Professional Documents
Culture Documents
1 LoadShedAndRest-sambodo
1 LoadShedAndRest-sambodo
(1)
1. Governors sense small changes in speed
and will adjust the mechanical input, an
increase of load will cause a decrease in
speed and the prime mover’s governor will
increase the mechanical power input to
restore the speed or frequency. This
increase in mechanical power may cause
overload
Criteria:
1. Each island must consist of steam power plants with load
20%<load<100% so that the automatic control of the units operate
stably.
2. Avoid (if possible) long EHV line with light load or no load at the
receiving end: Ferranti effect will cause over voltage; Untransposed
EHV may produce negative sequence current, harmonic etc. Negative
sequence current may damage damper windings, field windings, axes or
salient poles of generators and may cause mal-function of generator
and transmission relays
3. Avoid EHV line going out of service reenergizing will have above
mentioned (see No.2) consequences.
Thank You