temperature decrease by sub-cooler. In case of cascading
type, it represents the decrease in condenser temperature of the vapor compression cycle.
As depicted in Figure 5, the cascading type achieved much larger energy saving effect
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
compared with that of the sub-cooling type. The large reduction in compressor power of vapor
compression cycle was achieved by the lowered condensor pressure of the vapor compression
cycle with cascading integration of the adsorption cycle. The energy saving effect was as high as
40% with the temperature decrease of the vapor compression cycle condenser by 10 oC. On the
otherhand, the energy saving effect of the sub-cooling type was 10% with the corresponding
temperature decrease of the refrigerant liquid by sub-cooler. The effect of the sub-cooling was the
increase of evaporator enthalpy difference. The COP of the vapor compression cycle would
improve due to the rise of the ratio of the enthalpy difference of the evaporator to that of the
The adsorbent mass and adsorption cycle COP of the sub-cooling type and the cascade
type hybrid systems were depicted in Figures 6 and 7, respectively. The adsorbent mass was
calculated from the required cooling effect in sub-cooler or cascading condenser/evaporator and
the specific cooling capacity of the adsorption cycle. For both type of the hybrid cycles, the larger
cooling effect of the adsorption cycle resulted in the increase of the required adsorbent mass and
the decrease in the adsorption cycle COP. The adsorption cycle COP was kept higher
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
than 0.7, however, which was a very high level compared with that of conventional adsorption
cooling systems used for air-conditioning. The reason of the improved COP of the adsorption
cycle for the hybrid system was the rise of the evaporator temperature of the adsorption cycle.
When chilled water is generated by stand-alone adsorption cooling system, the evaporation
temperature needs to be at 5-10 oC. On the other hand, the evaportion tempearture of the
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
adsorption cycle for the hybrid system was higher than 20 oC because the lowest level temperature
(= 10 oC) was generated by the vapor compression cycle. This difference had a large influence on
The cascading type hybrid system required large cooling effect on the adsorption cycle to
achieve a high energy saving because the adsorption cycle had to cope with condensation heat of
vapor compression cycle refrigerant. On the other hand, the sub-cooling type effectively worked
with smaller cooling effect of the adsorption cycle because the role of the adsorption cooling was
only for sensible heat cooling of refrigerant liquid. In case of the cooling effect by adsorption
cycle with 10 oC, the quantity of heat removed by the adsorption cycle was 10.5 kW for the
cascading type, whereas that was 1.2 kW for the sub-cooling type. As a result, the refrigerant
mass flow rate required in the adsorption cycle was 4.3 g/s for the cascading type and 0.5 g/s for
the sub-cooling type as an average of the cycle time. Therefore, the required adsorbent mass for
the cascading type was nearly ten times larger than that for the sub-cooling type.
CONCLUSIONS
The study presented an analytical model of the adsorption cycle and it was shown that the
model could predicted the performance of the adsorption cycle in a good agreeement with the
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
experimental results given in literature. Two types of hybrid adsorption-vapor compression cycles,
namely sub-cooling type and cascading type, were described and the energy saving effect of these
cycles were predicted. The results revealed that the cascading type would achieve a larger energy
saving effect as much as 40% of COP improvement, whereas the sub-cooling type had an
advantage in size and cost of adsorption cycle with reasonable COP improvement. The developed
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
semi-steady state model of the adsorption cycle and the performance prediction of the vapor
compression-adsorption hybrid system were useful for design, evaluation and analysis of the
application of waste heat driven adsorption cycles to be combined with conventional vapor
compression cycles.
NOMENCLATURE
M mass, kg
Q heat, J
T temperature, oC or K t
time, s
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Greek symbols
ratio
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
d dimensionless temperature
adsorption
T dimensionless time
transfer
Subscripts
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
a adsorption process
ad adsorption or adsorbent
b adsorbnet bed
c condenser
ch chilled water
d desorption process
dsg design
e evaporator
hybrid hybrid
cycle i inlet
o outlet
pr
pre-heating/cool
ing process
ref refrigerant
VCC vapor
compression
cycle
REFERENCES
Zhang, J.P., A
review on
ACCEPTED MANUSCRIPT
[2] Akisawa, A., Miyazaki, T., Multi-bed adsorption heat pump cycles and their optimal
operation, in Advances in Adsorption Technology, B.B. Saha and K.C. Ng, Editors, Nova
[3] Saha, B.B., El-Sharkawy, I.I., Koyama, S., Lee, J.B., Kuwahara, K., Waste heat driven
performance, Heat Transfer Eng., vol. 25, no.5, pp. 80-87, 2006.
