Professional Documents
Culture Documents
“FIRE”
NOTES BY:
CAPT. PARVINDER SINGH
BHATIA
UPDATED: 11 MAY 2021
• Following precautions and checks need to carried out once the foam fixed fire fighting system is
used for fire extinguishing purpose:
• 1. The place will be acquired with plenty of drainage which is a mixture of water and foam. Use
pumps to remove the drain mixture.
• 2. Ensure there are no gases present in the room and pumps are in good working condition before
using as it may lead to secondary accidents such as explosion or electrical shocks.
• 3. Use fresh water mist while cleaning the foam from the room.
• 4. Keep checking the gas content in the room as during cleaning, foam may contain poisonous
gases which was produced during the fire.
• 5. The electric machinery and systems covered with foam should be wiped out using cloth.
• 6. All the machinery to be inspected prior cleaning is finished. If internal electric parts or panels are
still moist, use hot air blow to clean the same.
• 7. After complete use of foam system, drain out foam solution lines and liquid lines by air blow.
• 8. Check the level of the foam liquid tank and refill it to the required level.
• 9. Check the foam discharge nozzle in the fire area and foam generator for any fire damages.
• 10. Check all the valves involved in the discharging of foam are set to normal ready-to-use position.
If the foam discharged is done manually, set the manual button to normal ready-to-use position.
• 11. The above points are required to ensure the affected space is checked and cleaned, and the
machinery in that space is ready for further usage. The foam system needs to be made normal as
soon as possible to ensure it is ready for any other emergency situation in near future.
ORALS - CO2 FIRE EXTINGISHING SYSTEM
• Q. What is requirements for CO2 that you must have to have on board for
cargo hold and Machinery space separately?
• For cargo hold:
• 30 % vol. of largest cargo hold if carried.
• 45 % vol. if cargo hold carry vehicles and vehicles are fitted with F. O. tanks
and tanks are full of F. O.
• For machinery space:
• 40 % vol. of Machinery spaces excluding Engine casing.
• 35 % vol. of machinery spaces including Engine casing.
• Q. How will you check the CO2 system and pressure in the bottles?
• Discharge requirement: At least 50% of CO2 discharge to be carried out in
1 minute and at least 85% discharge in 2 minutes.
• Monthly
• Alarms, Machinery trips, Door alarm, Quick closing valves, Flaps, Skylights,
Ventilation fan trips to be tested.
• Yearly
• General inspection of the installation, pipe lines to be checked.
ORALS - CO2 FIRE EXTINGISHING SYSTEM
• 2 Yearly
• 1+
• Verify CO2 contents by mechanical advantage lever, ultrasonic liquid level measurement or
radioactive liquid level measurement. Equipment for measuring CO2 content must be available on
board ships. A maximum reduction of 5% in CO2 content may be allowed provided total CO2
quantity on board is not less than the required amount.
• Blow through the system with 6-7 bar air with plastic air bags at the nozzle ends.
• 5 Yearly
• 1+2+
• The servo cylinders and any remote controlled stop valves to be tested by opening one pilot cylinder.
The main CO2 bottles must be uncoupled for this purpose.
• Spring loaded relief valves to be checked and pressure tested at 180 bar.
• Checking of HP alarms which operate with gas pressure.
• Section of CO2 which can be shut off must be tested with air at 25 bar.
• 10 Yearly
• 1+2+5+
• CO2 bottles to be inspected internally. Siphon tube or dip tube to be checked. Cylinders to be
pressure tested at 250 bar. If permanent change in volume is observed, those cylinders to be
discarded.
• What is the diameter of the orifice?
• 6MM. The discharge rate per unit area of CO2 nozzles (orifice) is determined with the pressure at
CO2 nozzles.
ORALS – EMERGENCY FIRE PUMP
• Describe the requirements, location and working of fire pump on last ship?
