Professional Documents
Culture Documents
measurement
by Win Jet Luo
HVAC 常用之量測
HVAC commonly used measurement
• 溫濕度量測 Temperature and humidity measurement
• 壓力量測 Pressure measurement
• 風速量測 Air velocity measurement
• 風量量測 Air volume measurement
• 冰水流量量測 Chilled water flow rate measurement
• 冰水泵前後壓差量測 Pressure difference measurement of
water pump
• 電壓 / 電流 / 電功率量測 Voltage/current/electric power
measurement
( 一 ) 溫濕度量測 (1)
(1) Temperature and humidity measurement (1)
Hotwire air velocity meter Air Hood air flow meter
• 全壓=靜壓 + 動壓
Total pressure ( B) =
static pressure(A) + dynamic pressure(C))
•
( 二 ) 壓力量測 (2)
(2) Pressure measurement (2)
1. 必須在風速、風量、氣流等測試完成後,才能測試壓力,
並且進氣與排氣系統要完全正常運轉。
2. 差壓量測時全部門與開口都要關閉。室外大氣壓力假設
為 0.0mmAq 錶壓力。
• 某科技大樓為國家重要單位所在之建築,且位於精華路段,
動見觀瞻。
• 經現場勘驗後,該建築之能源節約與室內空氣品質亟待改
進,以發揮示範與指標功能。
• A certain science and technology building is a building where
an important national unit is located, and it is located in the
elite section of the road.
• After on-site inspection, the building's energy conservation
and indoor air quality need to be improved urgently to
illustrate its demonstration and indicator functions.
規劃之節能改善措施
Planned energy-saving improvement measures
• 一、空調設備系統節能約能源
– 水路系統變頻控制改善
– 冷卻水塔與冷卻水系統節能改善
– 冷能回收設備
– 外氣引入控制與裝設室內二氧化碳濃度控制
• 1. Energy saving of air-conditioning equipment system
– Improvement of varied flow volume
– Energy saving improvement of cooling water tower and cooling
water loop
– Coldness energy recovery equipment
– Fresh air introduction control and installation indoor carbon
dioxide concentration control
規劃之節能改善措施
Planned energy-saving improvement measures
二、電力系統節約能源
三、再生能源—太陽光電應用與展示
四、所有節能措施之展示系統
2. Energy saving in electric power system
3. Renewable energy-solar photovoltaic application and display
4. Display system for all energy-saving measures
冰水系統變頻節能量分析
Analysis on Energy Saving of Varied Chilled
Water Volume
水路系統變頻控制改善
Improvement of varied chilled water volume
• 運轉模式:現況獨立兩套二次冰水變頻泵送水管修改共管後,再
分送原 AHU 及 FCU 冰水系統,並新增比例控制閥。
• 優點:於低負荷需求時,可四台二次冰水變頻泵彈性供應及備援。
• 改善後初期評估,水泵用電量為原系統的一半,一天節能量為
337kWh 。
• Operation mode: Two sets of independent secondary varied chilled water
volume loop are modified and shared, and then distribute chilled water to the
AHU and FCU secondary loop, and a proportional control valve is added in a
common tube.
• Advantages: In the case of low load demand, four secondary variable water
volume pumps can be flexibly supplied and backed up.
• In the initial evaluation after the improvement, the power consumption of the
water pump is half of the original system, and the daily energy saving is
337kWh.
冰水系統變頻控制改善節能效益
Energy-saving benefits from varied chilled water volume
冰水系統變頻控制改善節能效益
Energy-saving benefits from varied chilled water volume
• 系統二次側冰水泵由定頻改成變頻。
• 冰水系統管路末端裝設壓差控制器,提供感測迴授訊號,控制變頻
器藉以調整冰水泵轉速。
• The secondary chilled water pumps of the system is changed from
fixed driving frequency to variable driving frequency.
• A differential pressure controller is installed at the end of the chilled
water system pipeline to provide sensing feedback signals and control
冰水系統變頻控制改善節能效益
Energy-saving benefits from varied chilled water volume
• 加裝二次側冰水系統旁通閥,提供系統平衡調節用。
• 本冰水側節能系統於部分負載時依相似定律,節能潛
力大。
• Install a bypass valve in secondary loop to provide system
balance adjustment.