[4] Wang, X., Chua, H.T., A comparative evaluation of two different heat-recovery schemes as
applied to a two bed adsorption chiller, Int. J. Heat Mass Tran., vol. 50, pp. 433-443, 2007.
[5] Lychnos, G., Tamainot-Telto, Z., Performance of hybrid refrigeration system using
[6] Uddin, K., Miyazaki, T., Koyama, S., Saha, B.B., Performance investigation of adsorption-
compression hybrid refrigeration systems, Int. J. Air-Cond. Refrig., vol. 21, no. 4, 1350024,
2013.
[7] Luo, L., Feidt, M., Thermodynamics of adsorption cycles: a theoretical study, Heat Transfer
[8] Li, Y., Sumathy, K., Review of mathematical investigation on the closed adsorption heat
pump and cooling systems, Renew. Sust. Energ. Rev., vol. 6, pp. 305-337, 2002.
[9] Rhman, A.F.M.M., Miyazaki, T., Ueda, Y., Saha, B.B., Akisawa, A., Performance
comparison of three-bed adsorption cooling system with optimal cycle time setting, Heat
[10] Saha, B.B., Boelman, E.C., Kashiwagi, T., Computational analysis of an advanced
adsorption-refrigeration cycle, Energy, vol. 20, no. 10, pp. 983-994, 1995.
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
[11] Chua, H.T., Ng, N.G., Malek, A., Kashiwagi, T., Akisawa, A., Saha, B.B., Multi-bed
regenerative adsorption chiller - improving the utilization of waste heat and reducing the
chilled water outlet temperature fluctuation, Int. J. Refrig., vol. 24, pp. 124-136, 2001.
[12] Boelman, E.C., Saha, B.B., Kashiwagi, T., Experimental investigation of a silica gel-water
adsorption refrigeration cycle - The influence of operating conditions on cooling output and
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Table 1 Dimensionless variables and parameters
II
Adsorption uptake w - W ■ Wmax, Wmin: equilibrium uptake
6_ min W - W .
max min
Refrigerant mass Mref
W_ -—-
Mad (W,,x - Wmin)
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Figure 1 Schematics of the conventional vapor compression cycle and two hybrid cycles
Figure 6 Adsorbent mass and the adsorption cycle COP as a function of temperature decrease in
Figure 7 Adsorbent mass and the adsorption cycle COP as a function of temperature decrease in
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
Figure 1 Schematics of the conventional vapor compression cycle and two hybrid cycles
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
Figure 6 Adsorbent mass and the adsorption cycle COP as a function of temperature decrease in
subcooler in case of the sub-cooling type
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
Japan, in 1995 and his M.Sc. in renewable energy and architecture from
Agriculture and Technology from 2005 to 2010. Since 2011, he has been associate professor at
the Faculty of Engineering Sciences, Kyushu University, Japan. His main research interests are
Figure 7 Adsorbent mass and the adsorption cycle COP as a function of temperature decrease in
condenser in case of the cascading type ED ^ ^ A N U S C R I P I
ACCEPTED MANUSCRIPT
thermally driven air-conditioning systems including adsorption chillers/heat pumps and desiccant
air-conditioning.
Bidyut Baran Saha obtained his B.Sc. (Hons.) and M.Sc. degrees from
Downloaded by [University of Nebraska, Lincoln] at 23:05 07 June 2016
received his Ph.D. in 1997 from the Tokyo University of Agriculture and
University in 2010 as a Professor. He joined the Kyushu University Program for Leading
Graduate School, Green Asia Education Center in March 2013 as a professor. He has been
working as a professor at the International Institute for Carbon-Neutral Energy Research (WPI-
I2CNER) in the Division of Thermal Science and Engineering. His main research interests are
thermally powered sorption systems, heat and mass transfer analysis, and energy efficiency
assessment. He has published more than 300 articles in peer-reviewed journals and international
conference proceedings. He has edited four books and holds 10 patents. Recently, he served as
managing Guest Editor for Applied Thermal Engineering and Heat Transfer Engineering journal.
He serves as the editorial advisory board member of Applied Thermal Engineering journal;
editorial board member of Advances in Mechanical Engineering, AIMS Energy journal, and
ACCEPTED MANUSCRIPT
ACCEPTED MANUSCRIPT
University, Japan. He has been working as a professor at the International Institute for Carbon-
Neutral Energy Research (WPI-I2CNER) in the Division of Thermal Science and Engineering.
(IIR). He received his Ph.D. in 1980 from Kyushu University, Japan. His main research interests
are vapor compression systems, sorption systems, compact heat exchanger design, and heat and
mass transfer analysis. He has published more than 300 articles in well-recognized journals,
ACCEPTED MANUSCRIPT