Professional Documents
Culture Documents
BLOWER FAN
AIR
INLET
FOAM
SOLUTION
INLET
HAZARD CLASSIFICATION
(Page 6)
BUILDING CONSTRUCTION
(Page 6)
FOAM CALCULATE
BREAKDOWN RATE FOAM DISCHARGE RATE (R)
(Page 9) (Page 7)
R= ( T+ R )xC
V
S N x CL
R = minimum rate of foam discharge (cfm)
V = minimum submergence volume (cubic feet)
T = time to achieve submergence volume (min.)
RS = rate of foam breakdown by sprinklers (cfm)
CN = compensation for normal foam shrinkage (%)
CL = compensation for normal foam leakage (%)
Minimum
Submergence Volume
V = Cubic Feet
Rs = S x Q
S = Foam breakdown in cubic feet per minute (cfm) per
gpm of sprinkler discharge. S shall be 10 cfm/gpm.
Q = Estimated total discharge from the maximum number
of sprinklers expected to operate. (ie. .30 gpm/sq. ft.
over 3,000 sq. ft. = 900 gpm)
Compensation for
Foam Shrinkage
CN = %
This is an empirical number based on the average
expanded foam losses that can be expected due to
drainage, fire, wetting of surfaces, etc.
Example:
Hazard area of 125' wide by 180' long and 30' high with a maximum storage
height of 25'. Building is light steel construction and is not sprinklered. Product
is high density combustibles (rolled paper,coated-unbanded)
Depth of foam required is 25' X 1.1 = 27.5'.
Note: Minimum of 2 feet over hazard is required.
Submergence volume is 125' X 180' X 27.5' or 618,750 cubic feet and the
submergence time per Table 1 is 4 minutes.
Light or Unprotected Heavy or Protected
Steel Construction or Fire Resistant
HAZARD Sprinklered Not Sprinklered Sprinklered Not Sprinklered
High Density
Combustibles 5 minutes 4 minutes 6 minutes 5 minutes
e.g. Rolled Paper * *
Kraft or Coated-Unbanded
Calculating Foam Quantity
For Total Flooding Systems CONTINUED
Solution flow for the system is based upon the solution flow per generator and
the quantity of generators required.
The systems foam concentrate supply is based supplying foam for (1) continuous
operation of the system for 25 minutes or (2) sufficient supply to generate 4 times
the submergence volume, whichever is less, (3) but in no case less than than 15
minutes.
EXAMPLE:
1. 12 JET-X 15A(FM) x 128 gpm x 25 min. x 2.75% Proportioning = 1056 gallons
of JET-X Concentrate
2. 618,750 cu. ft.(V) x 4 = 2,475,000 cu. ft. ÷ 17,985 cfm JET-X 15A(FM) = 137.61
generators X 128 gpm x 2.75% Proportioning = 484.4 gallons of JET-X Concentrate
3. 12 JET-X 15A(FM) x 128 gpm x 15 min. x 2.75% Proportioning =
633.5 gal. of JET-X Concentrate
Local Application Systems
Local Application Systems are best suited for basically flat surfaces such as
confined spill, curbed area, pits, etc. When multi-level or three dimensional
hazards are protected with local application, some type of foam containment
must be provided.
Design criteria is to discharge sufficient expanded foam to cover the hazard
to a depth of 2 feet in two minutes.
For multi-level or three dimensional hazards, the design formula for total
flooding is used.
The system discharge duration shall be sufficient to supply at least
12 minutes duration.
High-Expansion
Example System
HAZARD SPECIFICATIONS
Type of Product Combustible Liquids [Flash Point of 100 °F (38 °C) and
above] Palletized Drum Storage
Type of Building Light Steel Construction (125' wide 80' long x 20' high)
Sprinklered (.25 gpm/sq. ft. over 3,000 sq. ft.)
Maximum Storage Height 8 feet (two pallets high)
SYSTEM DESIGN
1. Hazard Classification (Page 6) - Combustible Liquids
2. Building Construction (Page 6) - Light Steel Construction.
3. Submergence Time (Page 8) - 4 Minutes (based upon the buildings light
steel construction and also that the area is sprinklered).
High-Expansion
Example System CONTINUED