Vacon 8000 SOLAR Inverters
2
Content
Overview
Technical Data
Approvals
Software
Maximum Power Point Tracking
Grid Codes
MultiMaster
Service
Touchpad Control Panel
Accessories and Options
3
Overview
Central inverters for 3-phase grid tied PV systems
Power range from 10kW to 1.2MW, covering the Commercial, Industry
and Utility segment
Features inbuilt transformer up to 100kW for isolation
Unique Multi-Master concept for >= 400kW
– Designed for reliability by using standardized 200kW modules.
– Including centralized high grade control panel
Thin Film panels supported
Options:
– String boxes
– Remote monitoring system
– Incoming boxes
4
From Solar Energy to AC Power
5
Vacon Scope of Supply
Inverter
Option
6
Technical Data: General
10-1200kW
AC Current harmonics: <3% at nominal
IP21
Relative Humidity: <95%
Ambient Temperature:-10 to 40°C (50°C with approx 1,5%/°C de-rating.)
Communication: RS485, Ethernet, GPRS(remote monitor option)
Ground fault monitoring
Emergency stop (>= 40kW units.)
Thin Film compatiblity
– Negative or Positive grounding as option
7
DC Input
[Optional]
DC Input [Optional]
Surge Protection
– MPP Voltage Range 340-800VDC
– Max Starting Voltage 850VDC
– Max Input Voltage 900VDC
Vacon Inverter
– Isolation Transformer
[Optional]
– LC Filter Surge Protection
– RFI Filter
– Surge Protection (optional)
AC Output
8
DC Input
[Optional]
Vacon Inverter
[Optional]
DC Input Surge Protection
AC Output
9
DC Input
[Optional]
Vacon Inverter
DC Input
– MPP Voltage Range 410-800VDC [Optional]
Surge Protection
– Max Starting Voltage 850VDC
– Max Input Voltage 900VDC
– DC Insulation monitoring
EMC Capacitors
– Surge Protection (optional)
AC Output
– Output Voltage 280V, 3 Phase LC Filter
– LC Filter
– Surge Protection (optional)
[Optional]
– Optimized for connection to medium voltage Surge Protection
transformer
Neutral not connected and percentage
impedance (Z%): >= 6%
AC Output
10
Technical Data: NXV0400-NXV1200
11
NXV1000 Multi-Master Optional
Incoming Inverter Sections Outgoing
12
Technical Data:Power Range
Type Nominal Max PV Power Max Efficiency % Euro Efficiency %
Power [kW] [kW]
13
Technical Data: Mechanical
Type Dimensions Weight Air flow Max # DC IP Class
WxHxD [kg] requirement Connections
[mm] [m3/h]
600x1481x600 220 300 IP21
NXV00104A2L 2
NXV00154A2L 600x1481x600 220 300 2 IP21
NXV00204A2L 600x1481x600 300 425 2 IP21
NXV00254A2L 600x1481x600 300 425 2 IP21
NXV00304A2L 600x1481x600 300 425 2 IP21
NXV00404A2L 800x1881x600 550 700 4 IP21
NXV00504A2L 800x1881x600 550 700 4 IP21
NXV00804A2L 800x2281x600 850 800 4 IP21
NXV01004A2L 800x2281x600 850 800 4 IP21
NXV01252A2L 800x2281x600 450 800 4 IP21
NXV02002A2L 800x2281x600 645 1000 4 IP21
NXV04002A2L 2800x2281x600 1675 2000 20 IP21
NXV06002A2L 3600x2281x600 2285 3000 20 IP21
NXV08002A2L 4600x2281x600 3160 4000 32 IP21
NXV10002A2L 5400x2281x600 3770 5000 32 IP21
NXV12002A2L 6200x2281x600 4380 6000 32 IP21
14
Example: Efficiency curve, 200kW Units
100
98
96
Efficiency, %
94
410V
92
90
88
0.05 0.15 0.25 0.35 0.45 0.55 0.65 0.75 0.85 0.95
Efficiency curve for 200kW unit performed with external auxiliary power supply.
15
Buses and Communication
Remote
monitoring over
Internet
W t/
W e
W ern
h
Et
Ethernet/
WWW GRID
Vacon Database &
GPRS
Webserver
Customer
Supervisory/SCADA
AC
Vacon Remote
Monitoring
box
Modbus TCP
Supervisory/Scada
RS-485/Modbus RTU
Supervisory/Scada
DC
Vacon’s offering
16
Approvals: Safety & EMC
17
Approvals: Grid Codes
Country Low Voltage Medium voltage
Germany VDE 0126-1-1 BDEW 2008
France EN 50438 Arrêté du 23 avril 2008
Italy CEI 11-20 Allegato 17. Terna
Spain R.D. 1663/2000 P.O. 12.2; P.O. 12.3
Czech EN 50438
UK EN 50438
Belgium EN 50438
Australia AS 4777.2; AS 4777.3
Anti-Islanding IEC-62116
18
General About Software
Main functions
– Maximum Power Point tracking
For maximization of yield.
– Grid Code Functions
For compliance with national grid standards.
19
Maximum Power Point
20
Why are grid codes needed?
21
Grid Code functions
22
Grid Code functions
23
Multimaster
24
Touchpad Control Panel
On incoming cabinet
High end touchpad panel
Clear and simple user interface
Multimaster system
– NXV0400-NXV1000
25
Touchpad Control Panel: Main functions
26
Vacon Service Network
88 Service centers in more than 50 countries
Vacon Factory
Authorized Service
Partner
17/03/2023
Design for Service
28
Service Offering
Start-up
– Planned on-time start up of the plant and verification on the ambient conditions
for long life time of the inverter
Maintenance and parts
– Scheduled maintenance and verification on the ambient conditions for long life
time of the inverter
Repair and parts
– Recovery of energy production in case of failure
Support
– Professional network at your service
29
Accessories: Remote monitoring
30
Accessories: String Boxes
8 strings
DC Breaker for isolation
Lightning protection
10A string fuses
Options:
– String monitoring for remote monitoring
system.
Current sensors (hall elements)
Modbus RTU
– MC3 string connectors.
31
ORDERING:Type Codes
VACON NXV-0010-4-A-2-T-A1A2D7-XXYY
Monitoring Bus
Stand-Alone:
B500 = No bus
B5C2 = Modbus RTU
B5CI = Modbus TCP
Multi-Master:
D2CI = Modbus RTU and/or TCP through touchpad as default
Enclosure class
2 = IP21
Output
2 = 3 x 280 VAC, no galvanic isolation transformer (125-1200kW)
4 = 3 x 400 VAC, galvanic isolation transformer (10-100kW)
Nominal Power:
e.g. 0010 = 10kW, 0600 = 600kW
32
-
ORDERING: “+Codes”
33