• Follows the similar law under partial load, the energy-saving
of the system in chilled water loop has great energy-saving
冰水系統變頻控制改善節能效益
Energy-saving benefits from varied chilled water volume
冰水系統變頻冰水泵節能量分析
Energy-saving benefits from varied chilled water volume
由圖可知,量測水側系統實際用電
量與相似定律計算值非常接近。 It
can be seen from the figure that the actual
power consumption measured in the chilled
water loop is very close to the value
calculated by the similarity law.
本系統應用冰水側水泵變頻節能,
於空調部分負載下,節能量
大 。 This system uses the variable
rotating speed pump on the chilled
water loop, and the energy saving is
large under the partial load operation.
冰水泵性能方程式迴歸
Chilled water pump performance regression equation
冰水系統現場量測所得之水泵運
轉數據,經回歸計算求出水泵系統
特 性 方 程 式 。 The water pump
operation data obtained from the on-
site measurement of the chilled water
loop is used to calculate the
characteristic equation of the water
pump system through regression
calculation.
結果顯示平均每月冰水水泵系
統總節能省約 2688kWh 電力,約
可降低 CO2 排放量約 1720ton 。
The results show that the average
monthly chilled water pump system saves
about 2688kWh of electricity and can
reduce CO2 emissions by about 1,720ton.
冰水泵變頻省能量分析
Energy-saving analysis of varied chilled water volume
改善後約可降低耗能
量平均約 18.6% ,節能
量極大。
After the improvement, the
energy consumption can be
reduced by an average of
about 18.6%, which is a huge
amount of energy saving.
冷卻水塔與冷卻水系統節能量分析
Analysis on Energy Saving of Cooling Water Tower and
Cooling Water System
冷卻水塔與冷卻水系統節能改善
Analysis on Energy Saving of Cooling Water Tower and Cooling Water System
冷卻水塔與冷卻水系統節能改善
Analysis on Energy Saving of Cooling Water Tower and Cooling Water System
冷卻水塔與冷卻水系統節能改善
Analysis on Energy Saving of Cooling Water Tower and Cooling Water System
現場量測冷卻水塔運轉數據經數值後,
經數值迴歸,取得冷卻水塔風車性能方程
式 。 After the on-site measurement of the
cooling tower operating data is numerical, the
numerical regression is performed to obtain
the cooling tower windmill performance
equation.
最後將此方程式併入圖控系統,經現場
感測點迴授取得相關參數自動計算後可取
得遂時冷卻水塔之用電量與節能
量。 Finally, this equation is incorporated into
the graphic control system, and the relevant
parameters are automatically calculated by
feedback from on-site sensing points to obtain
the electricity consumption and energy saving
of the cooling water tower.
冷卻水塔風車能量分析
Energy Analysis of Cooling Tower Windmill
分析計算結果顯示冷卻水塔系
統,每月約可節省用電量約
822kWh, 經換算後約可降低 CO2
排 放 量 524ton. Analysis and
calculation results show that the
cooling tower system can save about
822kWh of electricity per month,
and after conversion, it can reduce
CO2 emissions by about 524ton.
改善前後冷卻水塔風車節能約
9.2% 。 The energy saving of the
front and rear cooling tower
windmills is about 9.2%.
冷能回收節能措施效益分析
Benefit analysis of energy-saving measures for
coldness energy recovery
冷能回收節能措施
Energy-saving measures for coldness energy recovery
冷能回收節能措施效益分析
Benefit analysis of energy-saving measures for coldness energy recovery
全熱交換器的改善效益可由全熱交換器出
入口溫濕度求得。
The improved benefit of the energy recovery
ventilator can be obtained from the
temperature and humidity of the inlet and
outlet of the total heat exchanger.
