Professional Documents
Culture Documents
Submitted by – Guided by –
• Hospitals maintain high ventilation rates to lessen the risk of microbial contamination. Because requirements for
outdoor air are substantial. HVAC account for nearly half of a hospital’s total energy use.
• By optimizing the HVAC performance Hospitals can achieve substantial energy savings and meet the demands of
infection control.
• The main way that ventilation systems can be tweaked to improve operational efficiency is by optimizing the
design and outdoor air demand controls along with reducing pressure losses for individual components.
• The hospital study also looks into the extent to which heat recovery systems can be used in hospital ventilation
systems.
Research Questions:
• What are the energy savings potential of ventilation systems in hospitals?
• What are the strategies to maximize ventilation system output in Hospitals?
• What are the main parameters affect large energy consumption in the hospital ventilation
systems and how to minimize it ?
• How to optimize ventilation systems with specific requirements?
5 6 Why?
Air filtration often accounts for a lot of the overall pressure loss in a ventilation system. The greater
hygiene requirements in hospitals make the situation even more difficult because the filters required
3 often have two or three stages.
2 4 1 As the filters capture more and more dirt, the pressure drop increases.
If the filters are allowed to accumulate dirt, the pressure drop starts affecting the fan efficiency, and
Zone the filters may even start to collapse.
How to achieve this?
The filter area could be made larger to reduce pressure loses –
Temperature sensors This could be done in 2 ways –
Controller 1. Make the filter outlet area larger
2. Make the filter deeper.
1. The fan control system turns on when the fan is energized. This maybe a clock signal or a high
temperature space condition.
2. The OA temperature sensor supplies a signal to the damper controller. Or alternatively, the Maintaining a continuous positive pressure -
mixed air low or high temperature controller controls the outside air dampers to avoid excessive
high temperature air from entering the coils. Why?
3. The space temperature signal determines if the space is above or below the setpoint. If above, Positive pressure ensures a protective environment for the patient.
the economizer feature will be activated to control the outdoor and mixed air dampers. If below, The air should flow from within the ICU to the outside of the room during all the times.
the OA damper is set to a minimum position.
4. The mixed air controller controls both sets of dampers (OA and RA) to provide the desired mixed
air temperature. How to achieve this?
5. If the outdoor air temperature rises above the cut-off point for economiser operation, it’s
damper is returned to its minimum position. Differential Pressure indication device should be installed to permit air pressure readings
6. The return air damper is then opened up to a max. in the rooms and provide an alarm in case of a fan failure.
7. The discharge air controller controls the heating coil valve, outdoor air damper, exhaust air
damper, return air damper and cooling coil valve after economiser upper limit is reached. Ensuring air tightness by Well sealed rooms and openings.
Pressure control is maintained by modulating the main supply and exhaust dampers
based on a signal from a pressure transducer located inside the ICU room.