• Passenger ships of 1000 GT and upwards and in cargo ships of 2000 GT and upwards
must have fixed emergency fire pump. The emergency fire pump, its sea water inlet and the
suction and delivery pipes and isolating valves shall be located outside the machinery space.
• The suction lift of any pump is limited and for this reason emergency fire pumps are
restricted to being at a maximum of 6 m from the water level at light draught conditions.
Ideally they are installed below the waterline to guarantee avoidance of suction problems.
If the location of a centrifugal type emergency fire pump is the steering flat then, because of
the high suction lift involved, a priming pump is fitted.
• The first stage below the waterline is driven by a hydraulic motor. The second stage and the
hydraulic power unit are driven by a prime mover (or electric motor from the emergency
supply) which can be positioned at more than the normal distance from the waterline. If the
fire pump is driven by a water-cooled diesel engine supplied with cooling water from the fire
pump a header tank will be provided to ensure that the engine is cooled while the fire pump
is being primed. The engine could have a closed circuit fresh-water system, with the water
being cooled in a radiator. It is usual however, to fit an air-cooled diesel engine.
• Where a closed-circuit fresh-water cooled engine is installed, anti-freeze may be needed for
the radiator in cold weather. An emergency pump has an independent diesel drive or some
alternative such as an electric motor powered from the emergency generator.
ORALS – HYPER MIST SYSTEM
• Explain hyper mist system and its working?
• Hyper mist is a very fine form of droplet of water which act like a fog of cloud when high
pressure water is injected through nozzle.
• Hyper mist is installed near the critical machinery such as:
• 1.Boiler Incinerator.
• 2.Main engine.
• 3.Purifier Room.
• 4. Aux Generator.
• 5. Steering Gear Room, etc.
• Activation:
• Hyper Mist is activated by two sensor placed near to each other. One is smoke detector and
second is Flame Detector. When both get Activated then the system injected Hyper mist
through it nozzle. Hyper Mist system is installed along with the CO2 system but it is
independent of each other.
• Working:
• 1.A fresh water pump takes suction from fresh water tank (A particular dedicated tank is
provided in which we need to maintain certain water level with alarm provided as warning)
to supply high-pressure water to the sprinkler system.
2.Each area is isolated by valves, which can be opened during emergency situations
involving fire. The system is kept at constant stage of readiness.
ORALS – HYPER MIST SYSTEM
• Actuation:
• Automatic Activation:
Water mist system will be automatically released Hyper Mist into the protected area where fire is
detected by the fire alarm system (both need to activated- smoke and flame detectors), and an
audible and visible alarm is activated in that protected area.
Manual Activation:
1.For the manual release push button is provided on the local control panel at each section and on
the main control panel at the fire control station. When the manual release push button is
pressed, the fire alarm, as well as the system, will be activated in the designated area.
2.Manual activation is required to test periodically that particular area hyper mist is working
correctly or not. Some time Vetting inspector or PSC personnel want to see the activation of Hyper
mist at that time we actuate it manually.
• Stopping the hyper mist system:
After extinction of a fire, the hyper mist system can be stopped manually by cancelling the fire
alarm signal from the fire alarm system by pressing the “Stop” button on the control panel or local
control point.
• Advantage of Hyper Mist System
1.Cooling effect – Mist contains a water molecule, which provides the cooling effect when injected
at particular area.
2.Smoke eliminating effect – The smoke particles being absorbed and settled by the mist (fog).
3.Oxygen replacement effect – Mist get evaporated by taking latent heat. The water vapour is
heavier than air, replace the oxygen.
4.Shut off effect – The floating mist as fog forms a layer of water on fire.
ORAL NOTES- FIRE FIGHTER’S OUTFIT/RADIOS
•According to SOLAS Chapter II-2, Regulation 10.10.2.1 all ships shall carry at least
two fire-fighter´s outfit.
•According to SOLAS Chapter II-2, Regulation 10.10.2.2 an additional fire-fighter’s
outfit is required for passenger vessels depending on the design of the passenger
vessel / cruise ship; i.e. length of passenger spaces, number of decks, number of
vertical zones and number of passengers.