全熱交換器改善效益為 39.4kWh
The improvement benefit of ERV is 39.4kWh
冷能回收節能措施效益分析
Benefit analysis of energy-saving measures for coldness energy recovery
以 2007/8/14 日為例全熱交換器前後的溫濕度數據如下表,全熱
交換器的風量為 1700m³/h ,以一天運轉 10 小時來計算,全熱交
換器的改善效益如下表所示。 Taking 2007/8/14 as an example, the
temperature and humidity data before and after ERV is as follows, the air
volume of the total heat exchanger is 1700m³/h, calculated by operating
for 10 hours a day, the improvement benefits of ERV are shown in the
following table Show.
全熱交換器出入口溫濕度(日平均值) inlet and outlet temperature
and humidity of ERV (daily average)
冷能回收節能措施效益分析
Benefit analysis of energy-saving measures for coldness energy recovery
由實際監測圖可知,加裝
冷能回收設備後,於 22 樓
可回收調節室內空氣品質時
之排氣冷能,每月約可節省
用電量約 390kWh 。
It can be seen from the actual
monitoring map that after the
installation of energy recovery
equipment, the exhaust cooling
energy used to adjust indoor air
quality can be recovered on the
22nd floor, saving about 390kWh
of electricity per month.
外氣引入控制節能措施分析
Analysis of energy-saving measures to control the
introduction of Fresh air
外氣引入時機分析
Analysis of the timing of introduction of fresh air
圖為氣象局氣象資料,為大安區近幾年外
氣溫度與溼度分佈情況。
本外氣系統控制方式應用焓差與 CO2 濃度
連鎖控制,可自動調節合理控制外氣引入量,
並兼顧良好室內空氣品質。
The picture shows the meteorological data
of the Meteorological Bureau, showing the
distribution of outdoor temperature and
humidity in Daan District in recent years.
The fresh air control method uses the chain
control of the ehthalpy difference and the CO2
concentration, which can automatically adjust
and reasonably control the amount of fresh air
introduced, and maintain good indoor air
quality.
外氣引入時機分析
Analysis of the timing of introduction of fresh air
外氣空調使用時機,於每
年 12~3 月為最佳時機,因
此時外氣溫度比室內低,故
引入大量外氣調節,本方法
可降低空調主機耗能。 The
best time to introduce fresh is from
December to March each year.
Therefore, the temperature of the
outdoor air is lower than that of
the indoor air. Therefore, a large
amount of outdoor air conditioning
is introduced. This method can
reduce the energy consumption of
the air conditioner.
外氣引入控制節能措施
External air introduction control and energy-saving measures
外氣引入控制與裝設室內二氧化碳濃度控制。
Fresh air introduction control and indoor carbon
dioxide concentration control.
21F
外氣引入控制節能措施分析
Fresh air introduction control and energy-saving measures
外氣引入控制與裝設室內二氧化碳濃度控制。
External air introduction control and indoor carbon dioxide concentration
control.
21F
外氣引入控制節能措施分析
Fresh air introduction control and energy-saving measures
• 引入新鮮外氣,可維持良好室內空氣側之空氣品質。
• 本大樓應用本外氣空調系統後 CO2 濃度約可控制在 650ppm 以
下。
• 應用本外氣空調系統,引入新鮮外氣,於每年 12~3 月各樓每
月約可節省 700~800kWh 用電量。
• Introducing fresh air can maintain good indoor air quality.
• The CO2 concentration can be controlled below 650ppm after
applying this outdoor air conditioning system in this building.
• The application of this fresh air conditioning system and the
introduction of fresh external air can save about 700~800kWh of
electricity consumption in each building from December to
March each year.
外氣引入控制節能措施分析
Fresh air introduction control and energy-saving measures
• 於秋冬季夜間排氣節能每月約節省 11~29kWh 。
• 而於夏季因建築外殼白天熱獲得較大,故夜間排氣節能量
應會更佳。
• In autumn and winter, the exhaust energy is saved at night
and save about 11~29kWh per month.
• In summer, the heat gain of the building shell during the day
is greater, so the exhaust energy saving at night should be
better.