•According to SOLAS Chapter II-2, Regulation 10.10.2.3 an additional two fire-
fighter’s outfits shall be provided on Tankers.
•“Two-way portable radiotelephone apparatus” shall be referred to as “Fire-Fighter
Radios”.
•The purpose of the Fire-Fighter Radios is to provide a dedicated means of
communication between a team of fire fighters entering the space and the crew
member located outside the space who is assigned to control this team.
•Fire-fighter’s radios as required by Regulation 10.10.4, is additional to the above
fire-fighters outfit and intended for the Fire Party.
•Therefore, the total number of these radios to be carried on board will depend upon
the number of fire parties detailed on the Muster List rather than the number of
fire-fighter outfits.
ORAL NOTES- FIRE FIGHTER’S OUTFIT/RADIOS
• Each Fire Party must have at least two of these dedicated radios during fire-
fighting operations or if the Fire Party consist of more crew members than the
actual fire fighters, i.e. incident commander, the actual number of fire-fighter radios
may vary from vessel to vessel as more than two radios may be required for each
Fire Party.
• These radio devices shall be of an explosion proof type or intrinsically safe.
• To obtain maximum coverage on-board a vessel, UHF is the most commonly used
frequency band (working in the range of 457 MHz to 467 MHz) for maritime use,
due to the ability to propagate inside metal structures.
• The main reason why each party must have at least two of these dedicated radios is
that, the fire-fighters may need to use Direct Mode Operation (DMO)
communication (like 'Walkie-Talkies’ independent of the network), which means all
radios working on the same frequency will have the ability to send and receive on
the same channel during fire-fighting operations.
• It is important to ensure that firefighters’ radios are “fit for purpose”, i.e. work
within the environment of a fire scenario, have a sufficient operating range and are
designed for use by crew members wearing full firefighter suits with large gloves,
helmets and breathing apparatus.
• Radios that can be fitted on helmets and used with breathing masks should
therefore be considered.
FIRE RADIO- IMO SYMBOL
ACCESSORIES DONNED WITH FIRE SUIT
Fires In Containers
• Containers with combustible cargoes should be stuffed in a controlled
environment, and their contents properly declared.
• Cargoes liable to spontaneously combust "in stow" should not be unnecessarily
ventilated and should be checked regularly for a rise in temperature.
• The securing of wheeled transport, containers, and other cargo on the vehicle
decks of Ro-Ro vessels must be arranged so that firefighting equipment
remains unobstructed and fully accessible during loading, discharging, and
passage. This includes valves, emergency pumps, hoses, etc.
• The details of all hazardous containers, together with the fire fighting
instructions for each hazardous container, must be kept on the bridge.
• Mobile fire fighting equipment, such as hi-expansion foam generators, water
mist lances, and mobile water monitors should be maintained in good
condition and readiness.
• Note: Container vessels designed to carry containers on or above the
weather deck constructed on or after 1st January 2016 are required to carry
at least one water mist lance. Modern vessels have been fitted with fixed
water spraying systems (water curtains, large monitors, deluge systems).
MOBILE WATER MONITORS
•ORAL NOTES:
•Firefighting for Ships Designed to
Carry Containers on or above the
Weather Deck (SOLAS II-2/10) and
further, MSC.1/Circ.1472 was also
approved to set design and
performance standards of a mobile
water monitor.
•IMO introduced some special
additional requirements concerning
firefighting equipment in large
containerships.
•SOLAS now requires
containerships built after 1 January
2016 to have:
•If 5 or more tiers of containers are
carried on or above weather deck,
ships with a breadth up to 30
meters are to have at least two
mobile water monitors, and for
vessels with a breadth exceeding 30
meters there are to be at least four.
WATER LANCE MIST
•ORAL NOTES:
•Firefighting for Ships Designed to
Carry Containers on or above the
Weather Deck (SOLAS II-2/10) and
further, MSC.1/Circ.1472 was also
approved to set design and
performance standards of a mobile
water monitor.
•IMO introduced some special
additional requirements concerning
firefighting equipment in large
containerships.
•SOLAS now requires
containerships built after 1 January
2016 to have:
•Water mist lance (at least one
should be installed on board), which
is a device to penetrate a container
wall and produce water mist inside
containers. The water mist lance
tool case contains a battery
operated drill, a fire hose and the
lance itself.
DELUGE SYSTEM
•ORAL NOTES:
•IMO introduced some special
additional requirements
concerning firefighting equipment
in large containerships.
•Applied to ships keel laid on or
after 1 January 2016.
•Modern vessels have been fitted
with fixed water spraying systems
(water curtains, large monitors,
deluge system).
• A deluge fire sprinkler system is
one in which the sprinkler heads
are open and the pipe is not
pressurized with air.
•Deluge systems are connected to
a water supply through a deluge
valve that is opened by the
operation of a smoke or heat
detection system.
Fire in Cargo Hold at Sea
• Usually fires in a general cargo hold are more difficult to extinguish with C02
than fires in an engine room and it may not be possible to completely
extinguish a deep seated fire at sea by the only use of C02 (or halons).
However, by working on one or two the elements of the fire triangle i.e. by
seating of the hold and using C02, which reduces the amount of oxygen, and
by cooling off, it may be possible to keep a burning cargo hold under control
until the vessel reaches a port.
• It should be borne in mind that C02 should be released gradually and that
the instructions for the C02 total flooding should be followed, taking into
consideration the volume of the burning compartment.
• Calculate the approximate free air volume in the compartment and
compensate for the air volume contained in the cargo depending on its
composition.
• About 0.7 kgs of C02 are required for 1 m3 of air in a compartment in order
to obtain the extinguishing 40 % gas air mixture. As the gas is heavier than
the air, the gas tends to sink down to the lowest parts of the compartment.
Fire in Cargo Hold at Sea
•IMMEDIATE ACTIONS:
•1. Sound fire alarm.
•2. Announce by PA.
•3. Inform E/R.
•4. Reduce speed, if and as necessary.
•5. Activate ship's contingency plan for fire.
•6. Muster in the emergency station.
•7. Muster as per emergency team.
•8. Carry out head count.
•9. Check if any casualty.
•10. Establish communication between Emergency teams and Bridge.
•COMMAND TEAM:
•1. Check vessel’s position.
•2. Check weather condition, wind direction, force.
•3. Suit vessel’s course appropriate for minimum wind
effect if traffic condition permits.
•4. Alter course.
•5. Reduce speed.
•6. Record all the events and steps taken.
•7. Send ALERT (urgency or distress message) depending on the extent of fire.
Fire in Cargo Hold at Sea
• The fire fighting agent together with the tactics to be used will certainly depend on the
concentration and the types of the materials present, the free surfaces of such materials and
the air circulation. For a small, local fire, extinguish fire in an early stage using Fire
Extinguishers, Blankets, Fire buckets, and others.
• Several areas in the vessel will contain more plastic materials than others (radio-rooms,
engine -control rooms, accommodation, etc.). A fire can be successfully coped with, at the
initial stage, using the classic means and methods. An important fire will have to be dealt
with by inert methods. Protein and synthetic foams will be used.
• Ventilation and exhaust fans must be stopped and fire flaps closed.
• Evacuate the crew and other people right away to safe places except the Fire-fighting team(s).
• Be sure to use Spray nozzles and if fire hoses are used care should be taken not to spread the
fire.
• For a fire of Electric equipment including switchboards, shut down the power and use Carbon
dioxide Fire Extinguishers.
• The galley area presents a somewhat different fire hazard. Here Class B materials, such as
cooking oil, fat or grease, will be present requiring the use of foam, dry powder or carbon
dioxide extinguishers.
• A fire blanket quickly spread over burning cooking utensils could extinguish a potentially
dangerous fire.
Fire in Galley