夜間排氣節能量分析
Analysis on Energy Saving of Exhaust Air at Night
由圖可看出,本大樓於辦公人員下班
後室內熱頷(熱負荷)隨時間經過逐漸
降至平衡。
經量測評估發現,加裝室內外焓差控
制節能系統,控制夜間排氣量可在夜間
直街將熱負荷排至室外。
It can be seen from the figure that the
indoor heat (heat load) of this building
gradually decreases to equilibrium with the
passage of time after the office staff work.
After measurement and evaluation, it is found
that the installation of an energy-saving
system for indoor and outdoor enthalpy
control to control the exhaust volume at night
can discharge the heat load to the outdoors at
night.
夜間排氣節能量分析
Analysis on Energy Saving of Exhaust Air at Night
分析結果指出,室內外熱焓
(熱負荷)差量約
0.3~0.8kJ/kg 。於秋冬季每月
節能量約可節省用電
11~29kWh 。
The analysis result points out
that the enthalpy difference
between indoor and outdoor (heat
load) is about 0.3~0.8kJ/kg. The
monthly energy saving in autumn
and winter can save about
11~29kWh of electricity.
電力系統監控
Power system monitoring
大樓電力系統數據分析
• 電力系統
本期加裝電力監測設備,故只能監測該大樓的用電量。
電力系統的改善效益需由監測設備長期監測,才能有較好
的契約容量。
下圖為改善後( 96.8~9) 與去年( 95.8~9) 的用電比較。
需量監測資料
Demand monitoring data
變頻運轉模式與非變頻運轉用電量分析
Analysis of power consumption in variable frequency operation mode and
non-frequency conversion operation
本工程改善於 2007 年 7 月完
成測試驗收,相關節能設備投
入運轉。
由圖可知系統在未切換手動
前約可降低總建築物用電量
10~15% 。
The improvement of this project was
completed in July 2007, and the
relevant energy-saving equipment was
put into operation. It can be seen from
the figure that the system can reduce
the total building power consumption
by approximately 10-15% before
switching to manual operation.
變頻運轉模式與非變頻運轉用電量分析
Analysis of power consumption in variable frequency operation mode and
non-frequency conversion operation
於 2007 年 11 月初,現場發生
部份設備故障,保養人員即逕行
強制旁通起動水側與空氣側設備,
導致已損毀之馬達因電路突破燒
毀。
At the beginning of November
2007, some equipment failures
occurred at the site, and the
maintenance personnel forcedly
bypassed the starting water side and
air side equipment, causing the
damaged motor to be burned due to
a breakthrough in the circuit.
變頻運轉模式與非變頻運轉用電量分析
Analysis of power consumption in variable frequency operation mode and
non-frequency conversion operation
由 2006~2008 年總用電量比較,
於 2007 年 11 月切換手動後至今,
節能量與前期落差極大,節能量
明顯變小。
Comparing the total electricity
consumption from 2006 to 2008,
after switching to manual operation
in November 2007, the energy saving
has been greatly different from the
previous period, and the energy
saving has been significantly
reduced.
大樓電力系統數據分析
Data analysis of building power system
本工程於 2007 年 7 月啟用,由用電歷史數據證實應用本改善
工程案所提出之節能方法,有極大節能效益。
於控制系統資料庫取得水側與空氣側運轉特性研究分析,顯
示本月水側節能量約 38~49% 之節能效益,空氣側節能量約
25% 。
This project was commissioned in July 2007, and the historical data of
electricity consumption confirmed that the application of the energy-
saving methods proposed in this improvement project has great
energy-saving benefits.
The research and analysis on the operation characteristics of the
water side and the air side obtained from the control system database
showed that the energy saving on the water side this month was
about 38~49%, and the energy saving on the air side was about 25%.
大樓電力系統數據分析
Data analysis of building power system
於 2007 年 11 月直接旁通至手動控制(非自動控制)模式,
至今節能量與前期落差極大,節能量明顯變小。
In November 2007, it was directly bypassed to manual
control (non-automatic control) mode. So far, the energy
saving has been greatly different from the previous period,
and the energy saving has been significantly reduced.